ANSI/TIA-568

Last updated

ANSI/TIA-568 is a technical standard for commercial building cabling for telecommunications products and services. The title of the standard is Commercial Building Telecommunications Cabling Standard and is published by the Telecommunications Industry Association (TIA), a body accredited by the American National Standards Institute (ANSI).

Contents

As of 2020, the revision status of the standard is ANSI/TIA-568-D, published 2015, which replaced TIA/EIA-568-C of 2009, revision B of 2001, and revision A of 1995, and the initial issue of 1991, which are now obsolete. [1] [2]

Perhaps the best-known features of ANSI/TIA-568 are the pin and pair assignments for eight-conductor 100-ohm balanced twisted pair cabling. These assignments are named T568A and T568B.

History

ANSI/TIA-568 was developed through the efforts of more than 60 contributing organizations including manufacturers, end-users, and consultants. Work on the standard began with the Electronic Industries Alliance (EIA), to define standards for telecommunications cabling systems. EIA agreed to develop a set of standards, and formed the TR-42 committee, [3] with nine subcommittees to perform the work. The work continues to be maintained by TR-42 within the TIA. EIA no longer exists, hence EIA has been removed from the name.

The first version of the standard, TIA/EIA-568, was released in 1991. The standard was updated to revision A in 1995. The demands placed upon commercial wiring systems increased dramatically over this period due to the adoption of personal computers and data communication networks and advances in those technologies. The development of high-performance twisted pair cabling and the popularization of fiber optic cables also drove significant change in the standards. These changes were first released in a revision C in 2009 which has subsequently been replaced by revision D (named ANSI/TIA-568-D). [4]

Goals

ANSI/TIA-568 defines structured cabling system standards for commercial buildings, and between buildings in campus environments. The bulk of the standards define cabling types, distances, connectors, cable system architectures, cable termination standards and performance characteristics, cable installation requirements and methods of testing installed cable. The main standard, ANSI/TIA-568.0-D defines general requirements, while ANSI/TIA-568-C.2 focuses on components of balanced twisted-pair cable systems. ANSI/TIA-568.3-D addresses components of fiber optic cable systems, and ANSI/TIA-568-C.4, addressed coaxial cabling components. [5]

The intent of these standards is to provide recommended practices for the design and installation of cabling systems that will support a wide variety of existing and future services. Developers hope the standards will provide a lifespan for commercial cabling systems in excess of ten years. This effort has been largely successful, as evidenced by the definition of Category 5 cabling in 1991,[ citation needed ] a cabling standard that (mostly) satisfied cabling requirements for 1000BASE-T, released in 1999. Thus, the standardization process can reasonably be said to have provided at least a nine-year lifespan for premises cabling, and arguably a longer one.

All these documents accompany related standards that define commercial pathways and spaces (TIA-569-C-1, February 2013), residential cabling (ANSI/TIA-570-C, August 2012), administration standards (ANSI/TIA-606-B, December 2015), grounding and bonding (TIA-607-C, November 2015), and outside plant cabling (TIA-758-B, April 2012).

Cable categories

The standard defines categories of shielded and unshielded twisted pair cable systems, with different levels of performance in signal bandwidth, insertion loss, and cross-talk. Generally increasing category numbers correspond with a cable system suitable for higher rates of data transmission. Category 3 cable was suitable for telephone circuits and data rates up to 16 million bits per second. Category 5 cable, with more restrictions on attenuation and cross talk, has a bandwidth of 100 MHz. [6] The 1995 edition of the standard defined Categories 3, 4, and 5. Categories 1 and 2 were excluded from the standard since these categories were only used for voice circuits, not for data. [7] The current revision includes Category 5e (100 MHz), 6 (250 MHz), 6A (500 MHz), and 8 (2,000 MHz). Categories 7 and 7A were not officially recognized by TIA and were generally only used outside the United States. Category 8 was published with ANSI/TIA‑568‑C.2‑1 (June 2016) [8] to meet the performance specification intended by Category 7.

Structured cable system topologies

ANSI/TIA-568-D defines a hierarchical cable system architecture, in which a main cross-connect (MCC) is connected via a star topology across backbone cabling to intermediate cross-connects (ICCs) and horizontal cross-connects (HCCs). Telecommunications design traditions utilized a similar topology. Many people refer to cross-connects by their telecommunications names: distribution frames (with the various hierarchies called main distribution frames (MDFs), intermediate distribution frames (IDFs) and wiring closets). Backbone cabling is also used to interconnect entrance facilities (such as telco demarcation points) to the main cross-connect.

Horizontal cross-connects provide a point for the consolidation of all horizontal cabling, which extends in a star topology to individual work areas such as cubicles and offices. Under TIA/EIA-568-B, maximum allowable horizontal cable distance is 90 meters of installed twisted-pair cabling, with 100 meters of maximum total length including patch cords. No patch cord should be longer than 5 meters. Optional consolidation points are allowable in horizontal cables, often appropriate for open-plan office layouts where consolidation points or media converters may connect cables to several desks or via partitions.

At the work area, equipment is connected by patch cords to horizontal cabling terminated at jack points.

TIA/EIA-568 also defines characteristics and cabling requirements for entrance facilities, equipment rooms and telecommunications rooms.

T568A and T568B termination

Perhaps the most comprehensive known and most discussed feature of ANSI/TIA-568 is the definition of the pin-to-pair assignments, or pinout, between the pins in a connector (a plug or a socket) and the wires in a cable. Pinouts are critical because cables do not function if the pinouts at their two ends aren't correctly matched.

The standard specifies how to connect eight-conductor 100-ohm balanced twisted-pair cabling, such as Category 5 cable, to 8P8C modular connectors (often referred to as RJ45 connectors). The standard defines two alternative pinouts: T568A and T568B.

ANSI/TIA-568 recommends the T568A pinout for horizontal cables. This pinout is compatible with the 1-pair and 2-pair Universal Service Order Codes (USOC) pinouts. The U.S. Government requires it in federal contracts. [ citation needed ] The standard also allows, only in certain circumstances, the T568B pinout "if necessary to accommodate certain 8-pin cabling systems", i.e. when, and only when, adding to an existing installation that used the T568B wiring pattern before it was defined, being those that pre-dated ANSI/TIA-568 and used the previous AT&T 258A (Systimax) standard. In the 1990s, when the original TIA/EIA-568 was published, the most widely installed wiring pattern in UTP cabling infrastructure was that of AT&T 258A (Systimax), hence the inclusion of the same wiring pattern (as T568B) as a secondary option for use in such installations. Many organizations still use T568B out of inertia.

The colors of the wire pairs in the cable, in order, are blue (for pair 1), orange, green, and brown (for pair 4). Each pair consists of one conductor of solid color and a second conductor, which is white with a stripe of the other color. The difference between the T568A and T568B pinouts is that the orange and green wire pairs are exchanged.

Wiring

See modular connector for numbering of the pins. [9]

PinT568A pairT568B pair10BASE-T / 100BASE-TX [10] 1000BASE-T signal ID [11] WireT568A colorT568B colorPins on plug face
132TX+DA+tip Wire white green stripe.svg
white/green stripe
Wire white orange stripe.svg
white/orange stripe
Rj45plug-8p8c.png

The pin numbering on the plug. Connected pins on the plug and jack have the same number.

2TX−DA−ring Wire green.svg
green solid
Wire orange.svg
orange solid
323RX+DB+tip Wire white orange stripe.svg
white/orange stripe
Wire white green stripe.svg
white/green stripe
41not usedDC+ring Wire blue.svg
blue solid
5not usedDC−tip Wire white blue stripe.svg
white/blue stripe
623RX−DB−ring Wire orange.svg
orange solid
Wire green.svg
green solid
74not usedDD+tip Wire white brown stripe.svg
white/brown stripe
8not usedDD−ring Wire brown.svg
brown solid
Some 8P8C wall sockets indicate T568A and T568B termination schemes internally. Commercial RJ45 wall socket internals.jpg
Some 8P8C wall sockets indicate T568A and T568B termination schemes internally.

The only difference between T568A and T568B is that pairs 2 and 3 (orange and green, respectively) are swapped. Both configurations wire the pins "straight through," i.e., pins 1 through 8 on one end are connected to pins 1 through 8 on the other end. [12] Also, the same sets of pins connect to the opposite ends that are paired in both configurations: pins 1 and 2 form a pair, as do 3 and 6, 4 and 5, and 7 and 8. One can use cables wired according to either configuration in the same installation without significant problems if the connections are the same on both ends.

A cable terminated according to T568A on one end and T568B on the other is a crossover cable when used with the earlier twisted-pair Ethernet standards that use only two of the pairs because the pairs used happen to be pairs 2 and 3, the same pairs on which T568A and T568B differ. Crossover cables are occasionally needed for 10BASE-T and 100BASE-TX Ethernet.

Swapping two wires between different pairs causes crosstalk, defeating one of the purposes of twisting wires in pairs. [13]

Use for T1 connectivity

In Digital Signal 1 (T1) service, pairs 1 and 3 (T568A) are used, and the USOC-8 jack is wired according to the RJ-48C specification. The termination jack is often wired according to the RJ-48X specification, providing a transmit-to-receive loopback when the plug is withdrawn.

Vendor cables are often wired with tip and ring reversed—i.e., pins 1 and 2 or 4 and 5 reversed. This does not affect the quality of the T1 signal, which is fully differential and uses the alternate mark inversion (AMI) signaling scheme.

Backward compatibility

Because pair 1 connects to the center pins (4 and 5) of the 8P8C connector in both T568A and T568B, both standards are compatible with the first line of RJ11, RJ14, RJ25, and RJ61 connectors that all have the first pair in the center pins of these connectors.

If the second line of an RJ14, RJ25, or RJ61 plug is used, it connects to pair 2 (orange/white) of jacks wired to T568A but to pair 3 (green/white) in jacks wired to T568B. This makes T568B potentially confusing in telephone applications.

Because of different pin pairings, the RJ25 and RJ61 plugs cannot pick up lines 3 or 4 from T568A or T568B without splitting pairs. This would most likely result in unacceptable levels of hum, crosstalk, and noise.

Theory

The original idea in wiring modular connectors, as seen in the registered jacks, was that the first pair would go in the center positions, the next pair on the next-innermost ones, and so on. Also, signal shielding would be optimized by alternating the live and earthy pins of each pair. The terminations diverge slightly from this concept because, on the eight-position connector, the resulting arrangement of conductors would separate the outermost pair, impairing balanced line performance too much to meet the electrical requirements of high-speed LAN protocols.

Standards

See also

Related Research Articles

<span class="mw-page-title-main">RS-232</span> Standard for serial communication

In telecommunications, RS-232 or Recommended Standard 232 is a standard originally introduced in 1960 for serial communication transmission of data. It formally defines signals connecting between a DTE such as a computer terminal or PC, and a DCE, such as a modem. The standard defines the electrical characteristics and timing of signals, the meaning of signals, and the physical size and pinout of connectors. The current version of the standard is TIA-232-F Interface Between Data Terminal Equipment and Data Circuit-Terminating Equipment Employing Serial Binary Data Interchange, issued in 1997. The RS-232 standard had been commonly used in computer serial ports and is still widely used in industrial communication devices.

<span class="mw-page-title-main">Ethernet over twisted pair</span> Ethernet physical layers using twisted-pair cables

Ethernet over twisted-pair technologies use twisted-pair cables for the physical layer of an Ethernet computer network. They are a subset of all Ethernet physical layers.

<span class="mw-page-title-main">Category 5 cable</span> Unshielded twisted pair communications cable

Category 5 cable (Cat 5) is a twisted pair cable for computer networks. Since 2001, the variant commonly in use is the Category 5e specification (Cat 5e). The cable standard provides performance of up to 100 MHz and is suitable for most varieties of Ethernet over twisted pair up to 2.5GBASE-T but more commonly runs at 1000BASE-T speeds. Cat 5 is also used to carry other signals such as telephone and video.

<span class="mw-page-title-main">Fast Ethernet</span> Ethernet standards that carry data at the nominal rate of 100 Mbit/s

In computer networking, Fast Ethernet physical layers carry traffic at the nominal rate of 100 Mbit/s. The prior Ethernet speed was 10 Mbit/s. Of the Fast Ethernet physical layers, 100BASE-TX is by far the most common.

<span class="mw-page-title-main">Gigabit Ethernet</span> Standard for Ethernet networking at a data rate of 1 gigabit per second

In computer networking, Gigabit Ethernet is the term applied to transmitting Ethernet frames at a rate of a gigabit per second. The most popular variant, 1000BASE-T, is defined by the IEEE 802.3ab standard. It came into use in 1999, and has replaced Fast Ethernet in wired local networks due to its considerable speed improvement over Fast Ethernet, as well as its use of cables and equipment that are widely available, economical, and similar to previous standards. The first standard for faster 10 Gigabit Ethernet was approved in 2002.

Category 3 cable, commonly known as Cat 3 or station wire, and less commonly known as VG or voice-grade, is an unshielded twisted pair (UTP) cable used in telephone wiring. It is part of a family of standards defined jointly by the Electronic Industries Alliance (EIA) and the Telecommunications Industry Association (TIA) and published in TIA/EIA-568-B.

StarLAN was the first IEEE 802.3 standard for Ethernet over twisted pair wiring. It was standardized by the IEEE Standards Association as 802.3e in 1986, as the 1BASE5 version of Ethernet. The StarLAN Task Force was chaired by Bob Galin.

<span class="mw-page-title-main">Registered jack</span> Telecommunication network interface

A registered jack (RJ) is a standardized telecommunication network interface for connecting voice and data equipment to a service provided by a local exchange carrier or long distance carrier. Registered interfaces were first defined in the Universal Service Ordering Code (USOC) system of the Bell System in the United States for complying with the registration program for customer-supplied telephone equipment mandated by the Federal Communications Commission (FCC) in the 1970s. They were subsequently codified in title 47 of the Code of Federal Regulations Part 68. Registered jack connections began to see use after their invention in 1973 by Bell Labs. The specification includes physical construction, wiring, and signal semantics. Accordingly, registered jacks are primarily named by the letters RJ, followed by two digits that express the type. Additional letter suffixes indicate minor variations. For example, RJ11, RJ14, and RJ25 are the most commonly used interfaces for telephone connections for one-, two-, and three-line service, respectively. Although these standards are legal definitions in the United States, some interfaces are used worldwide.

<span class="mw-page-title-main">RS-422</span> Standard for serial communication

RS-422, also known as TIA/EIA-422, is a technical standard originated by the Electronic Industries Alliance, first issued in 1975, that specifies electrical characteristics of a digital signaling circuit. It was meant to be the foundation of a suite of standards that would replace the older RS-232C standard with standards that offered much higher speed, better immunity from noise, and longer cable lengths. RS-422 systems can transmit data at rates as high as 10 Mbit/s, or may be sent on cables as long as 1,200 meters (3,900 ft) at lower rates. It is closely related to RS-423, which uses the same signaling systems but on a different wiring arrangement.

<span class="mw-page-title-main">Crossover cable</span> Cable with intentionally crossed wiring

A crossover cable connects two devices of the same type, for example DTE-DTE or DCE-DCE, usually connected asymmetrically (DTE-DCE), by a modified cable called a crosslink. Such a distinction between devices was introduced by IBM.

<span class="mw-page-title-main">Pinout</span>

In electronics, a pinout is a cross-reference between the contacts, or pins, of an electrical connector or electronic component, and their functions. "Pinout" now supersedes the term "basing diagram" which was the standard terminology used by the manufacturers of vacuum tubes and the RMA. The RMA started its standardization in 1934, collecting and correlating tube data for registration at what was to become the EIA. The EIA now has many sectors reporting to it and sets what is known as EIA standards where all registered pinouts and registered jacks can be found.

RS-485, also known as TIA-485(-A) or EIA-485, is a standard, originally introduced in 1983, defining the electrical characteristics of drivers and receivers for use in serial communications systems. Electrical signaling is balanced, and multipoint systems are supported. The standard is jointly published by the Telecommunications Industry Association and Electronic Industries Alliance (TIA/EIA). Digital communications networks implementing the standard can be used effectively over long distances and in electrically noisy environments. Multiple receivers may be connected to such a network in a linear, multidrop bus. These characteristics make RS-485 useful in industrial control systems and similar applications.

<span class="mw-page-title-main">Structured cabling</span> Telecommunications cabling infrastructure

In telecommunications, structured cabling is building or campus cabling infrastructure that consists of a number of standardized smaller elements called subsystems. Structured cabling components include twisted pair and optical cabling, patch panels and patch cables.

<span class="mw-page-title-main">Category 6 cable</span> Standardized data communications cable

Category 6 cable (Cat 6) is a standardized twisted pair cable for Ethernet and other network physical layers that is backward compatible with the Category 5/5e and Category 3 cable standards.

<span class="mw-page-title-main">EIA-530</span> Balanced serial interface

Currently known as TIA-530-A, but often called EIA-530, or RS-530, is a balanced serial interface standard that generally uses a 25-pin connector, originally created by the Telecommunications Industry Association.

An Ethernet crossover cable is a crossover cable for Ethernet used to connect computing devices together directly. It is most often used to connect two devices of the same type, e.g. two computers or two switches to each other. By contrast, straight through patch cables are used to connect devices of different types, such as a computer to a network switch.

International standard ISO/IEC 11801Information technology — Generic cabling for customer premises specifies general-purpose telecommunication cabling systems that are suitable for a wide range of applications. It is published by ISO/IEC JTC 1/SC 25/WG 3 of the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC). It covers both balanced copper cabling and optical fibre cabling.

<span class="mw-page-title-main">Modular connector</span> Electrical connector commonly used in telephone and computer networks

A modular connector is a type of electrical connector for cords and cables of electronic devices and appliances, such as in computer networking, telecommunication equipment, and audio headsets.

In copper twisted pair wire networks, copper cable certification is achieved through a thorough series of tests in accordance with Telecommunications Industry Association (TIA) or International Organization for Standardization (ISO) standards. These tests are done using a certification-testing tool, which provide pass or fail information. While certification can be performed by the owner of the network, certification is primarily done by datacom contractors. It is this certification that allows the contractors to warranty their work.

References

  1. Andrew Oliviero, Bill Woodward "Cabling: The Complete Guide to Copper and Fiber-Optic Networking", John Wiley & Sons, 2009, ISBN   0470550058 page 68
  2. "Standards and Technology Annual Report" (PDF). TIA. Archived from the original (PDF) on 2016-03-03. Retrieved 2014-04-14.
  3. "TR-42 - Telecommunications Cabling Systems". TIA. Archived from the original on 2014-04-10. Retrieved 2014-04-14.
  4. "TIA-568 Set : Commercial Building Telecommunications Cabling Standards Set".
  5. "TIA Publishes New Cabling Standards Designed to Improve Efficiency for Designers, Installers and End Users". TIA. 2009-03-12. Archived from the original on 2011-08-17.
  6. William Stallings Knowing UTP wiring basics can boost local net performance, Network World 9 July 1996, page 29
  7. Charles E. Spurgeon, Ethernet:The Definitive Guide, (O'Reilly Media, Inc., 2000) ISBN   1565926609 page 212
  8. "Category 8 Questions |". 10 June 2015.
  9. "Connector Pin Assignments". Cisco. Retrieved 2014-04-14.
  10. IEEE 802.3 Table 25-2
  11. IEEE 802.3 Table 40-12
  12. "RJ45 Pinout".
  13. "LAN Wiring & Pinouts".

Sources