Close Coupled Cooling

Last updated

Close Coupled Cooling is a last generation cooling system particularly used in data centers. The goal of close coupled cooling is to bring heat transfer closest to its source: the equipment rack. By moving the air conditioner closer to the equipment rack a more precise delivery of inlet air and a more immediate capture of exhaust air is ensured.

Contents

The proximity of the cooling system with the server cabinet allows a high-performance solution The proximity of the cooling system with the server cabinet allows a high-performance solution.jpg
The proximity of the cooling system with the server cabinet allows a high-performance solution

Air Conditioner Types

Commercially available close coupled solutions can be divided into two categories: Open-Loop and Closed-Loop.

Open-Loop Configuration

Open-Loop configurations are not totally independent from the room they are installed, and air flows interact with the ambient room environment.

In-Row Air Conditioners

Row-Based Air Conditioning units are installed inside the rack rows. Air flows generally follow short and linear paths, reducing, in this way, the necessary power needed to start up the fans and increasing the energy efficiency.

A Row-Based cooling solution offers one advantage with respect to the Room-Based solution, since the former one can be better adapted to the needs of cooling for specific rows; it is anyway appropriate not to locate the conditioning units at the beginning or at the end of the rows to maximise their performance.

Rear Door Heat Exchangers

This type of solution is based on the substitution of the rear door of an existing rack.

These heat exchangers leverage the front-to-back air dissipation of most of the IT equipments: the servers dissipate warm air, which passes the heat exchanger coil and is returned to the room at an agreeable temperature.

The cooling units of this category do not occupy additional space, so they are particularly indicated either to cool all the spaces originally designed as data centers, or to integrate an already existing cooling system.

Overhead Heat Exchangers

Generally, a heat exchanger of this type discharges air from the ceiling into the cold aisle whereas the exhaust air rises into the vents in the ceiling; in Close Coupled system cases, the units are positioned directly above the servers, making the cold air delivery and hot air return much more precise.

A system of this type, being positioned vertically, does not need further floor space in the room.

Closed-Loop Configuration

The Closed-Loop cooling typologies act independently from the room they are installed; the rack and the heat exchanger work exclusively with one another, creating an internal microclimate.

In Rack Cooling

The cooling system is adjoint to the server rack and both of them are completely sealed; the solid doors on the enclosure and In-Row Air Conditioners contain the air flow, directing cold air to the server inlet and exhaust air, by using fans, through the cooling coil.

The Close-Loop design allows a very focused cooling at rack level and it is possible to install very dense equipment disregarding the ambient environment, giving flexibility to use unconventional spaces to install the IT equipment.

Efficiency

In the traditional layout, the fans must move air from the perimeter of the room, under the raised floor, and through a perforated floor tile into servers intake. This process requires energy, that varies depending on the typology of the structure. Often, under the raised floor, holdbacks (large cable bundles, conduits) exist, requiring additional fan energy to move the required cold air volume.

Being that in Close Coupled solutions the cooling system and the equipment rack are close to one another, the energy needed is reduced. With an In-Row typology the cooling unit is incorporated in the row of racks and, providing air directly to the row, there are not impediments to consider under the floor. It is estimated, that when integrated, a Close Coupled system can guarantee up to 95% of annual energy reduction compared to a traditional CRAC system of equal cooling capacity.

Some cooling typologies can be associated to fans with variable velocity that adapt in better ways to the workload, so also to the internal temperature of the rack. Having fans that work at the minimum velocity satisfying the requirements of the Data Center is very important for energy consumption.

It is verified that the percentage of energy saved, hence the total energy cost decreases in a more than proportional way with respect to the decrease of air flow (for example, by reducing the fan velocity by 10% we save 27% of energy).

% FLOWHOURSANNUAL ENERGYANNUAL COSTRPMSAVINGS
100876049.774,431.742,1020400%
95876042.774,641.493,64193814.26%
90876036.285,561.269,99183627.10%
85876030.567,721.069,87173438.59%
80876025.484,51891,96163248.80%
75876020.998,59734,95153057.81%
70876017.072,63697,01142859.99%

Efficiency is also represented by modularity. With a Close Coupled solution in is indeed possible adding new conditioners in forecast of an increase of the Data Centre capacity.

Despite the fact that some past studies have speculated a very elevated growth of sales of Close Coupled solutions, more recent studies have instead shown a more contained growth. The reason seems to be due to the fact that the In-Row solutions offer significant energy savings as the rack densities are close to the 8-10 kW threshold; today's average densities for medium-sized data centers are instead about 5 kW and energy savings do not fully justify the higher cost of investment for the cooling system.

Refrigerated Water Temperatures

In traditional systems, the refrigerated water supply temperatures typically vary between 6 and 7 °C and cold water is in fact necessary to generate cold air that compensates for the rise that occurs on the floor of the data center, since the cold inlet air and the hot exhaust air interact. However, it is necessary to ensure that the inlet temperature is between 18 and 26.5 °C as established by the ASHRAE.

Some types of Close Coupled systems allow warmer water inlet temperatures due to the proximity of the refrigeration system and the design of the cooling coil while remaining within the guidelines of the ASHRAE.

Since the refrigerators represent 30-40% of the energy consumption of a data center and that this is largely due to mechanical refrigeration, a higher water inlet temperature allows increase the hours in which free cooling is possible and therefore increase the efficiency of the refrigerator.

Close Coupled system of Google Data Centers

Google Data Center - Photo: Connie Zhou Data google 1.jpg
Google Data Center - Photo: Connie Zhou

For several years now, Google, according to the statements of the vice president of Data Centers, Joseph Kava, restructures the cooling system of its Data Centers every 12 – 18 months, also focusing on Close Coupled type systems.

In 2012 Google published a photo gallery that shows the design of its cooling system, followed by an explanation of Data Center Vice President Joseph Kava, of how it works.

In the data center shown the rooms serve as cold corridors, there is a raised floor but there are no perforated tiles. Cooling occurs in closed corridors with rows of racks on both sides while cooling coils using cold water serve as the ceiling of these warm corridors, which also house the pipes that carry the water to and from the cooling towers housed in another part of the building.

The temperature of the air is generally maintained around 26.5 °C, getting warmer more and more due to the contact with various components, up to about 49 °C. When air is directed by fans in the warm closed corridor where, reaching the top of the room passes through the cooling coil and is cooled to room temperature. The flexible piping connects to the cooling coil at the top of the hot aisle and descends through an opening in the floor and flows under the raised floor.

From the statements of Kava "If we had leaks in the conduits, the water would sink down into our raised floor. We have a lot of experience with this design, and it has never happened a large water loss" , the presence of an emergency system for any water leaks is confirmed. It is also confirmed that the proximity of liquids to the servers is not considered problematic.

Kava also stated, referring to other types of cooling systems with installations on the ceiling to return the hot exhaust air to the air conditioners of the computer room (CRAC) located along the perimeter of the raised floor area, that The whole system is inefficient because the hot air is moved over a long distance while traveling towards the "CRAC", while a Close Coupled system is significantly more efficient.

Bibliography

Notes

Related Research Articles

A colocation center or "carrier hotel", is a type of data centre where equipment, space, and bandwidth are available for rental to retail customers. Colocation facilities provide space, power, cooling, and physical security for the server, storage, and networking equipment of other firms and also connect them to a variety of telecommunications and network service providers with a minimum of cost and complexity.

<span class="mw-page-title-main">Heating, ventilation, and air conditioning</span> Technology of indoor and vehicular environmental comfort

Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.

<span class="mw-page-title-main">Dehumidifier</span> Device which reduces humidity

A dehumidifier is an air conditioning device which reduces and maintains the level of humidity in the air. This is done usually for health or thermal comfort reasons, or to eliminate musty odor and to prevent the growth of mildew by extracting water from the air. It can be used for household, commercial, or industrial applications. Large dehumidifiers are used in commercial buildings such as indoor ice rinks and swimming pools, as well as manufacturing plants or storage warehouses. Typical air conditioning systems combine dehumidification with cooling, by operating cooling coils below the dewpoint and draining away the water that condenses.

<span class="mw-page-title-main">Data center</span> Building or room used to house computer servers and related equipment

A data center or data centre is a building, a dedicated space within a building, or a group of buildings used to house computer systems and associated components, such as telecommunications and storage systems.

<span class="mw-page-title-main">Air handler</span> Device used to regulate and circulate air as part of an HVAC system

An air handler, or air handling unit, is a device used to regulate and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. An air handler is usually a large metal box containing a blower, furnace or A/C elements, filter racks or chambers, sound attenuators, and dampers. Air handlers usually connect to a ductwork ventilation system that distributes the conditioned air through the building and returns it to the AHU, sometimes exhausting air to the atmosphere and bringing in fresh air. Sometimes AHUs discharge (supply) and admit (return) air directly to and from the space served without ductwork

<span class="mw-page-title-main">Variable air volume</span> Heating or air-conditioning system

Variable air volume (VAV) is a type of heating, ventilating, and/or air-conditioning (HVAC) system. Unlike constant air volume (CAV) systems, which supply a constant airflow at a variable temperature, VAV systems vary the airflow at a constant or varying temperature. The advantages of VAV systems over constant-volume systems include more precise temperature control, reduced compressor wear, lower energy consumption by system fans, less fan noise, and additional passive dehumidification.

<span class="mw-page-title-main">Underfloor heating</span> Form of central heating and cooling

Underfloor heating and cooling is a form of central heating and cooling that achieves indoor climate control for thermal comfort using hydronic or electrical heating elements embedded in a floor. Heating is achieved by conduction, radiation and convection. Use of underfloor heating dates back to the Neoglacial and Neolithic periods.

<span class="mw-page-title-main">Passive ventilation</span> Ventilation without use of mechanical systems

Passive ventilation is the process of supplying air to and removing air from an indoor space without using mechanical systems. It refers to the flow of external air to an indoor space as a result of pressure differences arising from natural forces.

Room air distribution is characterizing how air is introduced to, flows through, and is removed from spaces. HVAC airflow in spaces generally can be classified by two different types: mixing and displacement.

A chilled beam is a type of radiation/convection HVAC system designed to heat and cool large buildings through the use of water. This method removes most of the zone sensible local heat gains and allows the flow rate of pre-conditioned air from the air handling unit to be reduced, lowering by 60% to 80% the ducted design airflow rate and the equipment capacity requirements. There are two types of chilled beams, a Passive Chilled Beam (PCB) and an Active Chilled Beam (ACB). They both consist of pipes of water (fin-and-tube) that pass through a heat exchanger contained in a case suspended from, or recessed in, the ceiling. As the beam cools the air around it, the air becomes denser and falls to the floor. It is replaced by warmer air moving up from below, causing a constant passive air movement called convection, to cool the room. The active beam consists of air duct connections, induction nozzles, hydronic heat transfer coils, supply outlets and induced air inlets. It contains an integral air supply that passes through nozzles, and induces air from the room to the cooling coil. For this reason, it has a better cooling capacity than the passive beam. Instead, the passive beam provides space cooling without the use of a fan and it is mainly done by convection. Passive beams can be either exposed or recessed. The passive approach can provide higher thermal comfort levels, while the active approach uses the momentum of ventilation air that enters at relatively high velocity to induce the circulation of room air through the unit. A chilled beam is similar in appearance to a VRF unit.

<span class="mw-page-title-main">Server room</span> Room containing computer servers

A server room is a room, usually air-conditioned, devoted to the continuous operation of computer servers. An entire building or station devoted to this purpose is a data center.

<span class="mw-page-title-main">Fan coil unit</span> HVAC device

A fan coil unit (FCU), also known as a Vertical Fan Coil-Unit (VFC), is a device consisting of a heat exchanger (coil) and a fan. FCUs are commonly used in HVAC systems of residential, commercial, and industrial buildings that use ducted split air conditioning or with central plant cooling. FCUs are typically connected to ductwork and a thermostat to regulate the temperature of one or more spaces and to assist the main air handling unit for each space if used with chillers. The thermostat controls the fan speed and/or the flow of water or refrigerant to the heat exchanger using a control valve.

Liebert Corporation, a business of Vertiv, is a global manufacturer of power, precision cooling and infrastructure management systems for mainframe computer, server racks, and critical process systems. Liebert is headquartered in Westerville, Ohio, and employs more than 1,800 people across 12 manufacturing plants worldwide.

Free cooling is an economical method of using low external air temperatures to assist in chilling water, which can then be used for industrial processes, or air conditioning systems. The chilled water can either be used immediately or be stored for the short- or long-term. When outdoor temperatures are lower relative to indoor temperatures, this system utilizes the cool outdoor air as a free cooling source. In this manner, the system replaces the chiller in traditional air conditioning systems while achieving the same cooling result. Such systems can be made for single buildings or district cooling networks.

HVAC is a major sub discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary.

<span class="mw-page-title-main">Thermal destratification</span> Method of stirring a confined fluid to achieve equal temperatures

Thermal destratification is the process of mixing the internal air in a building to eliminate stratified layers and achieve temperature equalization throughout the building envelope.

Automatic balancing valves are utilised in central heating and cooling systems that rely on flow of water through the system. They use the latest flow technology to ensure that the design flow rate is achieved at all times irrespective of any pressure changes within the system.

<span class="mw-page-title-main">Underfloor air distribution</span>

Underfloor air distribution (UFAD) is an air distribution strategy for providing ventilation and space conditioning in buildings as part of the design of a HVAC system. UFAD systems use an underfloor supply plenum located between the structural concrete slab and a raised floor system to supply conditioned air to supply outlets, located at or near floor level within the occupied space. Air returns from the room at ceiling level or the maximum allowable height above the occupied zone.

<span class="mw-page-title-main">Radiant heating and cooling</span> Category of HVAC technologies

Radiant heating and cooling is a category of HVAC technologies that exchange heat by both convection and radiation with the environments they are designed to heat or cool. There are many subcategories of radiant heating and cooling, including: "radiant ceiling panels", "embedded surface systems", "thermally active building systems", and infrared heaters. According to some definitions, a technology is only included in this category if radiation comprises more than 50% of its heat exchange with the environment; therefore technologies such as radiators and chilled beams are usually not considered radiant heating or cooling. Within this category, it is practical to distinguish between high temperature radiant heating, and radiant heating or cooling with more moderate source temperatures. This article mainly addresses radiant heating and cooling with moderate source temperatures, used to heat or cool indoor environments. Moderate temperature radiant heating and cooling is usually composed of relatively large surfaces that are internally heated or cooled using hydronic or electrical sources. For high temperature indoor or outdoor radiant heating, see: Infrared heater. For snow melt applications see: Snowmelt system.

Temperature chaining can mean temperature, thermal or energy chaining or cascading.