An outage management system (OMS) is a computer system used by operators of electric distribution systems to assist in restoration of power.
Major functions usually found in an OMS include:
At the core of a modern outage management system is a detailed network model of the distribution system. The utility's geographic information system (GIS) is usually the source of this network model. By combining the locations of outage calls from customers, a rules engine is used to predict the locations of outages. For instance, since the distribution system is primarily tree-like or radial in design, all calls in particular area downstream of a fuse could be inferred to be caused by a single fuse or circuit breaker upstream of the calls.
The outage calls are usually taken by call takers in a call center utilizing a customer information system (CIS). Another common way for outage calls to enter into the CIS (and thus the OMS) is by integration with an interactive voice response (IVR) system. The CIS is also the source for all the customer records which are linked to the network model. Customers are typically linked to the transformer serving their residence or business. It is important that every customer be linked to a device in the model so that accurate statistics are derived on each outage. Customers not linked to a device in the model are referred to as "fuzzies".
More advanced automatic meter reading (AMR) systems can provide outage detection and restoration capability and thus serve as virtual calls indicating customers who are without power. However, unique characteristics of AMR systems such as the additional system loading and the potential for false positives requires that additional rules and filter logic must be added to the OMS to support this integration. [1]
Outage management systems are also commonly integrated with SCADA systems which can automatically report the operation of monitored circuit breakers and other intelligent devices such as SCADA reclosers.
Another system that is commonly integrated with an outage management system is a mobile data system. This integration provides the ability for outage predictions to automatically be sent to crews in the field and for the crews to be able to update the OMS with information such as estimated restoration times without requiring radio communication with the control center. Crews also transmit details about what they did during outage restoration.
It is important that the outage management system electrical model be kept up to current so that it can accurately make outage predictions and also accurately keep track of which customers are out and which are restored. By using this model and by tracking which switches, breakers and fuses are open and which are closed, network tracing functions can be used to identify every customer who is out, when they were first out and when they were restored. Tracking this information is the key to accurately reporting outage statistics. (P.-C. Chen, et al., 2014)
OMS benefits include:
An OMS supports distribution system planning activities related to improving reliability by providing important outage statistics. In this role, an OMS provides the data needed for the calculation of measurements of the system reliability. Reliability is commonly measured by performance indices defined by the IEEE P1366-2003 standard. The most frequently used performance indices are SAIDI, CAIDI, SAIFI and MAIFI.
An OMS also support the improvement of distribution reliability by providing historical data that can be mined to find common causes, failures and damages. By understanding the most common modes of failure, improvement programs can be prioritized with those that provide the largest improvement on reliability for the lowest cost.
While deploying an OMS improves the accuracy of the measured reliability indices, it often results an apparent degradation of reliability due to improvements over manual methods that almost always underestimate the frequency of outages, the size of outage and the duration of outages. To compare reliability in years before an OMS deployment to the years after requires adjustments to be made to the pre-deployment years measurements to be meaningful.
A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by current in excess of that which the equipment can safely carry (overcurrent). Its basic function is to interrupt current flow to protect equipment and to prevent fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.
A power outage, also called a powercut, a power out, a power failure, a power blackout, a power loss, a blackout or a power drought — is the loss of the electrical power network supply to an end user.
A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. There are 55,000 substations in the United States.
Automatic meter reading (AMR) is the technology of automatically collecting consumption, diagnostic, and status data from water meter or energy metering devices and transferring that data to a central database for billing, troubleshooting, and analyzing. This technology mainly saves utility providers the expense of periodic trips to each physical location to read a meter. Another advantage is that billing can be based on near real-time consumption rather than on estimates based on past or predicted consumption. This timely information coupled with analysis can help both utility providers and customers better control the use and production of electric energy, gas usage, or water consumption.
In electric power distribution, automatic circuit reclosers (ACRs) are a class of switchgear designed for use on overhead electricity distribution networks to detect and interrupt transient faults. Also known as reclosers or autoreclosers, ACRs are essentially rated circuit breakers with integrated current and voltage sensors and a protection relay, optimized for use as a protection asset. Commercial ACRs are governed by the IEC 62271-111/IEEE Std C37.60 and IEC 62271-200 standards. The three major classes of operating maximum voltage are 15.5 kV, 27 kV and 38 kV.
Reliability engineering is a sub-discipline of systems engineering that emphasizes the ability of equipment to function without failure. Reliability is defined as the probability that a product, system, or service will perform its intended function adequately for a specified period of time, OR will operate in a defined environment without failure. Reliability is closely related to availability, which is typically described as the ability of a component or system to function at a specified moment or interval of time.
Power-system automation is the act of automatically controlling the power system via instrumentation and control devices. Substation automation refers to using data from Intelligent electronic devices (IED), control and automation capabilities within the substation, and control commands from remote users to control power-system devices.
The availability factor of a power plant is the duration it achieves production of electricity divided by the duration that it was planned to produce electricity. In the field of reliability engineering, availability factor is known as operational availability, . The capacity factor of a plant includes numerous other factors which determine the durations the plant is planned to produce electricity. A solar photovoltaic plant is not planned to operate in the dark of a night, hence unplanned maintenance occurring whilst the sun is set does not impact the availability factor.
Power system protection is a branch of electrical power engineering that deals with the protection of electrical power systems from faults through the disconnection of faulted parts from the rest of the electrical network. The objective of a protection scheme is to keep the power system stable by isolating only the components that are under fault, whilst leaving as much of the network as possible in operation. The devices that are used to protect the power systems from faults are called protection devices.
The System Average Interruption Duration Index (SAIDI) is commonly used as a reliability index by electric power utilities. SAIDI is the average cumulative outage duration for each customer served, and is calculated as:
The System Average Interruption Frequency Index (SAIFI) is commonly used as a reliability index by electric power utilities. This index measures the average number of times that a system customer experiences an outage during the year or during a given time period.
The Customer Average Interruption Duration Index (CAIDI) is a reliability index commonly used by electric power utilities. It is related to SAIDI and SAIFI, and is calculated as
A phasor measurement unit (PMU) is a device used to estimate the magnitude and phase angle of an electrical phasor quantity in the electricity grid using a common time source for synchronization. Time synchronization is usually provided by GPS or IEEE 1588 Precision Time Protocol, which allows synchronized real-time measurements of multiple remote points on the grid. PMUs are capable of capturing samples from a waveform in quick succession and reconstructing the phasor quantity, made up of an angle measurement and a magnitude measurement. The resulting measurement is known as a synchrophasor. These time synchronized measurements are important because if the grid’s supply and demand are not perfectly matched, frequency imbalances can cause stress on the grid, which is a potential cause for power outages.
The smart grid is an enhancement of the 20th century electrical grid, using two-way communications and distributed so-called intelligent devices. Two-way flows of electricity and information could improve the delivery network. Research is mainly focused on three systems of a smart grid – the infrastructure system, the management system, and the protection system. Electronic power conditioning and control of the production and distribution of electricity are important aspects of the smart grid.
An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The electrical grid can be broadly divided into the generators that supply the power, the transmission system that carries the power from the generating centers to the load centers, and the distribution system that feeds the power to nearby homes and industries.
The Momentary Average Interruption Frequency Index (MAIFI) is a reliability index used by electric power utilities. MAIFI is the average number of momentary interruptions that a customer would experience during a given period. Electric power utilities may define momentary interruptions differently, with some considering a momentary interruption to be an outage of less than 1 minute in duration while others may consider a momentary interruption to be an outage of less than 5 minutes in duration.
A distribution management system (DMS) is a collection of applications designed to monitor and control the electric power distribution networks efficiently and reliably. It acts as a decision support system to assist the control room and field operating personnel with the monitoring and control of the electric distribution system. Improving the reliability and quality of service in terms of reducing power outages, minimizing outage time, maintaining acceptable frequency and voltage levels are the key deliverables of a DMS. Given the complexity of distribution grids, such systems may involve communication and coordination across multiple components. For example, the control of active loads may require a complex chain of communication through different components as described in US patent 11747849B2
Roy Billinton is a Canadian scholar and a Distinguished Emeritus Professor at the University of Saskatchewan, Saskatoon, Saskatchewan, Canada. In 2008, Billinton won the IEEE Canada Electric Power Medal for his research and application of reliability concepts in electric power system. In 2007, Billinton was elected a Foreign Associate of the United States National Academy of Engineering for "contributions to teaching, research and application of reliability engineering in electric power generation, transmission, and distribution systems."
A Distribution Transformer Monitor (DTM) is a specialized hardware device that collects and measures information relative to electricity passing into and through a distribution transformer. The DTM is typically retrofitted onto pole top and pad mount transformers. A pole top or pad mount transformer commonly powers anywhere from 5-8 homes in the US and is the last voltage transition in stepping down voltage before it gets to the home or business. The conventional placement of Distributed Temperature Monitoring (DTM) devices is typically observed at the terminals of transformers. However, there are instances where these devices are directly affixed to the secondary power lines.
Reliability index is an attempt to quantitatively assess the reliability of a system using a single numerical value. The set of reliability indices varies depending on the field of engineering, multiple different indices may be used to characterize a single system. In the simple case of an object that cannot be used or repaired once it fails, a useful index is the mean time to failure representing an expectation of the object's service lifetime. Another cross-disciplinary index is forced outage rate (FOR), a probability that a particular type of a device is out of order. Reliability indices are extensively used in the modern electricity regulation.