Stab-Lok

Last updated
Interior of a Federal Pacific Electric Stab-Lok circuit breaker panel Stab-Lok circuit breaker panel interior .jpg
Interior of a Federal Pacific Electric Stab-Lok circuit breaker panel

Stab-Lok is a brand name of electrical circuit breakers that were manufactured primarily by Federal Pacific Electric from 1950 to 1980. [1] [2] In June 1980, Reliance Electric, which had purchased FPE, reported to the United States Consumer Product Safety Commission that "many FPE circuit breakers did not fully comply with Underwriters Laboratories, Inc. (UL) requirements. Commission testing confirmed that these breakers fail certain UL calibration test requirements." [3] In 2018 it was reported that Stab-Lok breakers and panels, made by FPE and other companies, were still in use, and it was recommended that they be removed as a potential fire hazard. [4]

Contents

Safety issues

It has been widely reported in news media and online that Stab-Lok circuit breakers, and panels, do not meet the requirements of the National Electrical Code (NFPA 70) and Underwriters Laboratories, and should be replaced.

According to a 2012 news report by NBC Bay Area (KNTV):

The "Stab-Lok” circuit breaker and panel produced by Federal Pacific Electric (FPE) installed in hundreds of thousands of homes in the Bay Area may cause house fires, according decades of documentation and electrical experts interviewed by the NBC Bay Area Investigative Unit. Stab-Lok circuit breakers are most commonly found in houses built before 1990.

Federal Pacific Circuit Breakers: Investigation Finds Decades of Danger. [5]

According to an independent analysis performed by Jesse Aronson, P.E.:

FPE and replacement brands of Stab-Lok circuit breakers have a high defect rate. They do not provide the level of circuit protection required by the NEC (National Electrical Code). Homeowners should be alerted to this safety defect and advised to have it corrected. FPE Stab-Lok circuit breaker panels should be replaced unless the occupants are informed and willing to live with the resulting increased risk of fire and injury.

"HAZARDOUS FPE CIRCUIT BREAKERS AND PANELS: Information for Homeowners, Inspectors, and Electricians" [6]

According to ANGI Homeservices, formerly known as Angie's List,

If your home has a Federal Pacific Electric (FPE) circuit breaker panel with Stab-Lok circuit breakers, you run a significant risk of breaker malfunction and fire. While these types of circuit breakers were once commonly installed in houses across the country, many are defective. To be on the safe side, it’s a good idea to replace any Federal Pacific breakers in your home. [7]

Angie's List and NBC Bay Area both highlighted an October 2002 ruling in a New Jersey Superior Court, which found that FPE (Federal Pacific Electric), the manufacturer of the Stab-Lok breakers and panels, "knowingly and purposefully [sic] distributed circuit breakers which were not tested to meet UL standards as indicated on their label". [8]

Government response

After the 1979 sale of Federal Pacific Electric to Reliance Electric, a unit of Exxon Corporation, Reliance reported to the U.S. Consumer Product Safety Commission that the Stab-Lok breakers and panels did not meet the requirements published by Underwriters Laboratories, even though the products bore UL labels. The CPSC performed its own testing and concluded:

Commission testing confirmed that these breakers fail certain UL calibration test requirements. [9]

After a two-year investigation into whether these test failures would create a "serious risk of injury to consumers", the CPSC closed the investigation, citing a lack of budget to continue:

The Commission staff estimates that it would cost several million dollars to gather the data necessary to assess fully whether those circuit breakers that are installed in homes ... present a risk to the public. [10]

CPSC urged consumers to remain vigilant and report any failed breakers or equipment so it could continue to collect data.

Fate

The Stab-Lok brand was discontinued, and its maker, FPE, went through a succession of later owners: Reliance Electric, owned by Exxon, in 1979; Exxon later sold Reliance Electric to Rockwell, which sold the business to Baldor Electric in 2006. [11] Baldor was bought by ABB in 2011. [12]

Other companies began building Stab-Lok style breakers through around 1990. According to a Washington Post article, home inspection professionals now routinely advise consumers to remove and replace those panels that remain in service. [13]

Providers

Other manufacturers of Stab-Lok breakers may have included:[ citation needed ]

Related Research Articles

<span class="mw-page-title-main">Circuit breaker</span> Automatic circuit protection device

A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by current in excess of that which the equipment can safely carry (overcurrent). Its basic function is to interrupt current flow to protect equipment and to prevent fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.

<span class="mw-page-title-main">UL (safety organization)</span> Global safety certification company

The UL enterprise is a global private safety company headquartered in Northbrook, Illinois, composed of three organizations, UL Research Institutes, UL Standards & Engagement and UL Solutions.

<span class="mw-page-title-main">Surge protector</span> Protects electrical devices from voltage spikes

A surge protector (or spike suppressor, surge suppressor, surge diverter, surge protection device or transient voltage surge suppressor is an appliance or device intended to protect electrical devices in alternating current circuits from voltage spikes with very short duration measured in microseconds, which can arise from a variety of causes including lightning strikes in the vicinity.

<span class="mw-page-title-main">Residual-current device</span> Electrical safety device used in household wiring

A residual-current device (RCD), residual-current circuit breaker (RCCB) or ground fault circuit interrupter (GFCI) is an electrical safety device that interrupts an electrical circuit when the current passing through a conductor is not equal and opposite in both directions, therefore indicating leakage current to ground or current flowing to another powered conductor. The device's purpose is to reduce the severity of injury caused by an electric shock. This type of circuit interrupter cannot protect a person who touches both circuit conductors at the same time, since it then cannot distinguish normal current from that passing through a person.

<span class="mw-page-title-main">National Electrical Code</span> Electrical wiring standard

The National Electrical Code (NEC), or NFPA 70, is a regionally adoptable standard for the safe installation of electrical wiring and equipment in the United States. It is part of the National Fire Code series published by the National Fire Protection Association (NFPA), a private trade association. Despite the use of the term "national," it is not a federal law. It is typically adopted by states and municipalities in an effort to standardize their enforcement of safe electrical practices. In some cases, the NEC is amended, altered and may even be rejected in lieu of regional regulations as voted on by local governing bodies.

A distribution board is a component of an electricity supply system that divides an electrical power feed into subsidiary circuits while providing a protective fuse or circuit breaker for each circuit in a common enclosure. Normally, a main switch, and in recent boards, one or more residual-current devices (RCDs) or residual current breakers with overcurrent protection (RCBOs) are also incorporated.

<span class="mw-page-title-main">Arc-fault circuit interrupter</span> Circuit breaker that protects against intermittent faults associated with arcing

An arc-fault circuit interrupter (AFCI) or arc-fault detection device (AFDD) is a circuit breaker that breaks the circuit when it detects the electric arcs that are a signature of loose connections in home wiring. Loose connections, which can develop over time, can sometimes become hot enough to ignite house fires. An AFCI selectively distinguishes between a harmless arc, and a potentially dangerous arc.

<span class="mw-page-title-main">U.S. Consumer Product Safety Commission</span> United States government agency

The United States Consumer Product Safety Commission is an independent agency of the United States government. The CPSC seeks to promote the safety of consumer products by addressing "unreasonable risks" of injury ; developing uniform safety standards ; and conducting research into product-related illness and injury. In part due to its small size, the CPSC attempts to coordinate with outside parties—including companies and consumer advocates—to leverage resources and expertise to achieve outcomes that advance consumer safety. The agency was created in 1972 through the Consumer Product Safety Act. The agency reports to Congress and the President; it is not part of any other department or agency in the federal government. The CPSC has five commissioners, who are nominated by the president and confirmed by the Senate for staggered seven-year terms. Historically, the commission was often run by three commissioners or fewer. Since 2009, however, the agency has generally been led by five commissioners, one of whom serves as chairman. The commissioners set policy for the CPSC. The CPSC is headquartered in Bethesda, Maryland.

<span class="mw-page-title-main">Hot tub</span> Large tub for hydrotherapy or pleasure

A hot tub is a large tub full of water used for hydrotherapy, relaxation or pleasure. Some have powerful jets for massage purposes. Hot tubs are sometimes also known as "spas" or by the trade name Jacuzzi. Hot tubs may be located outdoors or indoors.

<span class="mw-page-title-main">Rare-earth magnet</span> Strong permanent magnet made from alloys of rare-earth elements

A rare-earth magnet is a strong permanent magnet made from alloys of rare-earth elements. Developed in the 1970s and 1980s, rare-earth magnets are the strongest type of permanent magnets made, producing significantly stronger magnetic fields than other types such as ferrite or alnico magnets. The magnetic field typically produced by rare-earth magnets can exceed 1.2 teslas, whereas ferrite or ceramic magnets typically exhibit fields of 0.5 to 1 tesla.

<span class="mw-page-title-main">Aluminum building wiring</span> Type of electrical wiring

Aluminum building wiring is a type of electrical wiring for residential construction or houses that uses aluminum electrical conductors. Aluminum provides a better conductivity-to-weight ratio than copper, and therefore is also used for wiring power grids, including overhead power transmission lines and local power distribution lines, as well as for power wiring of some airplanes. Utility companies have used aluminum wire for electrical transmission in power grids since around the late 1800s to the early 1900s. It has cost and weight advantages over copper wires. Aluminum in power transmission and distribution applications is still the preferred wire material today.

<span class="mw-page-title-main">Consumer Product Safety Act</span> 1972 American legislation

The Consumer Safety Act (CPSA) was enacted on October 27, 1972, by the United States Congress. The act should not be confused with an earlier Senate Joint Resolution 33 of November 20, 1967, which merely established a temporary National Commission on Product Safety (NCPS), and for only 90-days. Section 4 of the 1972 act established the United States Consumer Product Safety Commission (CPSC) as a permanent independent agency of the United States federal government and defined its basic authority. The act gives CPSC the power to develop safety standards and pursue recalls for products that present unreasonable or substantial risks of injury or death to consumers. It also allows CPSC to ban a product if there is no feasible alternative to an outright ban. CPSC has jurisdiction over more than 15,000 different consumer products. The CPSA excludes from jurisdiction those products that expressly lie in another federal agency's jurisdiction, for example food, drugs, cosmetics, medical devices, tobacco products, firearms and ammunition, motor vehicles, pesticides, aircraft, and boats. These products may fall under the purview of agencies such as the U.S. Food and Drug Administration, the U.S. Bureau of Alcohol, Tobacco, Firearms and Explosives, the U.S. Department of Agriculture, the U.S. Department of Transportation, the U.S. Environment Protection Agency, and the U.S. Federal Aviation Administration.

<span class="mw-page-title-main">Power entry module</span>

A power entry module (PEM) is an electromechanical component used in electrical appliances, integrating the appliance inlet with other components such as:

<span class="mw-page-title-main">Electrical Safety Foundation</span>

The Electrical Safety Foundation (ESFI), formerly the Electrical Safety Foundation International, is a 501(c)(3) non-profit organization based in Rosslyn, Virginia, US dedicated exclusively to promoting electrical safety at home, school, and in the workplace. Founded in 1994 as a cooperative effort by the National Electrical Manufacturers Association (NEMA), Underwriters Laboratories (UL), and the US Consumer Product Safety Commission (CPSC), ESFI is funded by charitable contributions from, distributors, Nationally Recognized Testing Laboratories, retailers, insurers, utilities, safety organizations, and trade and labor associations. The mission of the Electrical Safety Foundation (ESFI) is to prevent electrically-related injuries, deaths and fires; saving lives and property through public education and outreach.

<span class="mw-page-title-main">Consumer Product Safety Improvement Act</span>

The Consumer Product Safety Improvement Act (CPSIA) of 2008 is a United States law signed on August 14, 2008 by President George W. Bush. The legislative bill was known as HR 4040, sponsored by Congressman Bobby Rush (D-Ill.). On December 19, 2007, the U.S. House approved the bill 407-0. On March 6, 2008, the U.S. Senate approved the bill 79-13. The law—public law 110-314—increases the budget of the Consumer Product Safety Commission (CPSC), imposes new testing and documentation requirements, and sets new acceptable levels of several substances. It imposes new requirements on manufacturers of apparel, shoes, personal care products, accessories and jewelry, home furnishings, bedding, toys, electronics and video games, books, school supplies, educational materials and science kits. The Act also increases fines and specifies jail time for some violations.

<span class="mw-page-title-main">Pre-lit tree</span> Type of artificial tree

A pre-lit tree is an artificial Christmas tree which is pre-wired with Christmas lights. The lights are wrapped around the tree before it is sold, reducing set up time and making storage simpler. The lights cannot usually be removed from the tree because they are normally embedded within the artificial branches. The product may be sold as a kit - the user assembles the tree and plugs it into an electrical outlet - or the dealer may assemble it before the sale. Larger trees usually contain traditional strands of bulb lights or LEDs, while smaller tabletop trees may have fiber-optic branches. Pre-lit trees are categorised under the headings of electrical goods.

A generator interlock kit is a device designed to allow safe powering of a home by a portable generator during a power outage. It is a less-expensive alternative to purchasing and installing a dedicated transfer switch. The kit achieves the same function by adding an external interlock onto an existing breaker panel that allows the main breaker to be turned on or one designated load breaker to be turned on, but not both at the same time. The interlocked load breaker is repurposed as the "backfeed" breaker, and a generator is connected to it.

<span class="mw-page-title-main">Self-balancing scooter</span> Battery-powered electric vehicle

A self-balancing scooter is a self-balancing personal transporter consisting of two motorized wheels connected to a pair of articulated pads on which the rider places their feet. The rider controls the speed by leaning forward or backward, and direction of travel by twisting the pads.

<span class="mw-page-title-main">True DC</span> Type of Switch Disconnect

True DC is a type of switch disconnect (isolator) used in solar photovoltaic installations, in accordance with EN 60364–7–712. Created by UK based IMO Precision Controls Ltd, and later adopted by other manufacturers such as Senton and ABB. The isolator design ensures a very fast break/make action by incorporating a user independent switching action. As the handle is moved, it interacts with a spring mechanism causing the contacts to "snap" over upon reaching a set point. This mechanism means that the disconnection of the load circuits and the suppression of the electrical arc, produced by a constant DC load, is normally extinguished in a maximum of 5 MS using the specific pole suppression chambers incorporated into the design.

Federal Pacific Electric was an electrical products manufacturer based in Newark, New Jersey, US. It was one of the "big 5" electrical equipment manufacturers in the United States in the mid-20th century.

References

  1. Terry, Ken (26 February 2010). "Hazards of the Federal Pacific electrical panel made in the '50s". Redlands Daily Facts. Archived from the original on 9 April 2016. Retrieved 5 December 2013.
  2. "HELTER SHELTER: WORRISOME ELECTRICAL THINGS: It's all in the wiring; Federal Pacific (FPE) Stab-Lok Electrical Panels // Aluminum Wiring // Old Rag Wires in Attics". Boise Weekly. 6 August 2002. Archived from the original on 7 April 2016. Retrieved 5 December 2013.
  3. "Commission Closes Investigation Of FPE Circuit Breakers And Provides Safety Information For Consumers". U.S. Consumer Product Safety Commission. Retrieved 2021-07-30.
  4. Leamy, Elisabeth (2019-05-09). "Despite previous safety concerns, this circuit breaker is still in homes". Washington Post.
  5. Kovaleski, Tony (2012-09-29). "Federal Pacific Circuit Breakers: Investigation Finds Decades of Danger". NBC Bay Area. NBC Bay Area; KNTV. Archived from the original on 2021-03-02. Retrieved 2021-07-30.
  6. Aronson, Jesse. "Hazardous FPE Circuit Breakers and Panels: Information for Homeowners, Inspectors, and Electricians (Updated November 10, 2017)" (PDF). Retrieved 2021-07-30.
  7. Wack, Margaret (2021-06-09). "What You Need to Know About Federal Pacific Breakers". Angie's List. ANGI HomeServices / Angie's List. Archived from the original on 2021-06-12. Retrieved 2021-07-30.
  8. "Order for Partial Summary Judgement, Yacout vs. Federal Pacific Electric Company, et al., MID-L-2904-97" (PDF). FPE-Info. Middlesex County, New Jersey. Archived from the original (PDF) on 2010-07-14. Retrieved 2021-07-30.
  9. "Commission Closes Investigation Of FPE Circuit Breakers And Provides Safety Information For Consumers". U.S. Consumer Product Safety Commission. Retrieved 2021-07-30.
  10. "Commission Closes Investigation Of FPE Circuit Breakers And Provides Safety Information For Consumers". U.S. Consumer Product Safety Commission. Retrieved 2021-07-30.
  11. "Rockwell to sell Reliance Electric for $1.8B". Milwaukee Business Journal.
  12. ABB (Press Release) (2011-11-30). "ABB Acquires Baldor Electric For $4.2 Billion In Cash". Manufacturing.net. Archived from the original on 2021-07-31. Retrieved 2021-07-30.
  13. Leamy, Elizabeth (2019-05-09). "Despite previous safety concerns, this circuit breaker is still in homes". Washington Post. Retrieved 2021-07-30.