Circuit total limitation

Last updated

Circuit total limitation (CTL) is one of the present-day standards for electrical panels sold in the United States according to the National Electrical Code. This standard requires an electrical panel to provide a physical mechanism to prevent installing more circuit breakers than it was designed for. This has generally been implemented by restricting the use of tandem (duplex) breakers to replace standard single pole breakers.

Contents

Code Requirement

The 1965 edition of the NEC, article 384-15 was the first reference to the circuit total limitation of panelboards. [1] As of 2008, the location of this language is at Article 408.54 now titled "Maximum Number of Overcurrent Devices." Non-CTL panels have not been made by reputable manufacturers since 1965.[ citation needed ] Though this may change due to the 2008 repeal.

Non-CTL for replacement only

Circuitboards and panelboards built prior to 1965 did not have circuit total limiting devices or features built-in. To support these old panels, non-CTL circuit breakers that bypass the rejection feature are still sold "for replacement use only." [2] As a result, numerous unsafe situations have resulted where panels were dangerously overloaded because these non-CTL breakers continue to be used.[ citation needed ] With the use of non-CTL breakers, panels can be configured with the total number of circuits in excess of the designed capacity of that panel.

The 2008 code did away with the previous 42 circuit limitation on panelboards. [3] One can now order panelboards with as many as 84 circuit places, and a corresponding ampacity rating. If a panelboard with a sufficient number of breaker positions is installed in the first place, the need for non-CTL breakers should be eliminated.

In their 2019 catalog Eaton now specifies that their non-CTL breakers are "Suitable for use in plug-on neutral style loadcenters" [4] which negates the replacement only rule.

See also

Related Research Articles

<span class="mw-page-title-main">Ground (electricity)</span> Reference point in an electrical circuit from which voltages are measured

In electrical engineering, ground or earth may be a reference point in an electrical circuit from which voltages are measured, a common return path for electric current, or a direct physical connection to the Earth.

<span class="mw-page-title-main">Circuit breaker</span> Automatic circuit protection device

A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by overcurrent. Its basic function is to interrupt current flow to protect equipment and to prevent the risk of fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.

Eaton Corporation plc is an American-Irish multinational power management company with 2022 sales of $20.75 billion, founded in the United States with global headquarters in Dublin, Ireland, and a secondary administrative center in Beachwood, Ohio. Eaton has more than 92,000 employees and sells products to customers in more than 175 countries.

<span class="mw-page-title-main">Surge protector</span> Protects electrical devices from voltage spikes

A surge protector (or spike suppressor, surge suppressor, surge diverter, surge protection device or transient voltage surge suppressor is an appliance or device intended to protect electrical devices from voltage spikes in alternating current circuits. A voltage spike is a transient event, typically lasting 1 to 30 microseconds, that may reach over 1,000 volts. Lightning that hits a power line can give a spike of over 100,000 volts and can burn through wiring insulation and cause fires, but even modest spikes can destroy a wide variety of electronic devices, computers, battery chargers, modems and TVs etc, that happen to be plugged in at the time. Typically the surge device will trigger at a set voltage, around 3 to 4 times the mains voltage, and divert the current to earth. Some devices may absorb the spike and release it as heat. They are generally rated according to the amount of energy in joules they can absorb.

Electrical wiring in North America follows the regulations and standards applicable at the installation location. It is also designed to provide proper function, and is also influenced by history and traditions of the location installation.

<span class="mw-page-title-main">Residual-current device</span> Electrical safety device used in household wiring

A residual-current device (RCD), residual-current circuit breaker (RCCB) or ground fault circuit interrupter (GFCI) is an electrical safety device that quickly breaks an electrical circuit with leakage current to ground. It is to protect equipment and to reduce the risk of serious harm from an ongoing electric shock. Injury may still occur in some cases, for example if a human receives a brief shock before the electrical circuit is isolated, falls after receiving a shock, or if the person touches both conductors at the same time.

<span class="mw-page-title-main">National Electrical Code</span> Electrical wiring standard

The National Electrical Code (NEC), or NFPA 70, is a regionally adoptable standard for the safe installation of electrical wiring and equipment in the United States. It is part of the National Fire Code series published by the National Fire Protection Association (NFPA), a private trade association. Despite the use of the term "national", it is not a Federal law. It is typically adopted by states and municipalities in an effort to standardize their enforcement of safe electrical practices. In some cases, the NEC is amended, altered and may even be rejected in lieu of regional regulations as voted on by local governing bodies.

<span class="mw-page-title-main">Fuse (electrical)</span> Electrical safety device that provides overcurrent protection

In electronics and electrical engineering, a fuse is an electrical safety device that operates to provide overcurrent protection of an electrical circuit. Its essential component is a metal wire or strip that melts when too much current flows through it, thereby stopping or interrupting the current. It is a sacrificial device; once a fuse has operated it is an open circuit, and must be replaced or rewired, depending on its type.

A distribution board is a component of an electricity supply system that divides an electrical power feed into subsidiary circuits while providing a protective fuse or circuit breaker for each circuit in a common enclosure. Normally, a main switch, and in recent boards, one or more residual-current devices (RCDs) or residual current breakers with overcurrent protection (RCBOs) are also incorporated.

CTL can refer to:

<span class="mw-page-title-main">Arc-fault circuit interrupter</span> Circuit breaker that protects against intermittent faults associated with arcing

An arc-fault circuit interrupter (AFCI) or arc-fault detection device (AFDD) is a circuit breaker that breaks the circuit when it detects the electric arcs that are a signature of loose connections in home wiring. Loose connections, which can develop over time, can sometimes become hot enough to ignite house fires. An AFCI selectively distinguishes between a harmless arc, and a potentially dangerous arc.

In electrical engineering, ground and neutral are circuit conductors used in alternating current (AC) electrical systems. The ground circuit is connected to earth, and neutral circuit is usually connected to ground. As the neutral point of an electrical supply system is often connected to earth ground, ground and neutral are closely related. Under certain conditions, a conductor used to connect to a system neutral is also used for grounding (earthing) of equipment and structures. Current carried on a grounding conductor can result in objectionable or dangerous voltages appearing on equipment enclosures, so the installation of grounding conductors and neutral conductors is carefully defined in electrical regulations. Where a neutral conductor is used also to connect equipment enclosures to earth, care must be taken that the neutral conductor never rises to a high voltage with respect to local ground.

<span class="mw-page-title-main">Electrical wiring</span> Electrical installation of cabling

Electrical wiring is an electrical installation of cabling and associated devices such as switches, distribution boards, sockets, and light fittings in a structure.

Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.

<span class="mw-page-title-main">Aluminum building wiring</span> Type of electrical wiring

Aluminum building wiring is a type of electrical wiring for residential construction or houses that uses aluminum electrical conductors. Aluminum provides a better conductivity to weight ratio than copper, and therefore is also used for wiring power grids, including overhead power transmission lines and local power distribution lines, as well as for power wiring of some airplanes. Utility companies have used aluminum wire for electrical transmission in power grids since around the late 1800s to the early 1900s. It has cost and weight advantages over copper wires. Aluminum wire in power transmission and distribution applications is still the preferred material today.

<span class="mw-page-title-main">NEMA connector</span> Power plugs and receptacles used in North America and some other regions

NEMA connectors are power plugs and receptacles used for AC mains electricity in North America and other countries that use the standards set by the US National Electrical Manufacturers Association. NEMA wiring devices are made in current ratings from 15 to 60 amperes (A), with voltage ratings from 125 to 600 volts (V). Different combinations of contact blade widths, shapes, orientations, and dimensions create non-interchangeable connectors that are unique for each combination of voltage, electric current carrying capacity, and grounding system.

<span class="mw-page-title-main">Wiring diagram</span> Simplified conventional pictorial representation of an electrical circuit

A wiring diagram is a simplified conventional pictorial representation of an electrical circuit. It shows the components of the circuit as simplified shapes, and the power and signal connections between the devices.

<span class="mw-page-title-main">Cheater plug</span> Type of adapter

A cheater plug, AC ground lifter or three-prong/two-prong adapter is an adapter that allows a NEMA 5-15P grounding-type plug to connect to a NEMA 1-15R non-grounding receptacle. They are needed to allow appliances with 3-wire power cords to plug into legacy ungrounded receptacles found in older buildings. The use of such an adapter avoids the need to replace receptacles, but is potentially hazardous if the grounding tab is not connected to electrical ground. These adapters are illegal in some jurisdictions, in particular throughout Canada. A safer and more reliable alternative identified in the US and Canadian electrical codes is to replace the outlet with a Ground Fault Circuit Interrupter (GFCI) breaker outlet.

A generator interlock kit is a device designed to allow safe powering of a home by a portable generator during a power outage. It is a less-expensive alternative to purchasing and installing a dedicated transfer switch. The kit achieves the same function by adding an external interlock onto an existing breaker panel that allows the main breaker to be turned on or one designated load breaker to be turned on, but not both at the same time. The interlocked load breaker is repurposed as the "backfeed" breaker, and a generator is connected to it.

<span class="mw-page-title-main">Stab-Lok</span> Electrical circuit breakers, 1950 to 1980

Stab-Lok is a brand name of electrical circuit breakers that were manufactured primarily by Federal Pacific Electric between 1950-1980. In June 1980, Reliance Electric, which had purchased FPE, reported to the United States Consumer Product Safety Commission that "many FPE circuit breakers did not fully comply with Underwriters Laboratories, Inc. (UL) requirements. Commission testing confirmed that these breakers fail certain UL calibration test requirements." Professional home inspectors now routinely recommend removing and replacing Stab-Lok breakers and panels that remain in service, as they may pose a fire hazard.

References

  1. Terrell Croft; Wilford I. Summers; Frederic Hartwell (17 August 2008). American Electricians' Handbook. p. 4.52. ISBN   9780071642583.{{cite book}}: |work= ignored (help)
  2. "UL's Guide Information for Electrical Equipment: The White Book 2008" (PDF). p. 90. Archived from the original (PDF) on 2008-09-13.
  3. See "bullet" in 2008 NEC between Articles 408.30 and 408.36, where 2005's Article 408.35 appeared.
  4. https://www.eaton.com/ecm/groups/public/@pub/@electrical/documents/content/vol01_tab01.pdf [ bare URL PDF ]