A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by current in excess of that which the equipment can safely carry (overcurrent). Its basic function is to interrupt current flow to protect equipment and to prevent fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset (either manually or automatically) to resume normal operation.

Contents

Circuit breakers are made in varying current ratings, from devices that protect low-current circuits or individual household appliances, to switchgear designed to protect high-voltage circuits feeding an entire city. Any device which protects against excessive current by automatically removing power from a faulty system, such as a circuit breaker or fuse, can be referred to as an over-current protection device (OCPD).

Origins

An early form of circuit breaker was described by Thomas Edison in an 1879 patent application, although his commercial power distribution system used fuses. [1] Its purpose was to protect lighting circuit wiring from accidental short circuits and overloads. A modern miniature circuit breaker similar to the ones now in use was patented by Brown, Boveri & Cie in 1924. Hugo Stotz, an engineer who had sold his company to Brown, Boveri & Cie, was credited as the inventor on German patent 458392. [2] Stotz's invention was the forerunner of the modern thermal-magnetic breaker commonly used in household load centers to this day.

Interconnection of multiple generator sources into an electrical grid required the development of circuit breakers with increasing voltage ratings and increased ability to safely interrupt the increasing short-circuit currents produced by networks. Simple air-break manual switches produced hazardous arcs when interrupting high-voltage circuits; these gave way to oil-enclosed contacts, and various forms using the directed flow of pressurized air, or pressurized oil, to cool and interrupt the arc. By 1935, the specially constructed circuit breakers used at the Boulder Dam project used eight series breaks and pressurized oil flow to interrupt faults of up to 2,500 MVA, in three AC cycles. [3]

Operation

All circuit breaker systems have common features in their operation, but details vary substantially depending on the voltage class, current rating and type of the circuit breaker.

The circuit breaker must first detect a fault condition. In small mains and low-voltage circuit breakers, this is usually done within the device itself. Typically, the heating or magnetic effects of electric current are employed. Circuit breakers for large currents or high voltages are usually arranged with protective relay pilot devices to sense a fault condition and to operate the opening mechanism. These typically require a separate power source, such as a battery, although some high-voltage circuit breakers are self-contained with current transformers, protective relays, and internal power sources.

Once a fault is detected, the circuit breaker contacts must open to interrupt the circuit; this is commonly done using mechanically stored energy contained within the breaker, such as a spring or compressed air to separate the contacts. A breaker may also use the higher current caused by the fault to separate the contacts, via thermal expansion or increased magnetic field. A small circuit breakers typically has a manual control lever to switch the circuit off or reset a tripped breaker, while a larger unit may use a solenoid to trip the mechanism, and an electric motor to restore energy to springs (which rapidly separate contacts when the breaker is tripped).

The circuit breaker contacts must carry the load current without excessive heating, and must also withstand the heat of the arc produced when interrupting (opening) the circuit. Contacts are made of copper or copper alloys, silver alloys and other highly conductive materials. Service life of the contacts is limited by the erosion of contact material due to arcing while interrupting the current. Miniature and molded-case circuit breakers are usually discarded when the contacts have worn, but power circuit breakers and high-voltage circuit breakers have replaceable contacts.

When a high current or voltage is interrupted, an arc is generated. The maximum length of the arc is generally proportional to the voltage while the intensity (or heat) is proportional to the current. This arc must be contained, cooled and extinguished in a controlled way, so that the gap between the contacts can again withstand the voltage in the circuit. Different circuit breakers use vacuum, air, insulating gas, or oil as the medium the arc forms in. Different techniques are used to extinguish the arc including:

Finally, once the fault condition has been cleared, the contacts must again be closed to restore power to the interrupted circuit.

Arc interruption

Low-voltage miniature circuit breakers (MCB) use air alone to extinguish the arc. These circuit breakers contain so-called arc chutes, a stack of mutually insulated parallel metal plates that divide and cool the arc. By splitting the arc into smaller arcs the arc is cooled down while the arc voltage is increased and serves as an additional impedance that limits the current through the circuit breaker. The current-carrying parts near the contacts provide easy deflection of the arc into the arc chutes by a magnetic force of a current path, although magnetic blowout coils or permanent magnets could also deflect the arc into the arc chute (used on circuit breakers for higher ratings). The number of plates in the arc chute is dependent on the short-circuit rating and nominal voltage of the circuit breaker.

In larger ratings, oil circuit breakers rely upon vaporization of some of the oil to blast a jet of oil through the arc. [4]

Gas (usually sulfur hexafluoride) circuit breakers sometimes stretch the arc using a magnetic field, and then rely upon the dielectric strength of the sulfur hexafluoride (SF6) to quench the stretched arc.

Vacuum circuit breakers have minimal arcing (as there is nothing to ionize other than the contact material). The arc is quenched when it is stretched a very small amount (less than 3 mm (0.1 in)). Vacuum circuit breakers are frequently used in modern medium-voltage switch gear to 38000 volts.

Air circuit breakers may use compressed air to blow out the arc, or alternatively, the contacts are rapidly swung into a small sealed chamber, the escaping of the displaced air thus blowing out the arc.

Circuit breakers are usually able to terminate all current very quickly: typically the arc is extinguished between 30 ms and 150 ms after the mechanism has been tripped, depending upon age and construction of the device. The maximum current value and let-through energy determine the quality of the circuit breakers.

Short circuit

Circuit breakers are rated both by the normal current that they are expected to carry, and the maximum short-circuit current that they can safely interrupt. This latter figure is the ampere interrupting capacity (AIC) of the breaker.

Under short-circuit conditions, the calculated or measured maximum prospective short-circuit current may be many times the normal, rated current of the circuit. When electrical contacts open to interrupt a large current, there is a tendency for an arc to form between the opened contacts, which would allow the current to continue. This condition can create conductive ionized gases and molten or vaporized metal, which can cause the further continuation of the arc or create additional short circuits, potentially resulting in the explosion of the circuit breaker and the equipment that it is installed in. Therefore, circuit breakers incorporate various features to divide and extinguish the arcs.

The maximum short-circuit current that a breaker can interrupt is determined by testing. Application of a breaker in a circuit with a prospective short-circuit current higher than the breaker's interrupting capacity rating may result in failure of the breaker to safely interrupt a fault. In a worst-case scenario, a breaker may successfully interrupt a fault only to explode when reset.

Typical domestic panel circuit breakers are rated to interrupt 6  kA (6000 A) short-circuit current.

Miniature circuit breakers used to protect control circuits or small appliances may not have sufficient interrupting capacity to use at a panel board; these circuit breakers are called "supplemental circuit protectors" to distinguish them from distribution-type circuit breakers.

Standard current ratings

Time till trip versus current as multiple of nominal current Standard Trip Characteristic of a Thermomagnetic Circuit Breaker.svg
Time till trip versus current as multiple of nominal current

Circuit breakers are manufactured with standard ratings, using a system of preferred numbers to create a useful selection of ratings. A miniature circuit breaker has a fixed trip setting; changing the operating current value requires replacing the whole circuit breaker. Circuit breakers with higher ratings can have adjustable trip settings, allowing fewer standardized products to be used, adjusted to the applicable precise ratings when installed. For example, a circuit breaker with a 400 ampere frame size might have its over-current detection threshold set only 300 amperes where that rating is appropriate.

For low-voltage distribution circuit breakers an international standard, IEC 60898-1, defines rated current as the maximum current that a breaker is designed to carry continuously. The commonly available preferred values for rated current are 1 A, 2 A, 4 A, 6 A, 10 A, 13 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A, 63 A, 80 A, 100 A, [5] and 125 A. The circuit breaker is labeled with the rated current in amperes prefixed by a letter, which indicates the instantaneous tripping current that causes the circuit breaker to trip without intentional time delay expressed in multiples of the rated current:

TypeInstantaneous tripping current
B3–5 times rated current In, e.g. a nominally 10 A device will trip at 30–50 A
C5–10 times In
D10–20 times In
K8–12 times In

For the protection of loads that cause frequent short-duration (approximately 400 ms to 2 s) current peaks in normal operation

Z2–3 times In for durations on the order of tens of seconds.

For the protection of loads such as semiconductor devices or measuring circuits using current transformers.

Circuit breakers are also rated by the maximum fault current that they can interrupt; this allows use of more economical devices on systems unlikely to develop the high short-circuit current found on, for example, a large commercial building distribution system.

In the United States, Underwriters Laboratories (UL) certifies equipment ratings, called Series Ratings (or "integrated equipment ratings") for circuit breaker equipment used for buildings. Power circuit breakers and medium- and high-voltage circuit breakers used for industrial or electric power systems are designed and tested to ANSI or IEEE standards in the C37 series. For example, standard C37.16 lists preferred frame size current ratings for power circuit breakers in the range of 600 to 5000 amperes. Trip current settings and time–current characteristics of these breakers are generally adjustable.

For medium- and high-voltage circuit breakers used in switchgear, substations and generating stations, relatively few standard frame sizes are generally manufactured. These circuit breakers are usually controlled by separate protective relay systems, offering adjustable tripping current and time settings as well as allowing for more complex protection schemes.

Types

Front panel of a 1250 A air circuit breaker manufactured by ABB. This low-voltage power circuit breaker can be withdrawn from its housing for servicing. Trip characteristics are configurable via DIP switches on the front panel. LargeCircuitBreaker.jpg
Front panel of a 1250 A air circuit breaker manufactured by ABB. This low-voltage power circuit breaker can be withdrawn from its housing for servicing. Trip characteristics are configurable via DIP switches on the front panel.

Many classifications of circuit breakers can be made, based on their features such as voltage class, construction type, interrupting type, and structural features.

Low-voltage

Low-voltage (less than 1,000 VAC) types are common in domestic, commercial and industrial application, and include:

The characteristics of low-voltage circuit breakers are given by international standards such as IEC 947. These circuit breakers are often installed in draw-out enclosures that allow removal and interchange without dismantling the switchgear.

Large low-voltage molded-case and power circuit breakers may have electric motor operators so they can open and close under remote control. These may form part of an automatic transfer switch system for standby power.

Low-voltage circuit breakers are also made for direct-current (DC) applications, such as for subway lines. Direct current requires special breakers because the arc is continuous—unlike an AC arc, which tends to go out on each half cycle, a direct-current circuit breaker has a blow-out coil that generates a magnetic field that rapidly stretches the arc. Small circuit breakers are either installed directly in equipment or arranged in breaker panels.

Inside a miniature circuit breaker Circuitbreaker.jpg
Inside a miniature circuit breaker

The DIN-rail-mounted thermal-magnetic miniature circuit breaker is the most common style in modern domestic consumer units and commercial electrical distribution boards throughout Europe. The design includes the following components:

  1. Actuator lever  used to manually trip and reset the circuit breaker. Also indicates the status of the circuit breaker (On or Off/tripped). Most breakers are designed so they can still trip even if the lever is held or locked in the "on" position. This is sometimes referred to as "free trip" or "positive trip" operation.
  2. Actuator mechanism forces the contacts together or apart.
  3. Contacts allow current when touching and break the current when moved apart.
  4. Terminals
  5. Bimetallic strip separates contacts in response to smaller, longer-term overcurrents
  6. Calibration screw  allows the manufacturer to precisely adjust the trip current of the device after assembly.
  7. Solenoid separates contacts rapidly in response to high overcurrents
  8. Arc divider/extinguisher

Solid-state

Solid-state circuit breakers (SSCBs), also known as digital circuit breakers, are a technological innovation which promises to advance circuit breaker technology out of the mechanical level, into the electrical. This promises several advantages, such as acting much more quickly (breaking circuits in fractions of microseconds), better monitoring of circuit loads and longer lifetimes. [6] Solid-state circuit breakers have been developed for medium-voltage DC power and can use silicon carbide transistors or integrated gate-commutated thyristors (IGCTs) for switching. [7] [8] [9]

Magnetic

A magnetic circuit breaker uses a solenoid (electromagnet) whose pulling force increases with the current. Certain designs utilize electromagnetic forces in addition to those of the solenoid. The circuit breaker contacts are held closed by a latch. As the current in the solenoid increases beyond the rating of the circuit breaker, the solenoid's pull releases the latch, which lets the contacts open by spring action. They are the most commonly used circuit breakers in the United States.

Thermal–magnetic

Shihlin Electric MCCB with SHT SHT-06.jpg
Shihlin Electric MCCB with SHT

A thermal–magnetic circuit breaker, which is the type found in most distribution boards in Europe and countries with a similar wiring arrangement, incorporates both techniques with the electromagnet responding instantaneously to large surges in current (such as short circuits) and the bimetallic strip responding to lesser but longer-term over-current conditions. The thermal portion of the circuit breaker provides a time-response feature that trips the circuit breaker sooner for larger over-currents but allows smaller overloads to persist for a longer time. This allows short current spikes such as are produced when a motor or other non-resistive load is switched on. With a very large over-current, such as may be caused short circuit, the magnetic element trips the circuit breaker with no intentional additional delay. [10]

Magnetic–hydraulic

A magnetic–hydraulic circuit breaker uses a solenoid coil to provide operating force to open the contacts. A magnetic–hydraulic breaker incorporates a hydraulic time delay feature using a viscous fluid. A spring restrains the core until the current exceeds the breaker rating. During an overload, the speed of the solenoid motion is restricted by the fluid. The delay permits brief current surges beyond normal running current for motor starting, energizing equipment, etc. Short-circuit currents provide sufficient solenoid force to release the latch regardless of core position thus bypassing the delay feature. Ambient temperature affects the time delay but does not affect the current rating of a magnetic breaker. [11]

A large power circuit breaker, such as one applied in circuits of more than 1000 volts, may incorporate hydraulic elements in the contact operating mechanism. Hydraulic energy may be supplied by a pump or stored in accumulators. These form a distinct type from oil-filled circuit breakers where oil is the arc-extinguishing medium. [12]

Common-trip (ganged) breakers

Three-pole common-trip breaker for supplying a three-phase device. This breaker has a 2 A rating. Breaker3phase2a proc.jpg
Three-pole common-trip breaker for supplying a three-phase device. This breaker has a 2 A rating.

To provide simultaneous breaking on multiple circuits from a fault on any one, circuit breakers may be made as a ganged assembly. This is a very common requirement for three-phase systems, where breaking may be either three- or four-pole (solid or switched neutral). Some makers make ganging kits to allow groups of single-phase breakers to be interlinked as required.

In the US, where split-phase supplies are common, in a branch circuit with more than one live conductor, each live conductor must be protected by a breaker pole. To ensure that all live conductors are interrupted when any pole trips, a common-trip set of breakers must be used. These may either contain two or three tripping mechanisms within one case or, for small breakers, have the breakers externally tied together via their operating handles. Two-pole common-trip breakers are common on 120/240-volt systems where 240 volt loads (including major appliances or further distribution boards) span the two live wires. Three-pole common-trip breakers are typically used to supply three-phase power to powerful motors or further distribution boards.

Separate circuit breakers must never be used for live and neutral, because if the neutral is disconnected while the live conductor stays connected, a very dangerous condition arises: the circuit appears de-energized (appliances don't work), but wires remain live and some residual-current devices (RCDs) may not trip if someone touches the live wire (because some RCDs need power to trip). This is why only common-trip breakers must be used when neutral wire switching is needed.

Shunt-trip units

A shunt-trip unit appears similar to a normal breaker and the moving actuators are ganged to a normal breaker mechanism to operate together in a similar way, but the shunt trip is a solenoid intended to be operated by an external constant-voltage signal, rather than a current, commonly the local mains voltage or   DC. These are often used to cut the power when a high-risk event occurs, such as a fire or flood alarm, or another electrical condition, such as over-voltage detection. Shunt trips may be a user-fitted accessory to a standard breaker or supplied as an integral part of a circuit breaker.

Medium-voltage

A Siemens air circuit breaker rated for 1000 V and 2500 A continuous current mounted on a motor control cubicle Siemens WL II 2500N air circuit breaker.jpg
A Siemens air circuit breaker rated for 1000 V and 2500 A continuous current mounted on a motor control cubicle

Medium-voltage circuit breakers rated between 1 and 72 kV may be assembled into metal-enclosed switchgear line-ups for indoor use or may be individual components installed outdoors in a substation. Air-break circuit breakers replaced oil-filled units for indoor applications, but are now themselves being replaced by vacuum circuit breakers (up to about 40.5 kV). Like the high-voltage circuit breakers described below, these are also operated by current-sensing protective relays operated through current transformers. The characteristics of MV breakers are given by international standards such as IEC 62271. Medium-voltage circuit breakers nearly always use separate current sensors and protective relays instead of relying on built-in thermal or magnetic overcurrent sensors.

Medium-voltage circuit breakers can be classified by the medium used to extinguish the arc:

Medium-voltage circuit breakers may be connected into the circuit by bolted connections to bus bars or wires, especially in outdoor switchyards. Medium-voltage circuit breakers in switchgear line-ups are often built with draw-out construction, allowing breaker removal without disturbing power circuit connections, using a motor-operated or hand-cranked mechanism to separate the breaker from its enclosure.

High-voltage

Three single-phase Soviet/Russian 110-kV oil circuit breakers Oil circuit breaker MKP-110 Toliatti Russia.jpg
Three single-phase Soviet/Russian 110-kV oil circuit breakers
400 kV SF6 live-tank circuit breakers 400kv.jpg
400 kV SF6 live-tank circuit breakers

Electrical power transmission networks are protected and controlled by high-voltage breakers. The definition of high voltage varies but in power transmission work is usually thought to be 72.5 kV or higher, according to a recent definition by the International Electrotechnical Commission (IEC). High-voltage breakers are nearly always solenoid-operated, with current sensing protective relays operated through current transformers. In substations the protective relay scheme can be complex, protecting equipment and buses from various types of overload or ground/earth fault.

High-voltage breakers are broadly classified by the medium used to extinguish the arc:

Due to environmental and cost concerns over insulating oil spills, most new breakers use SF6 gas to quench the arc.

Circuit breakers can be classified as live tank, where the enclosure that contains the breaking mechanism is at line potential, or dead tank with the enclosure at earth potential. High-voltage AC circuit breakers are routinely available with ratings up to 765 kV. 1,200 kV breakers were launched by Siemens in November 2011, [14] followed by ABB in April the following year. [15]

High-voltage circuit breakers used on transmission systems may be arranged to allow a single pole of a three-phase line to trip, instead of tripping all three poles; for some classes of faults this improves the system stability and availability.

High-voltage direct current circuit breakers are still a field of research as of 2015. Such breakers would be useful to interconnect HVDC transmission systems. [16]

Sulfur hexafluoride (SF6) high-voltage

A sulfur hexafluoride circuit breaker uses contacts surrounded by sulfur hexafluoride gas to quench the arc. They are most often used for transmission-level voltages and may be incorporated into compact gas-insulated switchgear. In cold climates, supplemental heating or different gas mixtures are used for high voltage circuit breakers, due to liquefaction of the SF6 gas. In some northern power grids, gas mixtures of N2 and SF6, or CF4 and SF6 are installed in puffer-type HVCB to quench the arc without any liquefaction of the gas. https://ieeexplore.ieee.org/abstract/document/4080767. The minimum temperature ratings of these models are as low as -50 °C for some northern substations.

Disconnecting circuit breaker (DCB)

The disconnecting circuit breaker (DCB) was introduced in 2000 [17] and is a high-voltage circuit breaker modeled after the SF6-breaker. It presents a technical solution where the disconnecting function is integrated in the breaking chamber, eliminating the need for separate disconnectors. This increases the availability, since open-air disconnecting switch main contacts need maintenance every 2–6 years, while modern circuit breakers have maintenance intervals of 15 years. Implementing a DCB solution also reduces the space requirements within the substation, and increases the reliability, due to the lack of separate disconnectors. [18] [19]

In order to further reduce the required space of substation, as well as simplifying the design and engineering of the substation, a fiber optic current sensor (FOCS) can be integrated with the DCB. A 420 kV DCB with integrated FOCS can reduce a substation's footprint with over 50% compared to a conventional solution of live tank breakers with disconnectors and current transformers, due to reduced material and no additional insulation medium. [20]

Carbon dioxide (CO2) high-voltage

In 2012, ABB presented a 75 kV high-voltage breaker that uses carbon dioxide as the medium to extinguish the arc. The carbon dioxide breaker works on the same principles as an SF6 breaker and can also be produced as a disconnecting circuit breaker. By switching from SF6 to CO2, it is possible to reduce the CO2 emissions by 10 tons during the product's life cycle. [21]

"Smart" circuit breakers

Several firms have looked at adding monitoring for appliances via electronics or using a digital circuit breaker to monitor the breakers remotely. Utility companies in the United States have been reviewing use of the technology to turn appliances on and off, as well as potentially turning off charging of electric cars during periods of high electrical grid load. These devices under research and testing would have wireless capability to monitor the electrical usage in a house via a smartphone app or other means. [22]

Other breakers

Residual current circuit breaker with overcurrent protection ABB RCBO.jpg
Residual current circuit breaker with overcurrent protection

The following types are described in separate articles.

See also

Related Research Articles

<span class="mw-page-title-main">Relay</span> Electrically-operated switch

A relay is an electrically operated switch. It consists of a set of input terminals for a single or multiple control signals, and a set of operating contact terminals. The switch may have any number of contacts in multiple contact forms, such as make contacts, break contacts, or combinations thereof.

<span class="mw-page-title-main">Electrical substation</span> Part of an electrical transmission, and distribution system

A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. There are 55,000 substations in the United States.

<span class="mw-page-title-main">Residual-current device</span> Electrical safety device used in household wiring

A residual-current device (RCD), residual-current circuit breaker (RCCB) or ground fault circuit interrupter (GFCI) is an electrical safety device that interrupts an electrical circuit when the current passing through a conductor is not equal and opposite in both directions, therefore indicating an improper flow of current such as leakage current to ground or current flowing to another powered conductor. The device's purpose is to reduce the severity of injury caused by an electric shock. Injury from shock is limited to the time before the electrical circuit is interrupted, but the victim may also sustain further injury, e.g. by falling after receiving a shock. This type of circuit interrupter can not distinguish between current flowing though power carrying conductors that passes through a person from current that passes through electrical equipment and offer no protection when a person touches both conductors at the same time.

A motor controller is a device or group of devices that can coordinate in a predetermined manner the performance of an electric motor. A motor controller might include a manual or automatic means for starting and stopping the motor, selecting forward or reverse rotation, selecting and regulating the speed, regulating or limiting the torque, and protecting against overloads and electrical faults. Motor controllers may use electromechanical switching, or may use power electronics devices to regulate the speed and direction of a motor.

<span class="mw-page-title-main">Fuse (electrical)</span> Electrical safety device that provides overcurrent protection

In electronics and electrical engineering, a fuse is an electrical safety device that operates to provide overcurrent protection of an electrical circuit. Its essential component is a metal wire or strip that melts when too much current flows through it, thereby stopping or interrupting the current. It is a sacrificial device; once a fuse has operated, it is an open circuit, and must be replaced or rewired, depending on its type.

<span class="mw-page-title-main">Arc-fault circuit interrupter</span> Circuit breaker that protects against intermittent faults associated with arcing

An arc-fault circuit interrupter (AFCI) or arc-fault detection device (AFDD) is a circuit breaker that breaks the circuit when it detects the electric arcs that are a signature of loose connections in home wiring. Loose connections, which can develop over time, can sometimes become hot enough to ignite house fires. An AFCI selectively distinguishes between a harmless arc, and a potentially dangerous arc.

<span class="mw-page-title-main">Electric arc</span> Electrical breakdown of a gas that results in an ongoing electrical discharge

An electric arc is an electrical breakdown of a gas that produces a prolonged electrical discharge. The current through a normally nonconductive medium such as air produces a plasma, which may produce visible light. An arc discharge is initiated either by thermionic emission or by field emission. After initiation, the arc relies on thermionic emission of electrons from the electrodes supporting the arc. An arc discharge is characterized by a lower voltage than a glow discharge. An archaic term is voltaic arc, as used in the phrase "voltaic arc lamp".

<span class="mw-page-title-main">Current transformer</span> Transformer used to scale alternating current, used as sensor for AC power

A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary.

<span class="mw-page-title-main">Recloser</span>

In electric power distribution, automatic circuit reclosers (ACRs) are a class of switchgear designed for use on overhead electricity distribution networks to detect and interrupt transient faults. Also known as reclosers or autoreclosers, ACRs are essentially rated circuit breakers with integrated current and voltage sensors and a protection relay, optimized for use as a protection asset. Commercial ACRs are governed by the IEC 62271-111/IEEE Std C37.60 and IEC 62271-200 standards. The three major classes of operating maximum voltage are 15.5 kV, 27 kV and 38 kV.

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

<span class="mw-page-title-main">Electronic component</span> Discrete device in an electronic system

An electronic component is any basic discrete electronic device or physical entity part of an electronic system used to affect electrons or their associated fields. Electronic components are mostly industrial products, available in a singular form and are not to be confused with electrical elements, which are conceptual abstractions representing idealized electronic components and elements. A datasheet for an electronic component is a technical document that provides detailed information about the component's specifications, characteristics, and performance.

<span class="mw-page-title-main">Contactor</span> Electronic circuit element serving as a switch

A contactor is an electrically controlled switch used for switching an electrical power circuit. A contactor is typically controlled by a circuit which has a much lower power level than the switched circuit, such as a 24-volt coil electromagnet controlling a 230-volt motor switch.

<span class="mw-page-title-main">Arcing horns</span>

Arcing horns are projecting conductors used to protect insulators or switch hardware on high voltage electric power transmission systems from damage during flashover. Overvoltages on transmission lines, due to atmospheric electricity, lightning strikes, or electrical faults, can cause arcs across insulators (flashovers) that can damage them. Alternately, atmospheric conditions or transients that occur during switching can cause an arc to form in the breaking path of a switch during its operation. Arcing horns provide a path for flashover to occur that bypasses the surface of the protected device. Horns are normally paired on either side of an insulator, one connected to the high voltage part and the other to ground, or at the breaking point of a switch contact. They are frequently to be seen on insulator strings on overhead lines, or protecting transformer bushings.

<span class="mw-page-title-main">Arc flash</span> Heat and light produced during an electrical arc fault

An arc flash is the light and heat produced as part of an arc fault, a type of electrical explosion or discharge that results from a connection through air to ground or another voltage phase in an electrical system.

In Electrical Power Systems and Industrial Automation, ANSI Device Numbers can be used to identify equipment and devices in a system such as relays, circuit breakers, or instruments. The device numbers are enumerated in ANSI/IEEE Standard C37.2 "Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations".

<span class="mw-page-title-main">High-voltage switchgear</span>

High voltage switchgear is any switchgear used to connect or disconnect a part of a high-voltage power system. This equipment is essential for the protection and safe operation, without interruption, of a high voltage power system, and is important because it is directly linked to the quality of the electricity supply.

<span class="mw-page-title-main">Sulfur hexafluoride circuit breaker</span> Switching device used in high voltage power grids

Sulfur hexafluoride circuit breakers protect electrical power stations and distribution systems by interrupting electric currents, when tripped by a protective relay. Instead of oil, air, or a vacuum, a sulfur hexafluoride circuit breaker uses sulfur hexafluoride (SF6) gas to cool and quench the arc on opening a circuit. Advantages over other media include lower operating noise and no emission of hot gases, and relatively low maintenance. Developed in the 1950s and onward, SF6 circuit breakers are widely used in electrical grids at transmission voltages up to 800 kV, as generator circuit breakers, and in distribution systems at voltages up to 35 kV.

A hybrid switchgear is one that combines the components of traditional air-insulated switchgear (AIS) and SF6 gas-insulated switchgear (GIS) technologies. It is characterized by a compact and modular design, which encompasses several different functions in one module.

A high-resistance connection (HRC) is a hazard that results from loose or poor connections in traditional electrical accessories and switchgear which can cause heat to develop, capable of starting a fire.

<span class="mw-page-title-main">Vacuum interrupter</span>

In electrical engineering, a vacuum interrupter is a switch which uses electrical contacts in a vacuum. It is the core component of medium-voltage circuit-breakers, generator circuit-breakers, and high-voltage circuit-breakers. Separation of the electrical contacts results in a metal vapour arc, which is quickly extinguished. Vacuum interrupters are widely used in utility power transmission systems, power generation unit, and power-distribution systems for railways, arc furnace applications, and industrial plants.

References

  1. Robert Friedel and Paul Israel, Edison's Electric Light: Biography of an Invention, Rutgers University Press, New Brunswick New Jersey USA,1986 ISBN   0-8135-1118-6 pp.65-66
  2. ""1920-1929 Stotz miniature circuit breaker and domestic appliances", ABB, 2006-01-09, accessed 4 July 2011". Archived from the original on 2013-10-29. Retrieved 2011-07-04.
  3. Flurscheim, Charles H., ed. (1982). "Chapter 1". Power Circuit Breaker Theory and Design (Second ed.). IET. ISBN   0-906048-70-2.
  4. Weedy, B. M. (1972). Electric Power Systems (Second ed.). London: John Wiley and Sons. pp.  428–430. ISBN   0-471-92445-8.
  5. "What is an MCB and how does it work?". Fusebox Shop. 16 September 2016. Archived from the original on 11 July 2018. Retrieved 11 July 2018.
  6. "Solid State Circuit Breaker". Archived from the original on 2022-01-25. Retrieved 2018-11-14.
  7. "Atom Power is Launching the Era of Digital Circuit Breakers IEEE Spectrum".
  8. Rodrigues, Rostan; Du, Yu; Antoniazzi, Antonello; Cairoli, Pietro (2021). "A Review of Solid-State Circuit Breakers". IEEE Transactions on Power Electronics. 36 (1): 364–377. Bibcode:2021ITPE...36..364R. doi:10.1109/TPEL.2020.3003358. S2CID   221590105.
  9. https://web.archive.org/web/20181222212258/http://www.divtecs.com:80/data/File/papers/PDF/mvdc_full%20paper.pdf
  10. John Matthews Introduction to the Design and Analysis of Building Electrical Systems Springer 1993 0442008740 page 86
  11. Hwaiyu Geng, Data Center Handbook, John Wiley & Sons,2014 page 542
  12. G R Jones (ed), Electrical Engineer's Reference Book, Butterworth Heinemann Ltd, 1993, page 25/14
  13. A few manufacturers now offer a single-bottle vacuum breaker rated up to 72.5 kV and even 145 kV. See https://www.edu-right.com/full-knowledge-about-integrated%5B%5D Electrical Engineering in India, vol 157 issue 4 pages 13-23
  14. "Siemens launches world's first 1200kV SF6 Circuit Breaker". Archived from the original on 3 July 2013. Retrieved 14 November 2011.
  15. "ABB to develop ultra high voltage circuit breaker". Utilities Middle East. 16 April 2012. Archived from the original on 4 March 2016. Retrieved 14 August 2012.
  16. "High Voltage DC Switch Enables Supergrids for Renewable Energy, MIT Technology Review" . Retrieved 19 July 2013.
  17. "Applications of Disconnecting Circuit Breakers, Michael Faxå, p.1" (PDF). Archived from the original (PDF) on 16 May 2013. Retrieved 9 July 2012.
  18. "HPL Disconnecting Circuit Breaker". Archived from the original on 20 February 2014. Retrieved 9 July 2012.
  19. "Disconnecting Circuit Breakers, Buyer's and Application Guide, p. 10" (PDF). Archived (PDF) from the original on 5 December 2020. Retrieved 15 September 2014.
  20. "362 – 550 kV Disconnecting Circuit Breaker with FOCS: Small, smart and flexible, p.1". Archived from the original on 11 May 2020. Retrieved 3 July 2013.
  21. "Switzerland: ABB breaks new ground with environment friendly high-voltage circuit breaker". Archived from the original on 24 December 2019. Retrieved 7 June 2013.
  22. "Smart circuit-breakers for energy-efficient homes". The Economist. 2017-11-23. Archived from the original on 2018-01-15. Retrieved 2018-01-15.

Sources