Power system protection

Last updated

Power system protection is a branch of electrical power engineering that deals with the protection of electrical power systems from faults [ citation needed ] through the disconnection of faulted parts from the rest of the electrical network. The objective of a protection scheme is to keep the power system stable by isolating only the components that are under fault, whilst leaving as much of the network as possible in operation. The devices that are used to protect the power systems from faults are called protection devices.

Contents

Components

Protection systems usually comprise five components

For parts of a distribution system, fuses are capable of both sensing and disconnecting faults.

Failures may occur in each part, such as insulation failure, fallen or broken transmission lines, incorrect operation of circuit breakers, short circuits and open circuits. Protection devices are installed with the aims of protection of assets and ensuring continued supply of energy.

Switchgear is a combination of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switches are safe to open under normal load current (some switches are not safe to operate under normal or abnormal conditions), while protective devices are safe to open under fault current. Very important equipment may have completely redundant and independent protective systems, while a minor branch distribution line may have very simple low-cost protection. [1]

A digital (numeric) multifunction protective relay for distribution networks. A single such device can replace many single-function electromechanical relays, and provides self-testing and communication functions. Protective relay.jpg
A digital (numeric) multifunction protective relay for distribution networks. A single such device can replace many single-function electromechanical relays, and provides self-testing and communication functions.

Types of protection

High-voltage transmission network

Protection of the transmission and distribution system serves two functions: protection of the plant and protection of the public (including employees). At a basic level, protection disconnects equipment that experiences an overload or a short to earth. Some items in substations such as transformers might require additional protection based on temperature or gas pressure, among others.

Generator sets

In a power plant, the protective relays are intended to prevent damage to alternators or to the transformers in case of abnormal conditions of operation, due to internal failures, as well as insulating failures or regulation malfunctions. Such failures are unusual, so the protective relays have to operate very rarely. If a protective relay fails to detect a fault, the resulting damage to the alternator or to the transformer might require costly equipment repairs or replacement, as well as income loss from the inability to produce and sell energy.

Overload and back-up for distance (overcurrent)

Overload protection requires a current transformer which simply measures the current in a circuit and compares it to the predetermined value. There are two types of overload protection: instantaneous overcurrent (IOC) and time overcurrent (TOC). Instantaneous overcurrent requires that the current exceeds a predetermined level for the circuit breaker to operate. Time overcurrent protection operates based on a current vs time curve. Based on this curve, if the measured current exceeds a given level for the preset amount of time, the circuit breaker or fuse will operate. The function of both types is explained in "Non-Directional Overcurrent Protection" on YouTube.

Earth fault/ground fault

Earth fault protection also requires current transformers and senses an imbalance in a three-phase circuit. Normally the three phase currents are in balance, i.e. roughly equal in magnitude. If one or two phases become connected to earth via a low impedance path, their magnitudes will increase dramatically, as will current imbalance. If this imbalance exceeds a pre-determined value, a circuit breaker should operate. Restricted earth fault protection is a type of earth fault protection which looks for earth fault between two sets of current transformers [2] (hence restricted to that zone).

Distance (impedance relay)

Distance protection detects both voltage and current. A fault on a circuit will generally create a sag in the voltage level. If the ratio of voltage to current measured at the relay terminals, which equates to an impedance, lands within a predetermined level the circuit breaker will operate. This is useful for reasonably long lines, lines longer than 10 miles, because their operating characteristics are based on the line characteristics. This means that when a fault appears on the line the impedance setting in the relay is compared to the apparent impedance of the line from the relay terminals to the fault. If the relay setting is determined to be below the apparent impedance it is determined that the fault is within the zone of protection. When the transmission line length is too short, less than 10 miles, distance protection becomes more difficult to coordinate. In these instances the best choice of protection is current differential protection.[ citation needed ]

Back-up

The objective of protection is to remove only the affected portion of plant and nothing else. A circuit breaker or protection relay may fail to operate. In important systems, a failure of primary protection will usually result in the operation of back-up protection. Remote back-up protection will generally remove both the affected and unaffected items of plant to clear the fault. Local back-up protection will remove the affected items of the plant to clear the fault.

Low-voltage networks

The low-voltage network generally relies upon fuses or low-voltage circuit breakers to remove both overload and earth faults.

Cybersecurity

The bulk system which is a large interconnected electrical system including transmission and control system is experiencing new cybersecurity threats every day. (“Electric Grid Cybersecurity,” 2019). Most of these attacks are aiming the control systems in the grids. These control systems are connected to the internet and makes it easier for hackers to attack them. These attacks can cause damage to equipment and limit the utility professionals ability to control the system.

Coordination

Protective device coordination is the process of determining the "best fit" timing of current interruption when abnormal electrical conditions occur. The goal is to minimize an outage to the greatest extent possible. Historically, protective device coordination was done on translucent log–log paper. Modern methods normally include detailed computer based analysis and reporting.

Protection coordination is also handled through dividing the power system into protective zones. If a fault were to occur in a given zone, necessary actions will be executed to isolate that zone from the entire system. Zone definitions account for generators, buses, transformers, transmission and distribution lines, and motors. Additionally, zones possess the following features: zones overlap, overlap regions denote circuit breakers, and all circuit breakers in a given zone with a fault will open in order to isolate the fault. Overlapped regions are created by two sets of instrument transformers and relays for each circuit breaker. They are designed for redundancy to eliminate unprotected areas; however, overlapped regions are devised to remain as small as possible such that when a fault occurs in an overlap region and the two zones which encompass the fault are isolated, the sector of the power system which is lost from service is still small despite two zones being isolated. [3]

Disturbance-monitoring equipment

Disturbance-monitoring equipment (DME) monitors and records system data pertaining to a fault. DME accomplish three main purposes:

DME devices include: [5]

Performance measures

Protection engineers define dependability as the tendency of the protection system to operate correctly for in-zone faults. They define security as the tendency not to operate for out-of-zone faults. Both dependability and security are reliability issues. Fault tree analysis is one tool with which a protection engineer can compare the relative reliability of proposed protection schemes. Quantifying protection reliability is important for making the best decisions on improving a protection system, managing dependability versus security tradeoffs, and getting the best results for the least money. A quantitative understanding is essential in the competitive utility industry. [6] [7]

Reliability: Dependability vs Security

There are two aspects of reliable operation of protection systems: dependability and security. [8] Dependability is the ability of the protection system to operate when called upon to remove a faulted element from the power system. Security is the ability of the protection system to restrain itself from operating during an external fault. Choosing the appropriate balance between security and dependability in designing the protection system requires engineering judgement and varies on a case-by-case basis.

See also

Notes

  1. Alexandra Von Meier (2013). Electrical Engineer 137A: Electric Power Systems. Lecture 14:Introduction to Protection Systems, Slide 3.
  2. "Restricted Earth Fault Protection". myElectrical.com. Retrieved 2 July 2013.
  3. Glover J. D., Sarma M. S., Overbye T. J. (2010) Power System and Analysis 5th Edition. Cengage Learning. Pg 548-549.
  4. "System Protection Manual" (PDF). New York Independent System Operator . Retrieved 2011-12-31.
  5. "Glossary of Terms Used in Reliability Standards" (PDF). North American Electric Reliability Corporation . Retrieved 2011-12-31.
  6. Kumm, John J.; Weber, Mark S.; Schweitzer, E. O.; Hou, Daqing (March 1995). Philosophies for Testing Protective Relays (PDF). NETA International Electrical Testing Association Technical Conference.
  7. Kumm, John J.; Schweitzer, Edmund O.; Hou, Daqing (May 1995). Assessing the Effectiveness of Self-Tests and Other Monitoring Means in Protective Relays (PDF). 1995 Pennsylvania Electric Association Relay Committee Spring Meeting.
  8. NERC Reliability Fundamentals of System Protection, December 2010, Sec 3 - 4.1.2.3, https://www.nerc.com/comm/PC/System%20Protection%20and%20Control%20Subcommittee%20SPCS%20DL/Protection%20System%20Reliability%20Fundamentals_Approved_20101208.pdf

Related Research Articles

<span class="mw-page-title-main">Ground (electricity)</span> Reference point in an electrical circuit from which voltages are measured

In electrical engineering, ground or earth may be a reference point in an electrical circuit from which voltages are measured, a common return path for electric current, or a direct physical connection to the Earth.

<span class="mw-page-title-main">Short circuit</span> Electrical circuit with negligible impedance

A short circuit is an electrical circuit that allows a current to travel along an unintended path with no or very low electrical impedance. This results in an excessive current flowing through the circuit. The opposite of a short circuit is an open circuit, which is an infinite resistance between two nodes.

<span class="mw-page-title-main">Circuit breaker</span> Automatic circuit protection device

A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by current in excess of that which the equipment can safely carry (overcurrent). Its basic function is to interrupt current flow to protect equipment and to prevent fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.

<span class="mw-page-title-main">Substation</span> Part of an electrical transmission, and distribution system

A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. There are 55,000 substations in the United States.

<span class="mw-page-title-main">Fuse (electrical)</span> Electrical safety device that provides overcurrent protection

In electronics and electrical engineering, a fuse is an electrical safety device that operates to provide overcurrent protection of an electrical circuit. Its essential component is a metal wire or strip that melts when too much current flows through it, thereby stopping or interrupting the current. It is a sacrificial device; once a fuse has operated, it is an open circuit, and must be replaced or rewired, depending on its type.

<span class="mw-page-title-main">Ground and neutral</span> In mains electricity, part of a circuit connected to ground or earth

In electrical engineering, ground and neutral are circuit conductors used in alternating current (AC) electrical systems. The neutral conductor receives and returns alternating current to the supply during normal operation of the circuit; to limit the effects of leakage current from higher-voltage systems, the neutral conductor is often connected to earth ground at the point of supply. By contrast, a ground conductor is not intended to carry current for normal operation, but instead connects exposed metallic components to earth ground. A ground conductor only carries significant current if there is a circuit fault that would otherwise energize exposed conductive parts and present a shock hazard. In that case, circuit protection devices may detect a fault to a grounded metal enclosure and automatically de-energize the circuit, or may provide a warning of a ground fault.

Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.

The prospective short-circuit current (PSCC), available fault current, or short-circuit making current is the highest electric current which can exist in a particular electrical system under short-circuit conditions. It is determined by the voltage and impedance of the supply system. It is of the order of a few thousand amperes for a standard domestic mains electrical installation, but may be as low as a few milliamperes in a separated extra-low voltage (SELV) system or as high as hundreds of thousands of amps in large industrial power systems. The term is used in electrical engineering rather than electronics.

<span class="mw-page-title-main">Current transformer</span> Transformer used to scale alternating current, used as sensor for AC power

A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary.

<span class="mw-page-title-main">Recloser</span> Electricity distribution networks circuit breakers

In electric power distribution, automatic circuit reclosers (ACRs) are a class of switchgear designed for use on overhead electricity distribution networks to detect and interrupt transient faults. Also known as reclosers or autoreclosers, ACRs are essentially rated circuit breakers with integrated current and voltage sensors and a protection relay, optimized for use as a protection asset. Commercial ACRs are governed by the IEC 62271-111/IEEE Std C37.60 and IEC 62271-200 standards. The three major classes of operating maximum voltage are 15.5 kV, 27 kV and 38 kV.

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

In electric power distribution and transmission, a Buchholz relay is a safety device mounted on some oil-filled power transformers and reactors, equipped with an external overhead oil reservoir called a "conservator".

Power-system automation is the act of automatically controlling the power system via instrumentation and control devices. Substation automation refers to using data from Intelligent electronic devices (IED), control and automation capabilities within the substation, and control commands from remote users to control power-system devices.

An earthing system or grounding system (US) connects specific parts of an electric power system with the ground, typically the equipments conductive surface, for safety and functional purposes. The choice of earthing system can affect the safety and electromagnetic compatibility of the installation. Regulations for earthing systems vary among countries, though most follow the recommendations of the International Electrotechnical Commission (IEC). Regulations may identify special cases for earthing in mines, in patient care areas, or in hazardous areas of industrial plants.

<span class="mw-page-title-main">Arcing horns</span>

Arcing horns are projecting conductors used to protect insulators or switch hardware on high voltage electric power transmission systems from damage during flashover. Overvoltages on transmission lines, due to atmospheric electricity, lightning strikes, or electrical faults, can cause arcs across insulators (flashovers) that can damage them. Alternately, atmospheric conditions or transients that occur during switching can cause an arc to form in the breaking path of a switch during its operation. Arcing horns provide a path for flashover to occur that bypasses the surface of the protected device. Horns are normally paired on either side of an insulator, one connected to the high voltage part and the other to ground, or at the breaking point of a switch contact. They are frequently to be seen on insulator strings on overhead lines, or protecting transformer bushings.

In electric power systems and industrial automation, ANSI Device Numbers can be used to identify equipment and devices in a system such as relays, circuit breakers, or instruments. The device numbers are enumerated in ANSI/IEEE Standard C37.2 Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations.

In an electric power system, a fault or fault current is any abnormal electric current. For example, a short circuit is a fault in which a live wire touches a neutral or ground wire. An open-circuit fault occurs if a circuit is interrupted by a failure of a current-carrying wire or a blown fuse or circuit breaker. In three-phase systems, a fault may involve one or more phases and ground, or may occur only between phases. In a "ground fault" or "earth fault", current flows into the earth. The prospective short-circuit current of a predictable fault can be calculated for most situations. In power systems, protective devices can detect fault conditions and operate circuit breakers and other devices to limit the loss of service due to a failure.

<span class="mw-page-title-main">Electric power system</span> Network of electrical component deployed to generate, transmit & distribute electricity

An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The electrical grid can be broadly divided into the generators that supply the power, the transmission system that carries the power from the generating centers to the load centers, and the distribution system that feeds the power to nearby homes and industries.

<span class="mw-page-title-main">Numerical relay</span> System using algorithmic detection of electrical faults

In utility and industrial electric power transmission and distribution systems, a numerical relay is a computer-based system with software-based protection algorithms for the detection of electrical faults. Such relays are also termed as microprocessor type protective relays. They are functional replacements for electro-mechanical protective relays and may include many protection functions in one unit, as well as providing metering, communication, and self-test functions.

<span class="mw-page-title-main">Protective relay</span> Relay device designed to trip a circuit breaker when a fault is detected

In electrical engineering, a protective relay is a relay device designed to trip a circuit breaker when a fault is detected. The first protective relays were electromagnetic devices, relying on coils operating on moving parts to provide detection of abnormal operating conditions such as over-current, overvoltage, reverse power flow, over-frequency, and under-frequency.

References