Network analyzer (AC power)

Last updated

From 1929 [1] to the late 1960s, large alternating current power systems were modelled and studied on AC network analyzers (also called alternating current network calculators or AC calculating boards) or transient network analyzers. These special-purpose analog computers were an outgrowth of the DC calculating boards used in the very earliest power system analysis. By the middle of the 1950s, fifty network analyzers were in operation. [2] AC network analyzers were much used for power-flow studies, short circuit calculations, and system stability studies, but were ultimately replaced by numerical solutions running on digital computers. While the analyzers could provide real-time simulation of events, with no concerns about numeric stability of algorithms, the analyzers were costly, inflexible, and limited in the number of buses and lines that could be simulated. [3] Eventually powerful digital computers replaced analog network analyzers for practical calculations, but analog physical models for studying electrical transients are still in use.

Contents

Calculating methods

As AC power systems became larger at the start of the 20th century, with more interconnected devices, the problem of calculating the expected behavior of the systems became more difficult. Manual methods were only practical for systems of a few sources and nodes. The complexity of practical problems made manual calculation techniques too laborious or inaccurate to be useful. Many mechanical aids to calculation were developed to solve problems relating to network power systems.

DC calculating boards used resistors and DC sources to represent an AC network. A resistor was used to model the inductive reactance of a circuit, while the actual series resistance of the circuit was neglected. The principle disadvantage was the inability to model complex impedances. However, for short-circuit fault studies, the effect of the resistance component was usually small. DC boards served to produce results accurate to around 20% error, sufficient for some purposes.

Artificial lines were used to analyze transmission lines. These carefully constructed replicas of the distributed inductance, capacitance and resistance of a full-size line were used to investigate propagation of impulses in lines and to validate theoretical calculations of transmission line properties. An artificial line was made by winding layers of wire around a glass cylinder, with interleaved sheets of tin foil, to give the model proportionally the same distributed inductance and capacitance as the full-size line. Later, lumped-element approximations of transmission lines were found to give adequate precision for many calculations.

Laboratory investigations of the stability of multiple-machine systems were constrained by the use of direct-operated indicating instruments (voltmeters, ammeters, and wattmeters). To ensure that the instruments negligibly loaded the model system, the machine power level used was substantial. Some workers in the 1920s used three-phase model generators rated up to 600 kVA and 2300 volts to represent a power system. General Electric developed model systems using generators rated at 3.75 kVA. [4] It was difficult to keep multiple generators in synchronism, and the size and cost of the units was a constraint. While transmission lines and loads could be accurately scaled down to laboratory representations, rotating machines could not be accurately miniaturized and keep the same dynamic characteristics as full-sized prototypes; the ratio of machine inertia to machine frictional loss did not scale. [5]

Scale model

A network analyzer system was essentially a scale model of the electrical properties of a specific power system. Generators, transmission lines, and loads were represented by miniature electrical components with scale values in proportion to the modeled system. [6] Model components were interconnected with flexible cords to represent the schematic diagram of the modeled system.

Instead of using miniature rotating machines, accurately calibrated phase-shifting transformers were built to simulate electrical machines. These were all energized by the same source (at local power frequency or from a motor-generator set) and so inherently maintained synchronism. The phase angle and terminal voltage of each simulated generator could be set using rotary scales on each phase-shifting transformer unit. Using the per-unit system allowed values to be conveniently interpreted without additional calculation.

To reduce the size of the model components, the network analyzer often was energized at a higher frequency than the 50 Hz or 60 Hz utility frequency. The operating frequency was chosen to be high enough to allow high-quality inductors and capacitors to be made, and to be compatible with the available indicating instruments, but not so high that stray capacitance would affect results. Many systems used either 440 Hz, or 480 Hz, provided by a motor-generator set, to reduce size of model components. Some systems used 10 kHz, using capacitors and inductors similar to those used in radio electronics.

Model circuits were energized at relatively low voltages to allow for safe measurement with adequate precision. The model base quantities varied by manufacturer and date of design; as amplified indicating instruments became more common, lower base quantities were feasible. Model voltages and currents started off around 200 volts and 0.5 amperes in the MIT analyzer, which still allowed directly driven (but especially sensitive) instruments to be used to measure model parameters. The later machines used as little as 50 volts and 50 mA, used with amplified indicating instruments. By use of the per-unit system, model quantities could be readily transformed into the actual system quantities of voltage, current, power or impedance. A watt measured in the model might correspond to hundreds of kilowatts or megawatts in the modeled system. One hundred volts measured on the model might correspond to one per-unit, which could represent, say, 230,000 volts on a transmission line or 11,000 volts in a distribution system. Typically, results accurate to around 2% of measurement could be obtained. [7] Model components were single-phase devices, but using the symmetrical components method, unbalanced three-phase systems could be studied as well.

A complete network analyzer was a system that filled a large room; one model was described as four bays of equipment, spanning a U-shaped arrangement 26 feet (8 metres) across. Companies such as General Electric and Westinghouse could provide consulting services based on their analyzers; but some large electrical utilities operated their own analyzers. The use of network analyzers allowed quick solutions to difficult calculation problems, and allowed problems to be analyzed that would otherwise be uneconomic to compute using manual calculations. Although expensive to build and operate, network analyzers often repaid their costs in reduced calculation time and expedited project schedules. [8] For example, a stability study might indicate if a transmission line should have larger or differently spaced conductors to preserve stability margin during system faults; potentially saving many miles of cable and thousands of insulators.

Network analyzers did not directly simulate the dynamic effects of load application to machine dynamics (torque angle, and others). Instead, the analyzer would be used to solve dynamic problems in a stepwise fashion, first calculating a load flow, then adjusting the phase angle of the machine in response to its power flow, and re-calculating the power flow.

In use, the system to be modelled would be represented as a single line diagram and all the impedances of lines and machines would be scaled to model values on the analyzer. A plugging diagram would be prepared to show the interconnections to be made between the model elements. The circuit elements would be interconnected by patch cables. The model system would be energized, and measurements taken at the points of interest in the model; these could be scaled up to the values in the full-scale system. [9]

The MIT network analyzer

The network analyzer installed at Massachusetts Institute of Technology (MIT) grew out of a 1924 thesis project by Hugh H. Spencer and Harold Locke Hazen, investigating a power system modelling concept proposed by Vannevar Bush. Instead of miniature rotating machines, each generator was represented by a transformer with adjustable voltage and phase, all fed from a common source. This eliminated a significant source of the poor accuracy of models with miniature rotating machines. The 1925 publication of this thesis attracted the attention at General Electric, where Robert Doherty was interested in modelling problems of system stability. He asked Hazen to verify that the model could accurately reproduce the behavior of machines during load changes.

Design and construction was carried out jointly by General Electric and MIT. When first demonstrated in June 1929, the system had eight phase-shifting transformers to represent synchronous machines. Other elements included 100 variable line resistors, 100 variable reactors, 32 fixed capacitors, and 40 adjustable load units. The analyzer was described in a 1930 paper by H.L Hazen, O.R. Schurig and M.F. Gardner. The base quantities for the analyzer were 200 volts, and 0.5 amperes. Sensitive portable thermocouple-type instruments were used for measurement. [10] The analyzer occupied four large panels, arranged in a U-shape, with tables in front of each section to hold measuring instruments. While primarily conceived as an educational tool, the analyzer saw considerable use by outside firms, who would pay to use the device. American Gas and Electric Company, the Tennessee Valley Authority, and many other organizations studied problems on the MIT analyzer in its first decade of operation. In 1940 the system was moved and expanded to handle more complex systems.

By 1953 the MIT analyzer was beginning to fall behind the state of the art. Digital computers were first used on power system problems as early as "Whirlwind" in 1949. Unlike most of the forty other analyzers in service by that point, the MIT instrument was energized at 60 Hz, not 440 or 480 Hz, making its components large, and expansion to new types of problems difficult. Many utility customers had bought their own network analyzers. The MIT system was dismantled and sold to the Puerto Rico Water Resources Authority in 1954. [11]

Commercial manufacturers

By 1947, fourteen network analyzers had been built at a total cost of about two million US dollars. General Electric built two full-scale network analyzers for its own work and for services to its clients. Westinghouse built systems for their internal use and provided more than 20 analyzers to utility and university clients. After the Second World War analyzers were known to be in use in France, the UK, Australia, Japan, and the Soviet Union. Later models had improvements such as centralized control of switching, central measurement bays, and chart recorders to automatically provide permanent records of results.

General Electric's Model 307 was a miniaturized AC network analyzer with four generator units and a single electronically amplified metering unit. It was targeted at utility companies to solve problems too large for hand computation but not worth the expense of renting time on a full size analyzer. Like the Iowa State College analyzer, it used a system frequency of 10 kHz instead of 60 Hz or 480 Hz, allowing much smaller radio-style capacitor and inductors to be used to model power system components. The 307 was cataloged from 1957 and had a list of about 20 utility, educational and government customers. In 1959 its list price was $8,590. [12]

In 1953, the Metropolitan Edison Company and a group of six other electrical companies purchased a new Westinghouse AC network analyzer for installation at the Franklin Institute in Philadelphia. The system, described as the largest ever built, cost $400,000. [13]

In Japan, network analyzers were installed starting in 1951. The Yokogawa Electric company introduced a model energized at 3980 Hz starting in 1956. [14]

AC Network Analyzers [15]
OwnerYearFrequencyGenerator UnitsTotal circuitsRemarks
MIT 19296016209First system in commercial use
Purdue University 194244016383Reconstructed after 1929 initial installation
Pennsylvania Railroad 19324406296
Commonwealth Edison Company 19324406186
General Electric Company193748012313
Public Service Electric and Gas Co of New Jersey19384808163
Tennessee Valley Authority 193844018270
Bonneville Power Administration 193948018326
São Paulo Tramway, Light and Power Company 1940440698Brazil
Potomac Electric Power Company 19414406120
Hydro Electric Power Commission 194144015259Ontario, Canada
Public Service Co. of Oklahoma1941607185
Westinghouse Electric Corporation 194244022384
Illinois Institute of Technology 194544012236Cost $90,000, sponsored by 17 electrical utilities [16]
Iowa State College 194610,000464Continued in commercial use until the early 1970s.
Texas A and M College 194744018344Operated until 1971 when it was sold to Lower Colorado Power Authority
City of Los Angeles 194744018266
University of Kansas 1947608133
Associated Electrical Industries, Ltd. 194750012274United Kingdom
Georgia School of Technology 194844014322Donated by Georgia Power Corp, cost $300,000 [17]
Pacific Gas and Electric Company 194844014324
Consolidated Gas, Electric Light and Power Co. of Baltimore 194844016240
United States Bureau of Reclamation 194848012240
General Electric Company (No. 2)194948012392
University of California 19494806113
Indian Institute of Science 194948016338
State Electricity Commission of Victoria 195045012--Westinghouse make, in utility service to 1967, 10 kW motor generator input, [18]
Franklin Institute 1953440-----Westinghouse make, largest system delivered to that date, cost $400,000 in 1953 dollars
Cornell University 195344018---Decommissioned mid 1960s [19]

Other applications

Transient analyzer

A "transient network analyzer" was an analog model of a transmission system especially adapted to study high-frequency transient surges (such as those due to lightning or switching), instead of AC power frequency currents. Similarly to an AC network analyzer, they represented apparatus and lines with scaled inductances and resistances. A synchronously driven switch repeatedly applied a transient impulse to the model system, and the response at any point could be observed on an oscilloscope or recorded on an oscillograph. Some transient analyzers are still in use for research and education, sometimes combined with digital protective relays or recording instruments. [20]

Anacom

The Westinghouse Anacom was an AC-energized electrical analog computer system used extensively for problems in mechanical design, structural elements, lubrication oil flow, and various transient problems including those due to lightning surges in electric power transmission systems. The excitation frequency of the computer could be varied. The Westinghouse Anacom constructed in 1948 was used up to the early 1990s for engineering calculations; its original cost was $500,000. The system was periodically updated and expanded; by the 1980s the Anacom could be run through many simulation cases unattended, under the control of a digital computer that automatically set up initial conditions and recorded the results. Westinghouse built a replica Anacom for Northwestern University, sold an Anacom to ABB, and twenty or thirty similar computers by other makers were used around the world. [9]

Physics and chemistry

Since the multiple elements of the AC network analyzer formed a powerful analog computer, occasionally problems in physics and chemistry were modeled (by such researchers as Gabriel Kron of General Electric), in the late 1940s prior to the ready availability of general-purpose digital computers. [21] Another application was water flow in water distribution systems. The forces and displacements of a mechanical system could be readily modelled with the voltages and currents of a network analyzer, which allowed easy adjustment of properties such as the stiffness of a spring by, for example, changing the value of a capacitor. [22]

Structures

The David Taylor Model Basin operated an AC network analyzer from the late 1950s until the mid-1960s. The system was used on problems in ship design. An electrical analog of the structural properties of a proposed ship, shaft, or other structure could be built, and tested for its vibrational modes. Unlike AC analyzers used for power systems work, the exciting frequency was made continuously variable so that mechanical resonance effects could be investigated.

Decline and obsolescence

Even during the Depression and the Second World War, many network analyzers were constructed because of their great value in solving calculations related to electric power transmission. By the mid 1950s, about thirty analyzers were available in the United States, representing an oversupply. Institutions such as MIT could no longer justify operating analyzers as paying clients barely covered operating expenses. [22]

Once digital computers of adequate performance became available, the solution methods developed on analog network analyzers were migrated to the digital realm, where plugboards, switches and meter pointers were replaced with punch cards and printouts. The same general-purpose digital computer hardware that ran network studies could easily be dual-tasked with business functions such as payroll. Analog network analyzers faded from general use for load-flow and fault studies, although some persisted in transient studies for a while longer. Analog analyzers were dismantled and either sold off to other utilities, donated to engineering schools, or scrapped.

The fate of a few analyzers illustrates the trend. The analyzer purchased by American Electric Power was replaced by digital systems in 1961, and donated to Virginia Tech. The Westinghouse network analyzer purchased by the State Electricity Commission of Victoria, Australia in 1950 was taken out of utility service in 1967 and donated to the Engineering department at Monash University; but by 1985, even instructional use of the analyzer was no longer practical and the system was finally dismantled. [23]

One factor contributing to the obsolescence of analog models was the increasing complexity of interconnected power systems. Even a large analyzer could only represent a few machines, and perhaps a few score lines and busses. Digital computers routinely handled systems with thousands of busses and transmission lines.

See also

Related Research Articles

<span class="mw-page-title-main">Analog computer</span> Computer that uses continuously varying data technology

An analog computer or analogue computer is a type of computer that uses the continuous variation aspect of physical phenomena such as electrical, mechanical, or hydraulic quantities to model the problem being solved. In contrast, digital computers represent varying quantities symbolically and by discrete values of both time and amplitude.

<span class="mw-page-title-main">Electric power transmission</span> Bulk movement of electrical energy

Electric power transmission is the bulk movement of electrical energy from a generating site, such as a power plant, to an electrical substation. The interconnected lines that facilitate this movement form a transmission network. This is distinct from the local wiring between high-voltage substations and customers, which is typically referred to as electric power distribution. The combined transmission and distribution network is part of electricity delivery, known as the electrical grid.

<span class="mw-page-title-main">Alternating current</span> Electric current that periodically reverses direction

Alternating current (AC) is an electric current which periodically reverses direction and changes its magnitude continuously with time, in contrast to direct current (DC), which flows only in one direction. Alternating current is the form in which electric power is delivered to businesses and residences, and it is the form of electrical energy that consumers typically use when they plug kitchen appliances, televisions, fans and electric lamps into a wall socket. The abbreviations AC and DC are often used to mean simply alternating and direct, respectively, as when they modify current or voltage.

<span class="mw-page-title-main">Alternator</span> Device converting mechanical into electrical energy

An alternator is an electrical generator that converts mechanical energy to electrical energy in the form of alternating current. For reasons of cost and simplicity, most alternators use a rotating magnetic field with a stationary armature. Occasionally, a linear alternator or a rotating armature with a stationary magnetic field is used. In principle, any AC electrical generator can be called an alternator, but usually the term refers to small rotating machines driven by automotive and other internal combustion engines.

<span class="mw-page-title-main">War of the currents</span> Introduction of competing electric power transmission systems in the late 1880s and early 1890s

The war of the currents was a series of events surrounding the introduction of competing electric power transmission systems in the late 1880s and early 1890s. It grew out of two lighting systems developed in the late 1870s and early 1880s; arc lamp street lighting running on high-voltage alternating current (AC), and large-scale low-voltage direct current (DC) indoor incandescent lighting being marketed by Thomas Edison's company. In 1886, the Edison system was faced with new competition: an alternating current system initially introduced by George Westinghouse's company that used transformers to step down from a high voltage so AC could be used for indoor lighting. Using high voltage allowed an AC system to transmit power over longer distances from more efficient large central generating stations. As the use of AC spread rapidly with other companies deploying their own systems, the Edison Electric Light Company claimed in early 1888 that high voltages used in an alternating current system were hazardous, and that the design was inferior to, and infringed on the patents behind, their direct current system.

<span class="mw-page-title-main">Utility frequency</span> Frequency used on standard electricity grid in a given area

The utility frequency, (power) line frequency or mains frequency is the nominal frequency of the oscillations of alternating current (AC) in a wide area synchronous grid transmitted from a power station to the end-user. In large parts of the world this is 50 Hz, although in the Americas and parts of Asia it is typically 60 Hz. Current usage by country or region is given in the list of mains electricity by country.

<span class="mw-page-title-main">Power engineering</span> Subfield of electrical engineering

Power engineering, also called power systems engineering, is a subfield of electrical engineering that deals with the generation, transmission, distribution, and utilization of electric power, and the electrical apparatus connected to such systems. Although much of the field is concerned with the problems of three-phase AC power – the standard for large-scale power transmission and distribution across the modern world – a significant fraction of the field is concerned with the conversion between AC and DC power and the development of specialized power systems such as those used in aircraft or for electric railway networks. Power engineering draws the majority of its theoretical base from electrical engineering and mechanical engineering.

In power engineering, the power-flow study, or load-flow study, is a numerical analysis of the flow of electric power in an interconnected system. A power-flow study usually uses simplified notations such as a one-line diagram and per-unit system, and focuses on various aspects of AC power parameters, such as voltages, voltage angles, real power and reactive power. It analyzes the power systems in normal steady-state operation.

<span class="mw-page-title-main">Motor–generator</span> Device for converting electrical power to another form

A motor–generator is a device for converting electrical power to another form. Motor–generator sets are used to convert frequency, voltage, or phase of power. They may also be used to isolate electrical loads from the electrical power supply line. Large motor–generators were widely used to convert industrial amounts of power while smaller motor–generators were used to convert battery power to higher DC voltages.

<span class="mw-page-title-main">Alexanderson alternator</span>

An Alexanderson alternator is a rotating machine invented by Ernst Alexanderson in 1904 for the generation of high-frequency alternating current for use as a radio transmitter. It was one of the first devices capable of generating the continuous radio waves needed for transmission of amplitude modulated signals by radio. It was used from about 1910 in a few "superpower" longwave radiotelegraphy stations to transmit transoceanic message traffic by Morse code to similar stations all over the world.

In an alternating current (AC) electric power system, synchronization is the process of matching the frequency and phase and voltage of a generator or other source to an electrical grid in order to transfer power. If two unconnected segments of a grid are to be connected to each other, they cannot safely exchange AC power until they are synchronized.

In electrical power engineering, power systems CAD is computer-aided design (CAD) software that is used to design and simulate electrical power systems in commercial and industrial buildings.

Electrical power system simulation involves power system modeling and network simulation in order to analyze electrical power systems using design/offline or real-time data. Power system simulation software's are a class of computer simulation programs that focus on the operation of electrical power systems. These types of computer programs are used in a wide range of planning and operational situations for electric power systems.

<span class="mw-page-title-main">IEEE Nikola Tesla Award</span>

The IEEE Nikola Tesla Award is a Technical Field Award given annually to an individual or team that has made an outstanding contribution to the generation or utilization of electric power. It is awarded by the Board of Directors of the IEEE. The award is named in honor of Nikola Tesla. This award may be presented to an individual or a team.

<span class="mw-page-title-main">Electric power system</span> Network of electrical component deployed to generate, transmit & distribute electricity

An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The electrical grid can be broadly divided into the generators that supply the power, the transmission system that carries the power from the generating centers to the load centers, and the distribution system that feeds the power to nearby homes and industries.

<span class="mw-page-title-main">Numerical relay</span> System using algorithmic detection of electrical faults

In utility and industrial electric power transmission and distribution systems, a numerical relay is a computer-based system with software-based protection algorithms for the detection of electrical faults. Such relays are also termed as microprocessor type protective relays. They are functional replacements for electro-mechanical protective relays and may include many protection functions in one unit, as well as providing metering, communication, and self-test functions.

Electric power transmission, the tools and means of moving electricity far from where it is generated, date back to the late 19th century. They include the movement of electricity in bulk and the delivery of electricity to individual customers ("distribution"). In the beginning, the two terms were used interchangeably.

<span class="mw-page-title-main">Electrification of the New York, New Haven and Hartford Railroad</span>

The New York, New Haven and Hartford Railroad pioneered electrification of main line railroads using high-voltage, alternating current, single-phase overhead catenary. It electrified its mainline between Stamford, Connecticut, and Woodlawn, New York, in 1907 and extended the electrification to New Haven, Connecticut, in 1914. While single-phase AC railroad electrification has become commonplace, the New Haven's system was unprecedented at the time of construction. The significance of this electrification was recognized in 1982 by its designation as a Historic Mechanical Engineering Landmark by the American Society of Mechanical Engineers (ASME).

The following outline is provided as an overview of and topical guide to electronics:

This glossary of electrical and electronics engineering is a list of definitions of terms and concepts related specifically to electrical engineering and electronics engineering. For terms related to engineering in general, see Glossary of engineering.

References

  1. Thomas Parke Hughes Networks of power: electrification in Western society, 1880-1930 JHU Press, 1993 ISBN   0-8018-4614-5 page 376
  2. Charles Eames, Ray Eames A Computer Perspective: Background to the Computer Age, Harvard University Press, 1990 0674156269, page 117
  3. M.A. Laughton, D.F Warne (ed),Electrical Engineer's Reference Book (16th Edition), Elsevier, 2003 ISBN   978-1-60119-452-7 pages 368-369
  4. H.P. Kuehni, R.G. Lorraine, A New A-C Network Analyzer, Transactions AIEE, February 1938 volume 57 page 67
  5. David A. Mindell, Between Human and Machine: Feedback, Control and Computing Before Cybernetics, JHU Press, 2004 ISBN   0801880572 pp.149-150
  6. Edward Wilson Kimbark, Power System Stability, Wiley-IEEE ,1948, ISBN   0-7803-1135-3 page 64 and following
  7. Institution of Engineering and Technology, Power System Protection, Volumes 1-4, 1995 ISBN   978-1-60119-889-1 pages 216-220
  8. Aad Blok, Greg Downey (ed) Uncovering Labour in Information Revolutions, 1750-2000, Cambridge University Press, 2003 ISBN   0521543533, pp. 76-80
  9. 1 2 http://www.ieeeghn.org/wiki/images/e/ec/Chapter_6-Calculating_Power_(Edwin_L._Harder).pdf Calculating Power, retrieved 2013 Feb 26
  10. H.L Hazen, O.R. Schurig and M.F. Gardner. The M.I.T. Network Analyzer Design and Application to Power System Problems, Transactions AIEEE, July 1930 pp.1102-1113
  11. Karl L. Wildes, Nilo A. Lindgren A Century of Electrical Engineering and Computer Science at MIT, 1882-1982 MIT Press 1985 ISBN   0262231190, pp. 100-104
  12. http://ed-thelen.org/comp-hist/GE-Computer_Department_Data_Book_1960.pdf GE-Computer_Department_Data_Book_1960, page 150-152, retrieved 2013 Feb 7
  13. https://news.google.com/newspapers?nid=2202&dat=19530204&id=RVMmAAAAIBAJ&sjid=nf8FAAAAIBAJ&pg=830,3636416 Gettysburg Times 7 firms will put analyzer in institute, February 4, 1953
  14. http://www2.iee.or.jp/ver2/honbu/14-magazine/log/2004/2004_08a_03.pdf Historical Trends and Interactive Relationship in Establishment of the of Symmetrical Coordinates and AC Network Analyzer retrieved 2013 Feb 26
  15. W. A. Morgan, F. S. Rothe, J.J. Winsness An Improved A-C Network Analyzer, AIEE Transactions, Volume 68, 1949 pp. 891-896
  16. http://fultonhistory.com/newspaper%202/Auburn%20NY%20Citizen%20Advertiser/Auburn%20NY%20Citizen%20Advertiser%201945.pdf/Newspaper%20Auburn%20NY%20Citizen%20Advertiser%201945%20-%200253.PDF "$90,000 Electric Brain Installed at Illinois Tech"
  17. http://www.gtri.gatech.edu/history/our-forefathers/gerald-rosselot retrieved 2013 Feb 26
  18. https://collections.museumsvictoria.com.au/articles/10180 Bonwick, B. (2011) The Network Analyser - a detailed description in Museums Victoria Collections Accessed 04 August 2017
  19. http://www2.cit.cornell.edu/computer/history/Linke.html Cornell computing histories, retrieved 2013 Feb 26
  20. http://www.cpri.in/about-us/departmentsunits/power-system-division-psd/transient-network-analyser.html TNA at Central Power Research Institute, India retrieved 2013 Feb 26
  21. http://www.metaphorik.de/12/tympasdalouka.pdf retrieved 2008 Jan 26
  22. 1 2 James S. Small, The Analogue Alternative: The Electronic Analogue Computer in Britain and the USA, 1930-1975, Routledge, 2013, ISBN   1134699026, pages 35-40
  23. https://collections.museumsvictoria.com.au/items/1763754 Photograph of part of a Westinghouse network analyzer, retrieved 2017 Aug 3