Inverter-based resource

Last updated

An inverter-based resource (IBR) is a source of electricity that is asynchronously connected to the electrical grid via an electronic power converter ("inverter"). The devices in this category, also known as converter interfaced generation (CIG), include the variable renewable energy generators (wind, solar) and battery storage power stations. [1] These devices lack the intrinsic behaviors (like the inertial response of a synchronous generator) and their features are almost entirely defined by the control algorithms, presenting specific challenges to system stability as their penetration increases, [1] for example, a single software fault can affect all devices of a certain type in a contingency (cf. section on Blue Cut fire below). IBRs are sometimes called non-synchronous generators. [2] The design of inverters for the IBR generally follows the IEEE 1547 and NERC PRC-024-2 standards. [3]

Contents

Grid-following vs. grid-forming

A grid-following (GFL) device is synchronized to the local grid voltage and injects an electric current vector aligned with the voltage (in other words, behaves like a current source [4] ). The GFL inverters are built into an overwhelming majority of installed IBR devices. [1] Due to their following nature, the GFL device will shut down if a large voltage/frequency disturbance is observed. [5] The GFL devices cannot contribute to the grid strength, dampen active power oscillations, or provide inertia. [6]

A grid-forming (GFM) device partially mimics the behavior of a synchronous generator: its voltage is controlled by a free-running oscillator that slows down when more energy is withdrawn from the device. Unlike a conventional generator, the GFM device has no overcurrent capacity and thus will react very differently in the short-circuit situation. [1] Adding the GFM capability to a GFL device is not expensive in terms of components, but affects the revenues: in order to support the grid stability by providing extra power when needed, the power semiconductors need to be oversized and energy storage added. Modeling demonstrates, however, that it is possible to run a power system that almost entirely is based on the GFL devices. [7] A combination of GFM battery storage power station and synchronous condensers (SuperFACTS) is being researched. [8]

Features

Compliance with IEEE 1547 standard makes the IBR to support safety features: [9]

Once an IBR ceases to provide power, it can come back only gradually, ramping its output from zero to full power. [10]

The electronic nature of IBRs limits their overload capability: the thermal stress causes their components to even temporarily be able to function at no more than 1-2 times the nameplate capacity, while the synchronous machines can briefly tolerate an overload as high as 5-6 times their rated power. [11]

Vulnerabilities

New challenges to the system stability came with the increased penetration of IBRs. Incidences of disconnections during contingency events where the fault ride through was expected, and poor damping of subsynchronous oscillations in weak grids were reported. [1]

One of the most studied major power contingencies that involved IBRs is the Blue Cut Fire of 2016 in Southern California, with a temporary loss of more than a gigawatt of photovoltaic power in a very short time. [10]

Blue Cut fire

The Blue Cut fire in the Cajon Pass on August 16, 2016, has affected multiple high-voltage (500 kV and 287 kV) power transmission lines passing through the canyon. Throughout the day thirteen 500 kV line faults and two 287 kV faults were recorded. [12] The faults themselves were transitory and self-cleared in a short time (2-3.5 cycles, less than 60 milliseconds), but the unexpected features of the algorithms in the photovoltaic inverter software triggered multiple massive losses of power, with the largest one of almost 1,200 megawatts [13] at 11:45:16 AM, persisting for multiple minutes. [14]

The analysis performed by the North American Electric Reliability Corporation (NERC) had shown that:

  1. 700 MW of loss were caused by the poorly designed frequency estimation algorithm. The line faults had distorted the AC waveform and fooled the software into a wrong estimate of the grid frequency dropping below 57 Hz, a threshold where an emergency disconnect shall be initiated. However, the actual frequency during the event had never dropped below 59.867 Hz, [15] well above the low limit of the normal frequency range (59.5 Hz for the Western Interconnection).
  2. Additional 450 MW were lost when low line voltage caused the inverters to immediately cease to inject current, with gradual return to operative state within 2 minutes. At least one manufacturer had indicated that injecting the current when the voltage level is below 0.9 pu would involve a major redesign. [16]

As a result of the incident, NERC had issued multiple recommendations, involving the changes in inverter design and amendments to the standards. [3]

Related Research Articles

<span class="mw-page-title-main">Power inverter</span> Device that changes direct current (DC) to alternating current (AC)

A power inverter, inverter, or invertor is a power electronic device or circuitry that changes direct current (DC) to alternating current (AC). The resulting AC frequency obtained depends on the particular device employed. Inverters do the opposite of rectifiers which were originally large electromechanical devices converting AC to DC.

<span class="mw-page-title-main">Utility frequency</span> Frequency used on standard electricity grid in a given area

The utility frequency, (power) line frequency or mains frequency is the nominal frequency of the oscillations of alternating current (AC) in a wide area synchronous grid transmitted from a power station to the end-user. In large parts of the world this is 50 Hz, although in the Americas and parts of Asia it is typically 60 Hz. Current usage by country or region is given in the list of mains electricity by country.

<span class="mw-page-title-main">Power electronics</span> Technology of power electronics

Power electronics is the application of electronics to the control and conversion of electric power.

<span class="mw-page-title-main">15 kV AC railway electrification</span> Standard current and voltage settings for much of Central Europes train transport

Railway electrification using alternating current (AC) at 15 kilovolts (kV) and 16.7 hertz (Hz) are used on transport railways in Germany, Austria, Switzerland, Sweden, and Norway. The high voltage enables high power transmission with the lower frequency reducing the losses of the traction motors that were available at the beginning of the 20th century. Globally, railway electrification in late 20th century tends to use 25 kV, 50 Hz AC systems which has become the preferred standard for new railway electrifications. Nevertheless, local extensions of the existing 15 kV network is commonplace. In particular, the Gotthard Base Tunnel uses 15 kV, 16.7 Hz electrification.

<span class="mw-page-title-main">Frequency changer</span> Electronic device

A frequency changer or frequency converter is an electronic or electromechanical device that converts alternating current (AC) of one frequency to alternating current of another frequency. The device may also change the voltage, but if it does, that is incidental to its principal purpose, since voltage conversion of alternating current is much easier to achieve than frequency conversion.

<span class="mw-page-title-main">Electric clock</span> Clock powered by electricity

An electric clock is a clock that is powered by electricity, as opposed to a mechanical clock which is powered by a hanging weight or a mainspring. The term is often applied to the electrically powered mechanical clocks that were used before quartz clocks were introduced in the 1980s. The first experimental electric clocks were constructed around the 1840s, but they were not widely manufactured until mains electric power became available in the 1890s. In the 1930s, the synchronous electric clock replaced mechanical clocks as the most widely used type of clock.

Islanding is the intentional or unintentional division of an interconnected power grid into individual disconnected regions with their own power generation.

Doubly fed electric machines, Doubly fed induction generator (DFIG), or slip-ring generators, are electric motors or electric generators, where both the field magnet windings and armature windings are separately connected to equipment outside the machine.

<span class="mw-page-title-main">Grid-tie inverter</span> Electrical equipment

A grid-tie inverter converts direct current (DC) into an alternating current (AC) suitable for injecting into an electrical power grid, at the same voltage and frequency of that power grid. Grid-tie inverters are used between local electrical power generators: solar panel, wind turbine, hydro-electric, and the grid.

<span class="mw-page-title-main">Electric power system</span> Network of electrical component deployed to generate, transmit & distribute electricity

An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The electrical grid can be broadly divided into the generators that supply the power, the transmission system that carries the power from the generating centers to the load centers, and the distribution system that feeds the power to nearby homes and industries.

In an electric power system, overcurrent or excess current is a situation where a larger than intended electric current exists through a conductor, leading to excessive generation of heat, and the risk of fire or damage to equipment. Possible causes for overcurrent include short circuits, excessive load, incorrect design, an arc fault, or a ground fault. Fuses, circuit breakers, and current limiters are commonly used overcurrent protection (OCP) mechanisms to control the risks. Circuit breakers, relays, and fuses protect circuit wiring from damage caused by overcurrent.

<span class="mw-page-title-main">Electrical grid</span> Interconnected network for delivering electricity to consumers

An electrical grid is an interconnected network for electricity delivery from producers to consumers. Electrical grids consist of power stations, electrical substations to step voltage up or down, electric power transmission to carry power over long distances, and finally electric power distribution to customers. In that last step, voltage is stepped down again to the required service voltage. Power stations are typically built close to energy sources and far from densely populated areas. Electrical grids vary in size and can cover whole countries or continents. From small to large there are microgrids, wide area synchronous grids, and super grids. The combined transmission and distribution network is part of electricity delivery, known as the power grid.

<span class="mw-page-title-main">Wide area synchronous grid</span> Regional electrical grid

A wide area synchronous grid is a three-phase electric power grid that has regional scale or greater that operates at a synchronized utility frequency and is electrically tied together during normal system conditions. Also known as synchronous zones, the most powerful is the Northern Chinese State Grid with 1,700 gigawatts (GW) of generation capacity, while the widest region served is that of the IPS/UPS system serving most countries of the former Soviet Union. Synchronous grids with ample capacity facilitate electricity trading across wide areas. In the ENTSO-E in 2008, over 350,000 megawatt hours were sold per day on the European Energy Exchange (EEX).

<span class="mw-page-title-main">Unified power flow controller</span> Electrical device for reactive power compensation on high-voltage electricity transmission networks

A unified power flow controller (UPFC) is an electrical device for providing fast-acting reactive power compensation on high-voltage electricity transmission networks. It uses a pair of three-phase controllable bridges to produce current that is injected into a transmission line using a series transformer. The controller can control active and reactive power flows in a transmission line.

Inertial response is a property of large synchronous generators, which contain large synchronous rotating masses, and which acts to overcome any immediate imbalance between power supply and demand for electric power systems, typically the electrical grid. Due to the ever existing power imbalance between mechanical power supply and electric power demand the rotational frequency of the rotating masses in all synchronous generators in the grid either speed up and thus absorb the extra power in case of an excess power supply, or slow down and provide additional power in case of an excess power demand. This response in case of a synchronous generator is built-in into the design and happens without any external intervention or coordination, providing the automatic generation control and the grid operator with valuable time to rebalance the system The grid frequency is the combined result of the detailed motions of all individual synchronous rotors in the grid, which are modeled by a general equation of motion called the swing equation.

<span class="mw-page-title-main">Synchronverter</span> Type of electrical power inverter

Synchronverters or virtual synchronous generators are inverters which mimic synchronous generators (SG) to provide "synthetic inertia" for ancillary services in electric power systems. Inertia is a property of standard synchronous generators associated with the rotating physical mass of the system spinning at a frequency proportional to the electricity being generated. Inertia has implications towards grid stability as work is required to alter the kinetic energy of the spinning physical mass and therefore opposes changes in grid frequency. Inverter-based generation inherently lacks this property as the waveform is being created artificially via power electronics.

Power system operations is a term used in electricity generation to describe the process of decision-making on the timescale from one day to minutes prior to the power delivery. The term power system control describes actions taken in response to unplanned disturbances in order to provide reliable electric supply of acceptable quality. The corresponding engineering branch is called Power System Operations and Control. Electricity is hard to store, so at any moment the supply (generation) shall be balanced with demand. In an electrical grid the task of real-time balancing is performed by a regional-based control center, run by an electric utility in the traditional electricity market. In the restructured North American power transmission grid, these centers belong to balancing authorities numbered 74 in 2016, the entities responsible for operations are also called independent system operators, transmission system operators. The other form of balancing resources of multiple power plants is a power pool. The balancing authorities are overseen by reliability coordinators.

<span class="mw-page-title-main">Capability curve</span>

Capability curve of an electrical generator describes the limits of the active (MW) and reactive power (MVAr) that the generator can provide. The curve represents a boundary of all operating points in the MW/MVAr plane; it is typically drawn with the real power on the horizontal axis, and, for the synchronous generator, resembles a letter D in shape, thus another name for the same curve, D-curve. In some sources the axes are switched, and the curve gets a dome-shaped appearance.

The power system reliability is the probability of a normal operation of the electrical grid at a given time. Reliability indices characterize the ability of the electrical system to supply customers with electricity as needed by measuring the frequency, duration, and scale of supply interruptions. Traditionally two interdependent components of the power system reliability are considered:

In an electrical grid, the short circuit ratio is the ratio of: the short circuit apparent power (SCMVA) in the case of a line-line-line-ground (3LG) fault at the location in the grid where some generator is connected, to: the power rating of the generator itself (GMW).

References

  1. 1 2 3 4 5 Gu & Green 2022, p. 1.
  2. Khan & Minai 2023, p. 1.
  3. 1 2 NERC 2017, p. 10.
  4. Khan & Minai 2023, pp. 1–2.
  5. Khan & Minai 2023, p. 4.
  6. AEMO 2021, p. 15.
  7. Gu & Green 2022, p. 2.
  8. Gevorgian, V.; Shah, S.; Yan, W. (2021). "Hybridizing synchronous condensers with grid forming batteries for PV integration – a solution to enhance grid reliability and resiliency". Iet Conference Proceedings (12). Institution of Engineering and Technology: 85–108. doi:10.1049/icp.2021.2488. ISBN   978-1-83953-680-9.
  9. Popiel 2020, pp. 4–5.
  10. 1 2 Popiel 2020, p. 5.
  11. AEMO 2021, p. 16.
  12. NERC 2017, p. v.
  13. NERC 2017, p. 2.
  14. NERC 2017, p. 5.
  15. NERC 2017, p. 8.
  16. NERC 2017, p. 9.

Sources