Comtrade

Last updated

COMTRADE (Common format for Transient Data Exchange for power systems) is a file format for storing oscillography and status data related to transient power system disturbances.

Contents

Applications

COMTRADE files are typically generated by Intelligent Electronic Devices (IEDs), such as an electronic protective relay, in electrical substations during power systems disturbances. These IEDs monitor the electrical characteristics of the power system by digitally sampling measurements of the current, voltage, power, frequency, etc. at a high speed.

The IEDs then use digital signal processing algorithms on that data to detect abnormal conditions in the power system so that automated control actions can be taken to prevent damage to the power system. When faults are detected, the IEDs records the data that was used during processing into a COMTRADE file. Analysis tools can then process the COMTRADE file and calculate useful information related to the disturbance.

For instance, a COMTRADE recording of the fault current absorbed by a transformer prior to the circuit breaker opening can be used to calculate the total energy dissipated by the transformer. That helps the utility to more accurately estimate the impact of that fault on the lifetime of the transformer.

COMTRADE files from multiple devices can be used collectively to analyze large-scale power disturbance events (e.g. blackouts) to determine the root cause, improve system protection, and guide mitigation strategies.

Formats

The COMTRADE file format was standardized by the Power System Relaying & Controls Committee (PSRC) of the IEEE Power & Energy Society as C37.111. The original specification was published in 1991. The 1991 version specifies a file format that includes multiple file types designated by the assigned file extensions of *.CFG, *.HDR, and *.DAT. The .DAT file contains the digitized sample data in an ASCII text format. The .CFG file specifies what is in the .DAT file including information such as signal names, start time of the samples, number of samples, min/max values, and more. Only the .CFG and .DAT files were mandatory.

Although the values of the digitized samples in the .DAT file are viewable without the .CFG file, the value of the data is greatly diminished as it would then be difficult to fully analyze the data.

The most widely used version of the COMTRADE standard is C37.111-1999. The 1999 version added a 16-bit Binary .DAT file format and a .INF file. The .CFG file format was augmented to provide details of instrument transformers, allowing conversion between primary and secondary units.

The most recent version is C37.111-2013. The 2013 format added 32-bit Binary and IEEE 754 floating point .DAT formats as well as time zone information. A new, single-file format with extension .CFF was also introduced to combine C37.111-1999 files into a single file. Also known as IEC 60255-24 Ed.2, this standard defines a format for files containing transient waveform and event data collected from power systems or power system models. The standard is for files stored on currently used physical media such as portable external hard drives, USB drives, CD, or DVD.

The file format called Power Quality Data Interchange Format (PQDIF) is similar to COMTRADE in structure but is used primarily to convey power quality data instead of transient disturbance data. Like IEEE COMTRADE, IEEE PQDIF can be used to exchange waveform measurements and phasor measurements. However, IEEE PQDIF allows the storage of data logs, magnitude-duration measurements, histograms, and more. The IEEE Power Quality Subcommittee [1] of the IEEE Power & Energy Society specified the format in IEEE Std.1159.3-2019. [2]

History

As applications for using COMTRADE grew the limitations of the file format began to cause problems. For instance, the North American SynchroPhasor Initiative (NASPI) sponsored by the North American Electric Reliability Corporation [3] wanted to use COMTRADE files to exchange archives of streaming synchrophasor data (IEEE C37.118). The C37.111-1999 version of the COMTRADE configuration (.CFG) files did not include information describing time zones nor timing precision required for synchrophasor data. This would have complicated large-scale exchange of synchrophasor data.

Beginning in 2011, the IEEE PSRC began work on a new version of the COMTRADE standard published as C37.111-2013. The COMTRADE standard itself does not specify how to transfer data files over communication networks. [4]

Software

COMTRADE viewers and analysis software are available from many commercial companies. Viewer/analysis functionality varies. Free COMTRADE viewers and analysis software include advanced functionality (e.g. protection relay behavior analysis (line/transformer differential/impedance protection, fault/harmonic analysis, user-defined mathematical expressions, analysis and plots, COMTRADE file editing and creation, etc..

See also

Related Research Articles

<span class="mw-page-title-main">Digital audio</span> Technology that records, stores, and reproduces sound

Digital audio is a representation of sound recorded in, or converted into, digital form. In digital audio, the sound wave of the audio signal is typically encoded as numerical samples in a continuous sequence. For example, in CD audio, samples are taken 44,100 times per second, each with 16-bit sample depth. Digital audio is also the name for the entire technology of sound recording and reproduction using audio signals that have been encoded in digital form. Following significant advances in digital audio technology during the 1970s and 1980s, it gradually replaced analog audio technology in many areas of audio engineering, record production and telecommunications in the 1990s and 2000s.

In electrical engineering, partial discharge (PD) is a localized dielectric breakdown (DB) of a small portion of a solid or fluid electrical insulation (EI) system under high voltage (HV) stress. While a corona discharge (CD) is usually revealed by a relatively steady glow or brush discharge (BD) in air, partial discharges within solid insulation system are not visible.

<span class="mw-page-title-main">Current transformer</span> Transformer used to scale alternating current, used as sensor for AC power

A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary.

<span class="mw-page-title-main">Recloser</span>

In electric power distribution, automatic circuit reclosers (ACRs) are a class of switchgear designed for use on overhead electricity distribution networks to detect and interrupt transient faults. Also known as reclosers or autoreclosers, ACRs are essentially rated circuit breakers with integrated current and voltage sensors and a protection relay, optimized for use as a protection asset. Commercial ACRs are governed by the IEC 62271-111/IEEE Std C37.60 and IEC 62271-200 standards. The three major classes of operating maximum voltage are 15.5 kV, 27 kV and 38 kV.

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

Electric power quality is the degree to which the voltage, frequency, and waveform of a power supply system conform to established specifications. Good power quality can be defined as a steady supply voltage that stays within the prescribed range, steady AC frequency close to the rated value, and smooth voltage curve waveform. In general, it is useful to consider power quality as the compatibility between what comes out of an electric outlet and the load that is plugged into it. The term is used to describe electric power that drives an electrical load and the load's ability to function properly. Without the proper power, an electrical device may malfunction, fail prematurely or not operate at all. There are many ways in which electric power can be of poor quality, and many more causes of such poor quality power.

IEC 61850 is an international standard defining communication protocols for intelligent electronic devices at electrical substations. It is a part of the International Electrotechnical Commission's (IEC) Technical Committee 57 reference architecture for electric power systems. The abstract data models defined in IEC 61850 can be mapped to a number of protocols. Current mappings in the standard are to Manufacturing Message Specification (MMS), GOOSE [see section 3, Terms and definitions, term 3.65 on page 14], SV or SMV, and soon to web services. In the previous version of the standard, GOOSE stood for "Generic Object Oriented Substation Event", but this old definition is still very common in IEC 61850 documentation. These protocols can run over TCP/IP networks or substation LANs using high speed switched Ethernet to obtain the necessary response times below four milliseconds for protective relaying.

Power-system automation is the act of automatically controlling the power system via instrumentation and control devices. Substation automation refers to using data from Intelligent electronic devices (IED), control and automation capabilities within the substation, and control commands from remote users to control power-system devices.

<span class="mw-page-title-main">Phasor measurement unit</span>

A phasor measurement unit (PMU) is a device used to estimate the magnitude and phase angle of an electrical phasor quantity in the electricity grid using a common time source for synchronization. Time synchronization is usually provided by GPS or IEEE 1588 Precision Time Protocol, which allows synchronized real-time measurements of multiple remote points on the grid. PMUs are capable of capturing samples from a waveform in quick succession and reconstructing the phasor quantity, made up of an angle measurement and a magnitude measurement. The resulting measurement is known as a synchrophasor. These time synchronized measurements are important because if the grid’s supply and demand are not perfectly matched, frequency imbalances can cause stress on the grid, which is a potential cause for power outages.

In Electrical Power Systems and Industrial Automation, ANSI Device Numbers can be used to identify equipment and devices in a system such as relays, circuit breakers, or instruments. The device numbers are enumerated in ANSI/IEEE Standard C37.2 "Standard for Electrical Power System Device Function Numbers, Acronyms, and Contact Designations".

Electrical power system simulation involves power system modeling and network simulation in order to analyze electrical power systems using design/offline or real-time data. Power system simulation software's are a class of computer simulation programs that focus on the operation of electrical power systems. These types of computer programs are used in a wide range of planning and operational situations for electric power systems.

<span class="mw-page-title-main">Numerical relay</span> System using algorithmic detection of electrical faults

In utility and industrial electric power transmission and distribution systems, a numerical relay is a computer-based system with software-based protection algorithms for the detection of electrical faults. Such relays are also termed as microprocessor type protective relays. They are functional replacements for electro-mechanical protective relays and may include many protection functions in one unit, as well as providing metering, communication, and self-test functions.

<span class="mw-page-title-main">FNET</span>

FNET is a wide-area power system frequency measurement system. Using a type of phasor measurement unit (PMU) known as a frequency disturbance recorder (FDR), FNET/GridEye is able to measure the power system frequency, voltage, and angle very accurately. These measurements can then be used to study various power system phenomena, and may play an important role in the development of future smart grid technologies. The FNET/GridEye system is currently operated by the Power Information Technology Laboratory at the University of Tennessee (UTK) in Knoxville, Tennessee, and Oak Ridge National Laboratory (ORNL) in Oak Ridge, Tennessee.

The openPDC is a complete set of applications for processing streaming time-series data in real-time. The name stands for "open source phasor data concentrator" and was originally designed for the concentration and management of real-time streaming synchrophasors. Due to the system's modular design, the openPDC can be classified as a generic event stream processor.

IEEE 1344 is a standard that defines parameters for synchrophasors for power systems. The standard added extension to the IRIG-B time code to cover year, time quality, daylight saving time, local time offset and leap second information. IEEE 1344 was superseded by IEEE C37.118 in 2005 and the time extensions were adopted as part of the IRIG timing standard in the 2004 edition.

<span class="mw-page-title-main">Protective relay</span> Relay device designed to trip a circuit breaker when a fault is detected

In electrical engineering, a protective relay is a relay device designed to trip a circuit breaker when a fault is detected. The first protective relays were electromagnetic devices, relying on coils operating on moving parts to provide detection of abnormal operating conditions such as over-current, overvoltage, reverse power flow, over-frequency, and under-frequency.

IEC 60870 part 5 is one of the IEC 60870 set of standards which define systems used for telecontrol in electrical engineering and power system automation applications. Part 5 provides a communication profile for sending basic telecontrol messages between two systems, which uses permanent directly connected data circuits between the systems. The IEC Technical Committee 57 have developed a protocol standard for telecontrol, teleprotection, and associated telecommunications for electric power systems. The result of this work is IEC 60870-5. Five documents specify the base IEC 60870-5:

Condition monitoring of transformers in electrical engineering is the process of acquiring and processing data related to various parameters of transformers to determine their state of quality and predict their failure. This is done by observing the deviation of the transformer parameters from their expected values. Transformers are the most critical assets of electrical transmission and distribution systems, and their failures could cause power outages, personal and environmental hazards, and expensive rerouting or purchase of power from other suppliers. Identifying a transformer which is near failure can allow it to be replaced under controlled conditions at a non-critical time and avoid a system failure.

Power Quality Data Interchange Format (PQDIF) is a binary file format specified in IEEE Std. 1159.3 that is used to exchange voltage, current, power, and energy measurements between software applications with a focus on the power quality domain.

SATEC is a developer and manufacturer of specialty solutions for power measurement and power quality monitoring. The company's range of products includes traditional 3-phase power meters for real-time power measurement and data-logging, revenue meters, power quality analyzers and a software suite for energy management and billing.

References

  1. "IEEE PES Power Quality Subcommittee – IEEE Power & Energy Society".
  2. "IEEE 1159.3-2019 - IEEE Recommended Practice for Power Quality Data Interchange Format (PQDIF)".
  3. "NERC". www.nerc.com. Retrieved 2023-09-05.
  4. C37.111-2013 - IEEE/IEC Measuring relays and protection equipment – Part 24: Common format for transient data exchange (COMTRADE) for power systems