Cromer cycle

Last updated

The Cromer cycle is a thermodynamic cycle that uses a desiccant to interact with higher relative humidity air leaving a cold surface. When a system is taken through a series of different states and finally returned to its initial state, a thermodynamic cycle is said to have occurred. The desiccant absorbs moisture from the air leaving the cold surface, releasing heat and drying the air, which can be used in a process requiring dry air. The desiccant is then dried by an air stream at a lower relative humidity, where the desiccant gives up its moisture by evaporation, increasing the air's relative humidity and cooling it. This cooler, moister air can then be presented to the same cold surface as above to take it below its dew point and dry it further, or it can be expunged from the system.

Contents

Figure 1: Cromer cycle CromerCycle001.jpg
Figure 1: Cromer cycle

The desiccant undergoes a reversible process whereby in the first part of the cycle, it absorbs or adsorbs moisture from air leaving a cold surface, releasing heat, and then in the second part of the cycle evaporates moisture, absorbing heat and returning the desiccant to its original state to complete the cycle again. The result of the Cromer cycle is that the process air leaving the cycle is dehumidified further (higher latent ratio) than it would be leaving the cold surface without the cycle. The Cromer cycle concept was originally patented in the mid-1980's. Those patents have expired and thus the cycle is free for anyone to use. The cycle was first publicized in 1997 by Popular Mechanics in its Tech Update section. [1]

Psychrometrics

The Cromer cycle is primarily used in air conditioning and drying applications. The cold surface portion of the cycle is most often a result of a reversed Carnot or refrigeration cycle. For the Cromer cycle to operate, a desiccant must be exposed to two air streams, one with higher humidity from a cold surface, and one with lower humidity to dry it. This is most easily accomplished by moving the desiccant. Any cycling mechanism can be used, such as pumping a liquid desiccant, however an easy mechanical application is a rotating wheel, loaded with desiccant, through which the different air streams pass. This is shown in Figure 1 where a desiccant wheel has been applied to a standard air conditioning set-up.

Figure 2: On a standard psychrometric chart, the air flow state points of the Cromer cycle are shown. Figure 2 Psychrometrics of Cromer Cycle.jpg
Figure 2: On a standard psychrometric chart, the air flow state points of the Cromer cycle are shown.

The psychrometric process of the air passing through the system with four state points is shown on the psychrometric chart of Figure 2 as 1, 2, 3 and 4. The state points of the air are also depicted in Figure 1. In this application, the air returning from the space, typically around 50% relative humidity (RH), is presented to the desiccant wheel and dries the desiccant. The air picks up moisture and cools in process 1 to 2. The moist air is now presented to the cooling surface (cooling coil of the air conditioner), which cools it below its dew point and dries the air in process 2 to 3. This represents the work done by the cold coil. In the meantime, the dried desiccant from below is rotated to the upper air stream. The saturated air leaving the coil, typically 93–98% RH, is presented to the desiccant at 3, where the air is dried further in process 3 to 4, where it is presented to the space as supply air. The desiccant, now loaded with moisture, rotates to the return air, where the cycle repeats.

Typical cooling and drying by the cold coil without the Cromer cycle is depicted on the psychrometric chart and is also shown in Figure 2. State point 1 is the air that returns from the space to the system (return air). For a typical air conditioning system, this air at state point 1 enters the cooling coil and leaves at about state point 4' after cooling and drying. State point 4' represents the temperature and moisture content of the air that leaves the typical unit, about 45–50 °F (7–10 °C) and 95–98% RH.

Changes to a standard AC system by the Cromer cycle

The psychrometric chart depicts the changes of the cycle to the standard air conditioning cycle. First, the end state point 4 for air from the wheel represents a latent ratio increase (moisture removal) to about 45%, as opposed to the 25% of the typical coil shown. Secondly, the air quality delivered by the cycle is much dryer, about 55% RH (state point 4), rather than 98% with the standard coil (state point 4'). Third, this is accomplished with a higher average evaporator temperature. Compare the midpoint of the evaporator's temperature, line 1 to 4’, to the midpoint of the Cromer cycle's evaporator's temperature, line 2 to 3. These lines represent the work done by the coil on the air stream (its change in enthalpy). This is significant because, given a constant condenser temperature and equivalent change in enthalpy, the higher the evaporator coil temperature, the more efficient is the Carnot refrigeration cycle and the greater the energy efficiency a particular system can deliver.

Common dehumidification strategies include: reheating (electric or hot-gas bypass), where sensible heat is added to the air leaving the equipment; recuperative heat (run-around coils or heat pipes), where sensible heat is transferred from the return air to the supply air; or the Cromer cycle, where the latent heat of moisture sorption and evaporation is transferred from the return air to the supply air. These various strategies were compared in an ASHRAE Journal article that found that "the Cromer cycle produces similar enhanced dehumidification performance as is obtained with recuperative configurations." [2]

Desiccants used

To operate in this cycle, the desiccant is required to absorb moisture from air coming off of the coil that is colder and about 98% RH and to desorb moisture to air that is warmer and at a lower RH. The desiccant is regenerated by the vapor pressure differential inherent in the RH differences rather than heat or temperature difference. Desiccants that have a moisture sorption isotherm of the type shown in Figure 3 (Type III) are common, such as many formulations of silica gel. Type III desiccants absorb little moisture below 70% RH but many will take up more than their own weight in water from the air when presented with over 90% RH. The absorption isotherm is very steep between 90 and 100% RH. Desiccants of Type III have plenty of potential for the cycling of moisture from the air off of the coil, around 98% RH, over to the return air stream, typically around 50% RH.

Figure 3 Type III Desiccant Isotherm of Davidson Silica Gel.jpg

Field tests

In 2011, Khalifa, Al-Omran, and Mohammed reported on a monitored study of a 2-ton capacity air conditioner unit while exchanging out a silica gel wheel and a wheel made of activated carbon to determine if it would reduce the relative humidity in a small room in Baghdad when compared to the unit without the Cromer cycle added. They found that the "Cromer cycle can reduce the indoor relative humidity from 80% to about 60% using active carbon of 5 cm wheel thickness." [3]

Incorporating fresh air exchange

To maintain indoor air quality, it may be desirable to expunge return air from the conditioned space and replace it with fresh outdoor air, sometimes called "make-up air." The optimal location to expunge return air from a Cromer cycle system is just after the desiccant (location 2 on Figure 1). At this point, the return air has been loaded with moisture from the desiccant, and expunging it removes additional moisture from the space. Furthermore, this expunge air is cooled below the return air condition by the desiccant's evaporation of the moisture into it. Location 2 (but before the fan) is also the ideal place to bring outdoor air into the system, as the coil can then reduce its temperature and moisture before it enters the space. Also, if heat exchange is provided between the expunged air and the outdoor air, the incoming air can be cooled and brought near to or at saturation before it enters the cooling coil for process 2 to 3, enhancing its dehumidification. [4] [5]

Dehumidifier

When the process needed is more dehumidification or drying, the Cromer cycle can be enhanced by using the free heat available from the condensing side of the reverse Carnot refrigeration cycle. This heat, sometimes called "hot gas bypass" can be added before the desiccant wheel to enhance the drying of the wheel at location 1 of Figure 1 (but after the filter), called pre-heat. Hot gas bypass heat can also be added to the process at location 4, called reheat, which delivers warmer but even lower RH supply air. Either one or both hot gas bypass locations can be used. When a Cromer cycle air conditioning system is enhanced with hot gas bypass, it is typically referred to as "active" Cromer cycle air-conditioning. When the cycle is used as equipment designed for dehumidification or drying, it is typically called a Cromer cycle dehumidifier or Cromer cycle dryer.

R&D magazine recognized the Cromer cycle in 2006 with an R&D 100 Award in the mechanical/materials category, recognizing the year's 100 most significant technological innovations. [6]

Related Research Articles

<span class="mw-page-title-main">Humidity</span> Concentration of water vapour in the air

Humidity is the concentration of water vapor present in the air. Water vapor, the gaseous state of water, is generally invisible to the human eye. Humidity indicates the likelihood for precipitation, dew, or fog to be present.

<span class="mw-page-title-main">Dew point</span> Temperature at which air becomes saturated with water vapour during a cooling process

The dew point of a given body of air is the temperature to which it must be cooled to become saturated with water vapor. This temperature depends on the pressure and water content of the air. When the air is cooled below the dew point, its moisture capacity is reduced and airborne water vapor will condense to form liquid water known as dew. When this occurs through the air's contact with a colder surface, dew will form on that surface.

<span class="mw-page-title-main">Heating, ventilation, and air conditioning</span> Technology of indoor and vehicular environmental comfort

Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.

<span class="mw-page-title-main">Dehumidifier</span> Device which reduces humidity

A dehumidifier is an air conditioning device which reduces and maintains the level of humidity in the air. This is done usually for health or thermal comfort reasons, or to eliminate musty odor and to prevent the growth of mildew by extracting water from the air. It can be used for household, commercial, or industrial applications. Large dehumidifiers are used in commercial buildings such as indoor ice rinks and swimming pools, as well as manufacturing plants or storage warehouses. Typical air conditioning systems combine dehumidification with cooling, by operating cooling coils below the dewpoint and draining away the water that condenses.

<span class="mw-page-title-main">Hygrometer</span> Instrument for measuring humidity

A hygrometer is an instrument which measures the humidity of air or some other gas: that is, how much water vapor it contains. Humidity measurement instruments usually rely on measurements of some other quantities such as temperature, pressure, mass and mechanical or electrical changes in a substance as moisture is absorbed. By calibration and calculation, these measured quantities can lead to a measurement of humidity. Modern electronic devices use the temperature of condensation, or they sense changes in electrical capacitance or resistance to measure humidity differences. A crude hygrometer was invented by Leonardo da Vinci in 1480. Major leaps came forward during the 1600s; Francesco Folli invented a more practical version of the device, while Robert Hooke improved a number of meteorological devices including the hygrometer. A more modern version was created by Swiss polymath Johann Heinrich Lambert in 1755. Later, in the year 1783, Swiss physicist and Geologist Horace Bénédict de Saussure invented the first hygrometer using human hair to measure humidity.

<span class="mw-page-title-main">Desiccant</span> Substance used to induce or sustain dryness

A desiccant is a hygroscopic substance that is used to induce or sustain a state of dryness (desiccation) in its vicinity; it is the opposite of a humectant. Commonly encountered pre-packaged desiccants are solids that absorb water. Desiccants for specialized purposes may be in forms other than solid, and may work through other principles, such as chemical bonding of water molecules. They are commonly encountered in foods to retain crispness. Industrially, desiccants are widely used to control the level of water in gas streams.

<span class="mw-page-title-main">Evaporative cooler</span> Device that cools air through the evaporation of water

An evaporative cooler is a device that cools air through the evaporation of water. Evaporative cooling differs from other air conditioning systems, which use vapor-compression or absorption refrigeration cycles. Evaporative cooling exploits the fact that water will absorb a relatively large amount of heat in order to evaporate. The temperature of dry air can be dropped significantly through the phase transition of liquid water to water vapor (evaporation). This can cool air using much less energy than refrigeration. In extremely dry climates, evaporative cooling of air has the added benefit of conditioning the air with more moisture for the comfort of building occupants.

<span class="mw-page-title-main">Chiller</span> Machine that removes heat from a liquid coolant via vapor compression

A chiller is a machine that removes heat from a liquid coolant via a vapor-compression, adsorption refrigeration, or absorption refrigeration cycles. This liquid can then be circulated through a heat exchanger to cool equipment, or another process stream. As a necessary by-product, refrigeration creates waste heat that must be exhausted to ambience, or for greater efficiency, recovered for heating purposes. Vapor compression chillers may use any of a number of different types of compressors. Most common today are the hermetic scroll, semi-hermetic screw, or centrifugal compressors. The condensing side of the chiller can be either air or water cooled. Even when liquid cooled, the chiller is often cooled by an induced or forced draft cooling tower. Absorption and adsorption chillers require a heat source to function.

<span class="mw-page-title-main">Psychrometrics</span> Study of gas-vapor mixtures

Psychrometrics is the field of engineering concerned with the physical and thermodynamic properties of gas-vapor mixtures.

<span class="mw-page-title-main">Heat recovery ventilation</span> Method of reusing thermal energy in a building

Heat recovery ventilation (HRV), also known as mechanical ventilation heat recovery (MVHR) or energy recovery ventilation (ERV), is a ventilation system that recovers energy by operating between two air sources at different temperatures. It is used to reduce the heating and cooling demands of buildings.

<span class="mw-page-title-main">Air handler</span> Device used to regulate and circulate air as part of an HVAC system

An air handler, or air handling unit, is a device used to regulate and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. An air handler is usually a large metal box containing a blower, furnace or A/C elements, filter racks or chambers, sound attenuators, and dampers. Air handlers usually connect to a ductwork ventilation system that distributes the conditioned air through the building and returns it to the AHU, sometimes exhausting air to the atmosphere and bringing in fresh air. Sometimes AHUs discharge (supply) and admit (return) air directly to and from the space served without ductwork

<span class="mw-page-title-main">Wet-bulb temperature</span> Temperature read by a thermometer covered in water-soaked cloth

The wet-bulb temperature (WBT) is the temperature read by a thermometer covered in water-soaked cloth over which air is passed. At 100% relative humidity, the wet-bulb temperature is equal to the air temperature ; at lower humidity the wet-bulb temperature is lower than dry-bulb temperature because of evaporative cooling.

<span class="mw-page-title-main">Wood drying</span> Also known as seasoning, which is the reduction of the moisture content of wood prior to its use

Wood drying reduces the moisture content of wood before its use. When the drying is done in a kiln, the product is known as kiln-dried timber or lumber, whereas air drying is the more traditional method.

An atmospheric water generator (AWG), is a device that extracts water from humid ambient air, producing potable water. Water vapor in the air can be extracted either by condensation - cooling the air below its dew point, exposing the air to desiccants, using membranes that only pass water vapor, collecting fog, or pressurizing the air. AWGs are useful where potable water is difficult to obtain, because water is always present in ambient air.

Solar air conditioning, or "solar-powered air conditioning", refers to any air conditioning (cooling) system that uses solar power.

Convectant drying is a drying assembly method. It was developed in 1999 by Charles Cressy as an alternative to conventional refrigerant and desiccant dehumidifier drying techniques. In July 2013 British Standards PAS 64 "Mitigation and recovery of water damaged buildings - Code of practice" was published recognising and including descriptions of the process within the document.

<span class="mw-page-title-main">Air conditioning</span> Cooling of air in an enclosed space

Air conditioning, often abbreviated as A/C (US) or air con (UK), is the process of removing heat from an enclosed space to achieve a more comfortable interior environment and in some cases also strictly controlling the humidity of internal air. Air conditioning can be achieved using a mechanical 'air conditioner' or alternatively a variety of other methods, including passive cooling and ventilative cooling. Air conditioning is a member of a family of systems and techniques that provide heating, ventilation, and air conditioning (HVAC). Heat pumps are similar in many ways to air conditioners, but use a reversing valve to allow them both to heat and to cool an enclosed space.

HVAC is a major sub discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary.

<span class="mw-page-title-main">Thermal wheel</span> Type of energy recovery heat exchanger

A thermal wheel, also known as a rotary heat exchanger, or rotary air-to-air enthalpy wheel, energy recovery wheel, or heat recovery wheel, is a type of energy recovery heat exchanger positioned within the supply and exhaust air streams of air-handling units or rooftop units or in the exhaust gases of an industrial process, in order to recover the heat energy. Other variants include enthalpy wheels and desiccant wheels. A cooling-specific thermal wheel is sometimes referred to as a Kyoto wheel.

Compressed air dryers are special types of filter systems that are specifically designed to remove the water that is inherent in compressed air. The compression of air raises its temperature and concentrates atmospheric contaminants, primarily water vapor, as resulting in air with elevated temperature and 100% relative humidity. As the compressed air cools down, water vapor condenses into the tank(s), pipes, hoses and tools connected downstream from the compressor which may be damaging. Therefore water vapor is removed from compressed air to prevent condensation from occurring and to prevent moisture from interfering in sensitive industrial processes.

References

  1. Popular Mechanics, Vol 174, No 1, Jan 1997, p.26
  2. Dieckmann, J., McKenney, K., Brodrick, J.,"Energy-Efficient Dehumidification: Vapor Compression, Cromer Cycle";ASHRAE Journal, Vol 51, No 8, Aug. 2009, pp 78-80
  3. Khalifa, A., Al-Omran, A., Mohammed, H., EXPERIMENTAL STUDY OF AIR CONDITIONER UNIT PERFORMANCE USING CROMER CYCLE, AL-TAQANI. 24. E1-E13, 2011. https://www.researchgate.net/publication/323323036_EXPERIMENTAL_STUDY_OF_AIR_CONDITIONER_UNIT_PERFORMANCE_USING_CROMER_CYCLE
  4. Clark, J.; “Energy-Efficient Supermarket Heating, Ventilation and Air Conditioning in Humid Climates in the United States”; National Renewable Energy Laboratory, Boulder, CO; Technical Report, March 2015, NREL/TP-5500-63796, p 88; https://www.nrel.gov/docs/fy15osti/63796.pdf
  5. Kosar, D; Gulubovic, M; Khadir, M; Judge, J; Swami, M; Shirey, D; Raustad, R; Basarkar, M; Novosel, D; “Integrating Advanced Humidity Control to Reduce Energy Use”; Final Report – Task 6; NCEMBT-070621; 2007; National Center for Energy Management and Building Technologies; Washington, DC; United States Department of Energy; p22 https://www.nemionline.org/wp-content/uploads/2017/06/Kosar_D_Integrating_Advanced_Humidity_Control_To_Reduce_Energy_Use_NCEMBT-070621.pdf
  6. R & D Magazine, December, 2006, R&D 100 Award Winners https://www.rdworldonline.com/about-us/