A power distribution unit (PDU) is a device fitted with multiple outputs designed to distribute electric power, especially to racks of computers and networking equipment located within a data center. [1] Data centers face challenges in power protection and management solutions. This is why many data centers rely on PDU monitoring to improve efficiency, uptime, and growth. [2] [3] For data center applications, the power requirement is typically much larger than a home or office style power strips with power inputs as large as 22 kVA or even greater. Most large data centers utilize PDUs with 3-phase power input and 1-phase power output. There are two main categories of PDUs: Basic PDUs and Intelligent (networked) PDUs or iPDUs. Basic PDUs simply provide a means of distributing power from the input to a plurality of outlets. Intelligent PDUs normally have an intelligence module that allow the PDU for remote management of power metering information, power outlet on/off control, and/or alarms. Some advanced PDUs allow users to manage external sensors such as temperature, humidity, airflow, etc.

Contents

Form factors

PDUs vary from simple and inexpensive rack-mounted power strips to larger floor-mounted PDUs with multiple functions including power filtering to improve power quality, intelligent load balancing, and remote monitoring and control by LAN or SNMP. [1] This kind of PDU placement offers intelligent capabilities such as power metering at the inlet, outlet, and PDU branch circuit level [4] and support for environment sensors. [5]

Newer generation of intelligent PDUs allow for IP consolidation, which means many PDUs can be linked in an array under a single IP address. Next-generation models also offer integration with electronic locks, providing the ability to network and manage PDUs and locks through the same appliance. [6]

In data centers, larger PDUs are needed to power multiple server cabinets. Each server cabinet or row of cabinets may require multiple high current circuits, possibly from different phases of incoming power or different UPSs. Standalone cabinet PDUs are self-contained units that include main circuit breakers, individual circuit breakers, and power monitoring panels. The cabinet provides internal bus bars for neutral and grounding. Prepunched top and bottom panels allow for safe cable entry. [7]

See also

Related Research Articles

<span class="mw-page-title-main">19-inch rack</span> Standard width frame for C&N equipment

A 19-inch rack is a standardized frame or enclosure for mounting multiple electronic equipment modules. Each module has a front panel that is 19 inches (482.6 mm) wide. The 19 inch dimension includes the edges or ears that protrude from each side of the equipment, allowing the module to be fastened to the rack frame with screws or bolts. Common uses include computer servers, telecommunications equipment and networking hardware, audiovisual production gear, music production equipment, and scientific equipment.

<span class="mw-page-title-main">Power supply</span> Electronic device that converts or regulates electric energy and supplies it to a load

A power supply is an electrical device that supplies electric power to an electrical load. The main purpose of a power supply is to convert electric current from a source to the correct voltage, current, and frequency to power the load. As a result, power supplies are sometimes referred to as electric power converters. Some power supplies are separate standalone pieces of equipment, while others are built into the load appliances that they power. Examples of the latter include power supplies found in desktop computers and consumer electronics devices. Other functions that power supplies may perform include limiting the current drawn by the load to safe levels, shutting off the current in the event of an electrical fault, power conditioning to prevent electronic noise or voltage surges on the input from reaching the load, power-factor correction, and storing energy so it can continue to power the load in the event of a temporary interruption in the source power.

<span class="mw-page-title-main">Circuit breaker</span> Automatic circuit protection device

A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by overcurrent. Its basic function is to interrupt current flow to protect equipment and to prevent the risk of fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.

<span class="mw-page-title-main">Electrical substation</span> Part of an electrical transmission, and distribution system

A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. There are 55,000 substations in the United States.

<span class="mw-page-title-main">IEC 60320</span> Set of standards for AC power connectors used on domestic appliances on the appliance side

IEC 60320 Appliance couplers for household and similar general purposes is a set of standards from the International Electrotechnical Commission (IEC) specifying non-locking connectors for connecting power supply cords to electrical appliances of voltage not exceeding 250 V (a.c.) and rated current not exceeding 16 A. Different types of connector are specified for different combinations of current, temperature and earthing requirements. Unlike IEC 60309 connectors, they are not coded for voltage; users must ensure that the voltage rating of the equipment is compatible with the mains supply. The standard uses the term coupler to encompass connectors on power cords and power inlets and outlets built into appliances.

<span class="mw-page-title-main">Remote terminal unit</span> Computer peripheral to collect telemetry data

A remote terminal unit (RTU) is a microprocessor-controlled electronic device that interfaces objects in the physical world to a distributed control system or SCADA system by transmitting telemetry data to a master system, and by using messages from the master supervisory system to control connected objects. Other terms that may be used for RTU are remote telemetry unit and remote telecontrol unit.

<span class="mw-page-title-main">Power strip</span> Electrical component

A power strip is a block of electrical sockets that attaches to the end of a flexible cable, allowing multiple electrical devices to be powered from a single electrical socket. Power strips are often used when many electrical devices are in proximity, such as for audio, video, computer systems, appliances, power tools, and lighting. Power strips often include a circuit breaker to interrupt the electric current in case of an overload or a short circuit. Some power strips provide protection against electrical power surges. Typical housing styles include strip, rack-mount, under-monitor and direct plug-in.

Modbus or MODBUS is a client/server data communications protocol in the application layer of the OSI model. It was originally published by Modicon in 1979 for use with its programmable logic controllers (PLCs). Modbus has become a de facto standard communication protocol for communication between industrial electronic devices in a wide range of buses and network.

A distribution board is a component of an electricity supply system that divides an electrical power feed into subsidiary circuits while providing a protective fuse or circuit breaker for each circuit in a common enclosure. Normally, a main switch, and in recent boards, one or more residual-current devices (RCDs) or residual current breakers with overcurrent protection (RCBOs) are also incorporated.

<span class="mw-page-title-main">Network operations center</span> Location from which network management is performed

A network operations center, also known as a "network management center", is one or more locations from which network monitoring and control, or network management, is exercised over a computer, telecommunication or satellite network.

<span class="mw-page-title-main">KVM switch</span> Device that connects computer front-end hardware to multiple computers

A KVM switch is a hardware device that allows a user to control multiple computers from one or more sets of keyboards, video monitors, and mice.

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

<span class="mw-page-title-main">DNP3</span> Computer network protocol

Distributed Network Protocol 3 (DNP3) is a set of communications protocols used between components in process automation systems. Its main use is in utilities such as electric and water companies. Usage in other industries is not common. It was developed for communications between various types of data acquisition and control equipment. It plays a crucial role in SCADA systems, where it is used by SCADA Master Stations, Remote Terminal Units (RTUs), and Intelligent Electronic Devices (IEDs). It is primarily used for communications between a master station and RTUs or IEDs. ICCP, the Inter-Control Center Communications Protocol, is used for inter-master station communications. Competing standards include the older Modbus protocol and the newer IEC 61850 protocol.

<span class="mw-page-title-main">Phasor measurement unit</span>

A phasor measurement unit (PMU) is a device used to estimate the magnitude and phase angle of an electrical phasor quantity in the electricity grid using a common time source for synchronization. Time synchronization is usually provided by GPS or IEEE 1588 Precision Time Protocol, which allows synchronized real-time measurements of multiple remote points on the grid. PMUs are capable of capturing samples from a waveform in quick succession and reconstructing the phasor quantity, made up of an angle measurement and a magnitude measurement. The resulting measurement is known as a synchrophasor. These time synchronized measurements are important because if the grid’s supply and demand are not perfectly matched, frequency imbalances can cause stress on the grid, which is a potential cause for power outages.

<span class="mw-page-title-main">Raritan Inc.</span>

Raritan is a multinational technology company that manufactures hardware for data center power distribution, remote server management, and audio visual solutions. The company is headquartered in Somerset, New Jersey, and has a commercial presence in over 76 countries. Raritan was acquired by Legrand in September 2015.

Liebert Corporation, a business of Vertiv, is a global manufacturer of power, precision cooling and infrastructure management systems for mainframe computer, server racks, and critical process systems. Liebert is headquartered in Westerville, Ohio, and employs more than 1,800 people across 12 manufacturing plants worldwide.

<span class="mw-page-title-main">IP access controller</span>

An IP access controller is an electronic security device designed to identify users and control entry to or exit from protected areas using Internet Protocol-based technology. A typical IP access controller supports 2 or 4 basic access control readers. IP access controllers may have an internal web server that is configurable using a browser or using software installed on a host PC.

<span class="mw-page-title-main">Server Technology</span>

Server Technology, Inc. offers power distribution products for data centers, telecommunication equipment and remote administration. The company is headquartered in Reno, Nevada with offices in the United Kingdom, Germany, Hong Kong and India.

Canovate Elektronik Endüstri ve Ticaret A.Ş. is a manufacturer of industrial enclosures, server cabinets, fiber optic connectivity and data center products. Canovate Group product lines range from Fiber Optic Connectivity to Data Centers Solutions and from Rack Cabinets to Intelligent Power Distribution Units coupled with (B2B) and (B2C) sales.

<span class="mw-page-title-main">ATEN International</span>

ATEN International Co.(Ltd) is a multinational manufacturer of connectivity and access management hardware headquartered in Xizhi District, New Taipei, Taiwan. Its products include KVM switches, audiovisual switches and matrices, intelligent power distribution units, information technology management systems, and interface adapters. ATEN has subsidiaries in several countries and is the parent company of IOGEAR.

References

  1. 1 2 "Definition of: Power distribution unit". PCMag.com. Ziff Davis. Retrieved March 8, 2014.
  2. "Sentry Power Manager: Rack-Level Data Center Power Monitoring and Management". ServerTech.com. Server Technology. 2014. Retrieved January 1, 2015.
  3. "Benefits of intelligent power distribution". www.vertiv.com. Retrieved December 29, 2023.
  4. "PDU Metering at the Inlet, Outlet, and Branch Circuits - Raritan". Raritan.com. 2015. Retrieved May 25, 2015.
  5. "Rack PDU - Rack Power Distribution - Intelligent PDU". Raritan.com. 2015. Retrieved May 26, 2015.
  6. US 9865109,Roth, Wayne D.; Conner, Donald A.& Orris, Ronald S.,"Systems and methods for controlling an electronic lock for a remote device",published January 9, 2018
  7. "Cabinet Power Distribution". APC. Retrieved November 4, 2013.