Copper cable certification

Last updated

In copper twisted pair wire networks, copper cable certification is achieved through a thorough series of tests in accordance with Telecommunications Industry Association (TIA) or International Organization for Standardization (ISO) standards. These tests are done using a certification-testing tool, which provide pass or fail information. While certification can be performed by the owner of the network, certification is primarily done by datacom contractors. It is this certification that allows the contractors to warranty their work.

Contents

Need for certification

Installers who need to prove to the network owner that the installation has been done correctly and meets TIA or ISO standards need to certify their work. Network owners who want to guarantee that the infrastructure is capable of handling a certain application (e.g. Voice over Internet) will use a tester to certify the network infrastructure. In some cases, these testers are used to pinpoint specific problems. Certification tests are vital if there is a discrepancy between the installer and network owner after an installation has been performed.

Standards

The performance tests and their procedures have been defined in the ANSI/TIA-568.2 standard and the ISO/IEC 11801 standard. The TIA standard defines performance in categories (Cat 3, Cat 5e, Cat 6, Cat 6A, and Cat 8) and the ISO defines classes (Class C, D, E, EA, F and FA). These standards define the procedure to certify that an installation meets performance criteria in a given category or class.

The significance of each category or class is the limit values of which the Pass/Fail and frequency ranges are measured: Cat 3 and Class C (no longer used) test and define communication with 16 MHz bandwidth, Cat 5e and Class D with 100 MHz bandwidth, Cat 6 and Class E up to 250 MHz, Cat6A and Class EA up to 500 MHz, Cat7 and Class F up to 600 MHz and Cat 7A and Class FA with a frequency range through 1000 MHz., Cat 8, Class I, and Class II have a frequency range through 2000MHz

The standards also define that data from each test result must be collected and stored in either print or electronic format for future inspection.

Tests

Test ParameterTIA-568-BISO 11801:2002
WiremapPass/FailPass/Fail
Propagation DelayPass/FailPass/Fail
Delay SkewPass/FailPass/Fail
Cable LengthPass/FailInformation only
Insertion Loss (IL)Pass/FailPass/Fail
Return Loss (RL)Pass/Fail (except Cat3)Pass/Fail
Near-End Crosstalk (NEXT)Pass/FailPass/Fail
Power Sum NEXT (PSNEXT)Pass/FailPass/Fail
Equal-Level Far-End Crosstalk (ELFEXT)Pass/FailPass/Fail
Power Sum ELFEXT (PSELFEXT)Pass/FailPass/Fail
Attenuation-to-Crosstalk Ratio (ACR)Information onlyPass/Fail (except Class C)
Power sum ACR (PSACR)Information onlyPass/Fail (except Class C)
DC Loop ResistancePass/Fail

Wiremap

The wiremap test is used to identify physical installation errors; improper pin termination, shorts between any two or more wires, continuity to the remote end, split pairs, crossed pairs, reversed pairs, and any other mis-wiring.

Propagation Delay

The Propagation Delay test tests for the time it takes for the signal to be sent from one end and received by the other end.

Propagation delay.gif

Delay Skew

Delay skew.gif

The Delay Skew test is used to find the difference in propagation delay between the fastest and slowest set of wire pairs. An ideal skew is between 25 and 50 nanoseconds over a 100-meter cable. The lower this skew the better; less than 25 ns is excellent, but 45 to 50 ns is marginal. (Traveling between 50% and 80% of the speed of light, an electronic wave requires between 417 and 667 ns to traverse a 100-meter cable.

Cable Length

The Cable Length test verifies that the copper cable from the transmitter to receiver does not exceed the maximum recommended distance of 100 meters in a 10BASE-T/100BASE-TX/1000BASE-T network.

Insertion Loss

Insertion loss, also referred to as attenuation, refers to the loss of signal strength at the far end of a line compared to the signal that was introduced into the line. This loss is due to the electrical resistance of the copper cable, the loss of energy through the cable insulation, and impedance mismatches introduced at the connectors. Insertion loss is usually expressed in decibels dB. Insertion loss increases with distance and frequency. For every 3 dB of loss, signal power is reduced by a factor of and signal amplitude is reduced by a factor of .

Return Loss

Return Loss is the measurement (in dB) of the amount of signal that is reflected back toward the transmitter. The reflection of the signal is caused by the variations of impedance in the connectors and cable and is usually attributed to a poorly terminated wire. The greater the variation in impedance, the greater the return loss reading. If 3 pairs of wire pass by a substantial amount, but the 4 pair barely passes, it usually is an indication of a bad crimp or bad connection at the RJ45 plug. Return loss is usually not significant in the loss of a signal, but rather signal jitter.

Near-End Crosstalk (NEXT)

In twisted-pair cabling Near-End Crosstalk (NEXT) is a measure that describes the effect caused by a signal from one wire pair coupling into another wire pair and interfering with the signal therein. It is the difference, expressed in dB, between the amplitude of a transmitted signal and the amplitude of the signal coupled into another cable pair, at the signal-source end of a cable. A higher value is desirable as it indicates that less of the transmitted signal is coupled into the victim wire pair. NEXT is measured 30 meters (about 98 feet) from the injector/generator.[ citation needed ] Higher near-end crosstalk values correspond to higher overall circuit performance. Low NEXT values on a UTP LAN used with older signaling standards (IEEE 802.3 and earlier) are particularly detrimental.[ citation needed ] Excessive near-end crosstalk can be an indication of improper termination.

Power Sum NEXT (PSNEXT)

Power Sum NEXT (NEXT) is the sum of NEXT values from 3 wire pairs as they affect the other wire pair. The combined effect of NEXT can be very detrimental to the signal.

The Equal-Level Far-End Crosstalk (ELFEXT)

The Equal-Level Far-End Crosstalk (ELFEXT) test measures Far-End Crosstalk (FEXT). FEXT is very similar to NEXT, but happens at the receiver side of the connection. Due to attenuation on the line, the signal causing the crosstalk diminishes as it gets further away from the transmitter. Because of this, FEXT is usually less detrimental to a signal than NEXT, but still important nonetheless. Recently the designation was changed from ELFEXT to ACR-F (far end ACR).

Power Sum ELFEXT (PSELFEXT)

Power Sum ELFEXT (PSELFEXT) is the sum of FEXT values from 3 wire pairs as they affect the other wire pair, minus the insertion loss of the channel. Recently the designation was changed from PSELFEXT to PSACR-F (far end ACR).

Attenuation-to-Crosstalk ratio (ACR)

Attenuation-to-Crosstalk ratio (ACR) is the difference between the signal attenuation produced NEXT and is measured in decibels (dB). The ACR indicates how much stronger the attenuated signal is than the crosstalk at the destination (receiving) end of a communications circuit. The ACR figure must be at least several decibels for proper performance. If the ACR is not large enough, errors will be frequent. In many cases, even a small improvement in ACR can cause a dramatic reduction in the bit error rate. Sometimes it may be necessary to switch from un-shielded twisted pair (UTP) cable to shielded twisted pair (STP) in order to increase the ACR.

Power Sum ACR (PSACR)

Power Sum ACR (PSACR) done in the same way as ACR, but using the PSNEXT value in the calculation rather than NEXT.

DC Loop Resistance

DC Loop Resistance measures the total resistance through one wire pair looped at one end of the connection. This will increase with the length of the cable. DC resistance usually has less effect on a signal than insertion loss, but plays a major role if power over Ethernet is required. Also measured in ohms is the characteristic impedance of the cable, which is independent of the cable length.

See also

Notes

    Related Research Articles

    <span class="mw-page-title-main">Ethernet over twisted pair</span> Ethernet physical layers using twisted-pair cables

    Ethernet over twisted-pair technologies use twisted-pair cables for the physical layer of an Ethernet computer network. They are a subset of all Ethernet physical layers.

    In telecommunications and professional audio, a balanced line or balanced signal pair is a circuit consisting of two conductors of the same type, both of which have equal impedances along their lengths and equal impedances to ground and to other circuits. The primary advantage of the balanced line format is good rejection of common-mode noise and interference when fed to a differential device such as a transformer or differential amplifier.

    <span class="mw-page-title-main">Signal reflection</span> When a transmitted signal reflects back through the medium it was transmitted over

    In telecommunications, signal reflection occurs when a signal is transmitted along a transmission medium, such as a copper cable or an optical fiber. Some of the signal power may be reflected back to its origin rather than being carried all the way along the cable to the far end. This happens because imperfections in the cable cause impedance mismatches and non-linear changes in the cable characteristics. These abrupt changes in characteristics cause some of the transmitted signal to be reflected. In radio frequency (RF) practice this is often measured in a dimensionless ratio known as voltage standing wave ratio (VSWR) with a VSWR bridge. The ratio of energy bounced back depends on the impedance mismatch. Mathematically, it is defined using the reflection coefficient.

    <span class="mw-page-title-main">Coaxial cable</span> Electrical cable type with concentric inner conductor, insulator, and conducting shield

    Coaxial cable, or coax is a type of electrical cable consisting of an inner conductor surrounded by a concentric conducting shield, with the two separated by a dielectric ; many coaxial cables also have a protective outer sheath or jacket. The term coaxial refers to the inner conductor and the outer shield sharing a geometric axis.

    <span class="mw-page-title-main">Category 5 cable</span> Unshielded twisted pair communications cable

    Category 5 cable (Cat 5) is a twisted pair cable for computer networks. Since 2001, the variant commonly in use is the Category 5e specification (Cat 5e). The cable standard provides performance of up to 100 MHz and is suitable for most varieties of Ethernet over twisted pair up to 2.5GBASE-T but more commonly runs at 1000BASE-T speeds. Cat 5 is also used to carry other signals such as telephone and video.

    <span class="mw-page-title-main">Twisted pair</span> Type of wiring used for communications

    Twisted pair cabling is a type of wiring used for communications in which two conductors of a single circuit are twisted together for the purposes of improving electromagnetic compatibility. Compared to a single conductor or an untwisted balanced pair, a twisted pair reduces electromagnetic radiation from the pair and crosstalk between neighboring pairs and improves rejection of external electromagnetic interference. It was invented by Alexander Graham Bell.

    Very high-speed digital subscriber line (VDSL) and very high-speed digital subscriber line 2 (VDSL2) are digital subscriber line (DSL) technologies providing data transmission faster than the earlier standards of asymmetric digital subscriber line (ADSL) G.992.1, G.992.3 (ADSL2) and G.992.5 (ADSL2+).

    <span class="mw-page-title-main">Attenuation-to-crosstalk ratio</span> Measurement that represents the overall performance of a cable

    Attenuation-to-crosstalk ratio (ACR) is a parameter that is measured when testing a communication link, which represents the overall performance of the cable. AcR is a mathematical formula that calculates the ratio of attenuation to near-end crosstalk for each combination of cable pairs. ACR is expressed as a figure in decibels (dB), between the signal attenuation produced by a wire or cable transmission medium and the near-end crosstalk (NEXT). In order for a signal to be received with an acceptable bit error rate, the attenuation and the crosstalk must both be minimized. Crosstalk can be reduced by ensuring that twisted-pair wiring is tightly twisted and is not crushed, and by ensuring that connectors between wire and cable media are properly rated and installed.

    <span class="mw-page-title-main">Category 6 cable</span> Standardized data communications cable

    Category 6 cable (Cat 6) is a standardized twisted pair cable for Ethernet and other network physical layers that is backward compatible with the Category 5/5e and Category 3 cable standards.

    <span class="mw-page-title-main">Cable tester</span> Electronic device used to verify electrical connections

    A cable tester is an electronic device used to verify the electrical connections in a signal cable or other wired assembly. Basic cable testers are continuity testers that verify the existence of a conductive path between ends of the cable, and verify the correct wiring of connectors on the cable. More advanced cable testers can measure the signal transmission properties of the cable such as its resistance, signal attenuation, noise and interference.

    In electronics, crosstalk is any phenomenon by which a signal transmitted on one circuit or channel of a transmission system creates an undesired effect in another circuit or channel. Crosstalk is usually caused by undesired capacitive, inductive, or conductive coupling from one circuit or channel to another.

    <span class="mw-page-title-main">Signal integrity</span>

    Signal integrity or SI is a set of measures of the quality of an electrical signal. In digital electronics, a stream of binary values is represented by a voltage waveform. However, digital signals are fundamentally analog in nature, and all signals are subject to effects such as noise, distortion, and loss. Over short distances and at low bit rates, a simple conductor can transmit this with sufficient fidelity. At high bit rates and over longer distances or through various mediums, various effects can degrade the electrical signal to the point where errors occur and the system or device fails. Signal integrity engineering is the task of analyzing and mitigating these effects. It is an important activity at all levels of electronics packaging and assembly, from internal connections of an integrated circuit (IC), through the package, the printed circuit board (PCB), the backplane, and inter-system connections. While there are some common themes at these various levels, there are also practical considerations, in particular the interconnect flight time versus the bit period, that cause substantial differences in the approach to signal integrity for on-chip connections versus chip-to-chip connections.

    International standard ISO/IEC 11801Information technology — Generic cabling for customer premises specifies general-purpose telecommunication cabling systems that are suitable for a wide range of applications. It is published by ISO/IEC JTC 1/SC 25/WG 3 of the International Organization for Standardization (ISO) and the International Electrotechnical Commission (IEC). It covers both balanced copper cabling and optical fibre cabling.

    <span class="mw-page-title-main">Test probe</span>

    A test probe is a physical device used to connect electronic test equipment to a device under test (DUT). Test probes range from very simple, robust devices to complex probes that are sophisticated, expensive, and fragile. Specific types include test prods, oscilloscope probes and current probes. A test probe is often supplied as a test lead, which includes the probe, cable and terminating connector.

    <span class="mw-page-title-main">RG-6</span> Type of coaxial cable

    RG-6/U is a common type of coaxial cable used in a wide variety of residential and commercial applications. An RG-6/U coaxial cable has a characteristic impedance of 75 ohms. The term, RG-6, is generic and is applied to a wide variety of cable designs, which differ from one another in shielding characteristics, center conductor composition, dielectric type and jacket type. RG was originally a unit indicator for bulk radio frequency (RF) cable in the U.S. military's Joint Electronics Type Designation System. The suffix /U means for general utility use. The number was assigned sequentially. The RG unit indicator is no longer part of the JETDS system (MIL-STD-196E) and cable sold today under the RG-6 label is unlikely to meet military specifications. In practice, the term RG-6 is generally used to refer to coaxial cables with an 18 AWG center conductor and 75 ohm characteristic impedance.

    <span class="mw-page-title-main">Modular connector</span> Electrical connector commonly used in telephone and computer networks

    A modular connector is a type of electrical connector for cords and cables of electronic devices and appliances, such as in computer networking, telecommunication equipment, and audio headsets.

    <span class="mw-page-title-main">Twinaxial cabling</span>

    Twinaxial cabling, or "Twinax", is a type of cable similar to coaxial cable, but with two inner conductors instead of one. Due to cost efficiency it is becoming common in modern (2013) very-short-range high-speed differential signaling applications.

    <span class="mw-page-title-main">Fiber-optic cable</span> Cable assembly containing one or more optical fibers that are used to carry light

    A fiber-optic cable, also known as an optical-fiber cable, is an assembly similar to an electrical cable but containing one or more optical fibers that are used to carry light. The optical fiber elements are typically individually coated with plastic layers and contained in a protective tube suitable for the environment where the cable is used. Different types of cable are used for optical communication in different applications, for example, long-distance telecommunication or providing a high-speed data connection between different parts of a building.

    ANSI/TIA-568 is a technical standard for commercial building cabling for telecommunications products and services. The title of the standard is Commercial Building Telecommunications Cabling Standard and is published by the Telecommunications Industry Association (TIA), a body accredited by the American National Standards Institute (ANSI).

    <span class="mw-page-title-main">Copper conductor</span> Electrical wire or other conductor made of copper

    Copper has been used in electrical wiring since the invention of the electromagnet and the telegraph in the 1820s. The invention of the telephone in 1876 created further demand for copper wire as an electrical conductor.