EN 54

Last updated
EN 54-x
EN standard
ReferenceEN 54-x
StatusPublished
TitleFire detection and fire alarm systems
Committee CEN/TC 72
Work Itemvarious
Directives 305/2011, 89/106/EEC
Citation in OJEU 305/2011 (C 226, 2015-07-10)
CE markingYes

The EN 54 Fire detection and fire alarm systems is a series of European standards that includes product standards and application guidelines for fire detection and fire alarm systems as well as voice alarm systems.

Contents

The product standards define product characteristics, test methods and performance criteria against which the effectiveness and reliability of every component of fire detection and fire alarm system can be assessed and declared.

Many of the product standards of the EN 54 series are harmonised standards under the Construction Products Regulation (CPR) EU 305/2011. Annex ZA of the harmonised standards specifies which sections of the standard apply for the purposes of the CPR. Annex ZA also describes the two-stage certification:

This standard series is partly used around the world in several countries outside of European Union, for example in Latin American countries, Brasil, African and Asian countries and several islands in the Pacific Ocean.

History

How EN54 are made in the EU HowEN54areMadeintheEU.jpg
How EN54 are made in the EU

The standardization topics relating to fire protection were among the first dealt with by CEN. This is obvious since CEN numbers the European standards in numerical ascending order according to the date of project registration. The standard on fire classes is numbered EN 2 [1] and the series of standards on portable fire extinguishers is numbered EN 3. [2] The European standardization on fire detection and fire alarm systems started already in the 1970s. EN 54-1 and EN 54-5 were issued in 1976. [3] [4]

Technical Committee CEN/TC72 Fire detection and fire alarm systems

The EN 54 series has been prepared by Technical Committee CEN/TC72 "Fire detection and fire alarm systems" of the European Committee for Standardization (CEN, French: Comité Européen de Normalisation). The figure shows some examples of national mirror technical committees. [5]

EN 54 Standard Series

Current parts

The EN 54 series of standards covers the following topics and product groups related to fire detection and fire alarm systems: [6] [7]

The following table lists all parts of the EN 54 series of standards:

Parts of the EN 54 series on fire detection and fire alarm systems
Topics, group of productsNumber of the standardTitle of the standardStandHarmonized
IntroductionEN 54-1Part 1: Introduction [8] 2021No
Control panels and power supplyEN 54-2Part 2: Control and indicating equipment (Fire alarm control panel)1997 + A1:2006 + AC:1999Yes
Alarm devicesEN 54-3Part 3: Fire alarm devices - Sounders2014 + A1:2019Yes
Control panels and power supplyEN 54-4Part 4: Power supply equipment1997 + A1:2002 + A2:2006 + AC:1999Yes
DetectorsEN 54-5Part 5: Heat detectors - Point heat detectors2017 + A1:2018Yes
DetectorsEN 54-7Part 7: Smoke detectors - Point smoke detectors using scattered light, transmitted light or ionization2018Yes
DetectorsEN 54-10Part 10: Flame detectors - Point detectors2002 + A1:2005Yes
DetectorsEN 54-11Part 11: Manual call point 2001 + A1:2005Yes
DetectorsEN 54-12Part 12: Smoke detectors - Line detectors using an optical light beam2015Yes
System compatibilityEN 54-13Part 13: Compatibility and connectability assessment of system components2017 + A1:2019No
Application guidelinesCEN/TS 54-14Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance (of fire detection and fire alarm systems)2018-10No
Control panels and power supplyEN 54-16Part 16: Voice alarm control and indicating equipment2008Yes
Other devicesEN 54-17Part 17: Short circuit isolators2005 + AC:2007Yes
Other devicesEN 54-18Part 18: Input/output devices2005 + AC:2007Yes
DetectorsEN 54-20Part 20: Aspirating smoke detectors 2006 + AC:2008Yes
Other devicesEN 54-21Part 21: Alarm transmission and fault warning routing equipment2006Yes
DetectorsEN 54-22Part 22: Resettable line type heat detectors2015 + A1:2020No
Alarm devicesEN 54-23Part 23: Fire alarm devices - Visual alarm devices2010Yes
Alarm devicesEN 54-24Part 24: Component of voice alarm systems - Loudspeakers2008Yes
Other devicesEN 54-25Part 25: Components using radio links2008 + AC:2012Yes
DetectorsEN 54-26Part 26: Point fire detectors using carbon monoxide sensors2015No
DetectorsEN 54-27Part 27: Duct smoke detectors2015No
DetectorsEN 54-28Part 28: Non-resettable line-type heat detectors2016No
DetectorsEN 54-29Part 29: Multi-sensor fire detectors - Point detectors using a combination of smoke and heat sensors2015No
DetectorsEN 54-30Part 30: Multi-sensor fire detectors - Point detectors using a combination of carbon monoxide and heat sensors2015No
DetectorsEN 54-31Part 31: Multi-sensor fire detectors - Point detectors using a combination of smoke, carbon monoxide and optionally heat sensors2014 + A1:2016No
Application guidelinesCEN/TS 54-32Part 32: Guidelines for the planning, design, installation, commissioning, use and maintenance of voice alarm systems2015-07No

Withdrawn parts

Test fires of EN 54

The test fires TF1 to TF8 are used to test the fire sensitivity of the fire detectors according to the standard series EN 54.

The combustibles selected represent a spectrum of large and small combustion particles for both grey and black smoke. These include burning liquids, plastics and cellulosic (wood) materials, and glowing and smouldering fabrics. [9]

Test fires TF1 to TF8 according to EN 54 [10]
Fire typeCombustibleHeat

development

Upward

flow

Smoke

development

Aerosol

spectrum

Visible

part

TF1open cellulosic firewoodstrongstrongyesmainly invisibledark
TF2 Smoldering pyrolysis firewoodnegligibleweakyesvisiblebright
TF3glowing (smoldering) firecottonnegligiblevery weakyesmainly invisiblebright
TF4open plastics firepolyurethanestrongstrongyesmainly invisiblevery dark
TF5liquid firen-heptanestrongstrongyesmainly invisiblevery dark
TF6liquid firemethylated spiritstrongstrongnononenone
TF8liquid firedecalenenegligibleweakyesmainly invisiblevery dark

For smoke detectors according to EN 54-7 and fire detectors with smoke sensor (parts 12, 20 and 30 of EN 54) the test fires TF2, TF3, TF4 and TF5 are used. The EN 54-20 defines the following test fires with reduced fuel quantity for aspirating smoke detectors with enhanced or very high sensitivity (class A or B):

For flame detectors according to EN 54-10, the liquid fires TF5 and TF6 are used. TF5 (n-heptane) produces a yellow sooty flame and TF6 (methylated spirits) produces a clear invisible flame.

For CO fire detectors according to EN 54-26, the smoldering fires TF2 and TF3 are used.

For duct smoke detectors according to EN 54-27 the test fires TF2, TF4 and TF8 are used.

For multi-sensor fire detectors according to EN 54-29 and EN 54-31, the test fires TF1, TF2, TF3, TF4, TF5 and TF8 are used.

See also

Related Research Articles

<span class="mw-page-title-main">British Standards</span> Standards produced by BSI Group

British Standards (BS) are the standards produced by the BSI Group which is incorporated under a royal charter and which is formally designated as the national standards body (NSB) for the UK. The BSI Group produces British Standards under the authority of the charter, which lays down as one of the BSI's objectives to:

Set up standards of quality for goods and services, and prepare and promote the general adoption of British Standards and schedules in connection therewith and from time to time to revise, alter and amend such standards and schedules as experience and circumstances require.

<span class="mw-page-title-main">UL (safety organization)</span> Global safety certification company

The UL enterprise is a global safety science company headquartered in Northbrook, Illinois, composed of three organizations, UL Research Institutes, UL Standards & Engagement and UL Solutions.

<span class="mw-page-title-main">Smoke detector</span> Device that detects smoke, typically as an indicator of fire

A smoke detector is a device that senses smoke, typically as an indicator of fire. Smoke detectors are usually housed in plastic enclosures, typically shaped like a disk about 150 millimetres (6 in) in diameter and 25 millimetres (1 in) thick, but shape and size vary. Smoke can be detected either optically (photoelectric) or by physical process (ionization). Detectors may use one or both sensing methods. Sensitive alarms can be used to detect and deter smoking in banned areas. Smoke detectors in large commercial and industrial buildings are usually connected to a central fire alarm system.

<span class="mw-page-title-main">Fire door</span> Fire resistant door

A fire door is a door with a fire-resistance rating used as part of a passive fire protection system to reduce the spread of fire and smoke between separate compartments of a structure and to enable safe egress from a building or structure or ship. In North American building codes, it, along with fire dampers, is often referred to as a closure, which can be derated compared against the fire separation that contains it, provided that this barrier is not a firewall or an occupancy separation. In Europe national standards for fire doors have been harmonised with the introduction of the new standard EN 16034, which refers to fire doors as fire-resisting door sets. Starting September 2016, a common CE marking procedure was available abolishing trade barriers within the European Union for these types of products. In the UK, it is Part B of the Building Regulations that sets out the minimum requirements for the fire protection that must be implemented in all dwellings this includes the use of fire doors. All fire doors must be installed with the appropriate fire resistant fittings, such as the frame and door hardware, for it to fully comply with any fire regulations.

<span class="mw-page-title-main">Manual fire alarm activation</span> Button or lever to activate fire alarms

Manual fire alarm activation is the process of triggering a fire alarm through a call point, pull station, or other device. This usually causes the alarm to sound the evacuation signal for the relevant building or zone. Manual fire alarm activation requires human intervention, as distinct from automatic fire alarm activation such as that provided through the use of heat detectors and smoke detectors. It is, however, possible for call points/pull stations to be used in conjunction with automatic detection as part of the overall fire detection and alarm system. Systems in completed buildings tend to be wired in and include a control panel. Wireless activators are common during construction.

A helium mass spectrometer is an instrument commonly used to detect and locate small leaks. It was initially developed in the Manhattan Project during World War II to find extremely small leaks in the gas diffusion process of uranium enrichment plants. It typically uses a vacuum chamber in which a sealed container filled with helium is placed. Helium leaks out of the container, and the rate of the leak is detected by a mass spectrometer.

<span class="mw-page-title-main">Carbon monoxide detector</span> Device that measures carbon monoxide (CO)

A carbon monoxide detector or CO detector is a device that detects the presence of the carbon monoxide (CO) gas to prevent carbon monoxide poisoning. In the late 1990s Underwriters Laboratories changed the definition of a single station CO detector with a sound device to carbon monoxide (CO) alarm. This applies to all CO safety alarms that meet UL 2034 standard; however for passive indicators and system devices that meet UL 2075, UL refers to these as carbon monoxide detectors. Most CO detectors use a sensor with a defined, limited lifespan, and will not work indefinitely.

<span class="mw-page-title-main">Aspirating smoke detector</span>

An aspirating smoke detector (ASD) is a system used in active fire protection, consisting of a central detection unit which draws air through a network of pipes to detect smoke. The sampling chamber is based on a nephelometer that detects the presence of smoke particles suspended in air by detecting the light scattered by them in the chamber. ASDs can typically detect smoke before it is visible to the naked eye.

<span class="mw-page-title-main">Fire alarm system</span> A system, that works using multiple devices to warn of a fire or other types of emergencies

A fire alarm system is a building system designed to detect and alert occupants and emergency forces of the presence of smoke, fire, carbon monoxide, or other fire-related emergencies. Fire alarm systems are required in most commercial buildings. They may include smoke detectors, heat detectors, and manual fire alarm activation devices, all of which are connected to a Fire Alarm Control Panel (FACP) normally found in an electrical room or panel room. Fire alarm systems generally use visual and audio signalization to warn the occupants of the building. Some fire alarm systems may also disable elevators, which under most circumstances, are unsafe to use during a fire.

<span class="mw-page-title-main">Passive fire protection</span> Component or system to passively prevent the spread of fire

Passive fire protection (PFP) is components or systems of a building or structure that slows or impedes the spread of the effects of fire or smoke without system activation, and usually without movement. Examples of passive systems include floor-ceilings and roofs, fire doors, windows, and wall assemblies, fire-resistant coatings, and other fire and smoke control assemblies. Passive fire protection systems can include active components such as fire dampers.

<span class="mw-page-title-main">FEMA Urban Search and Rescue Task Force</span> Task force in American emergency management

A FEMA Urban Search and Rescue Task Force is a team of individuals specializing in urban search and rescue, disaster recovery, and emergency triage and medicine. The teams are deployed to emergency and disaster sites within six hours of notification. The Federal Emergency Management Agency (FEMA) created the Task Force concept to provide support for large scale disasters in the United States. FEMA provides financial, technical and training support for the Task Forces as well as creating and verifying the standards of Task Force personnel and equipment.

<span class="mw-page-title-main">BSI Group</span> National standards body of the UK

The British Standards Institution (BSI) is the national standards body of the United Kingdom. BSI produces technical standards on a wide range of products and services and also supplies certification and standards-related services to businesses.

A gas detector is a device that detects the presence of gases in an area, often as part of a safety system. A gas detector can sound an alarm to operators in the area where the leak is occurring, giving them the opportunity to leave. This type of device is important because there are many gases that can be harmful to organic life, such as humans or animals.

<span class="mw-page-title-main">Keymark</span>

The Keymark is a voluntary European certification mark demonstrating compliance with the European Standard (EN). It is owned by CEN, the European Committee for Standardization, and CENELEC, the European Committee for Electrotechnical Standardization.

<span class="mw-page-title-main">Fire damper</span>

Fire dampers are passive fire protection products used in heating, ventilation, and air conditioning (HVAC) ducts to prevent and isolate the spread of fire inside the ductwork through fire-resistance rated walls and floors. Fire/smoke dampers are similar to fire dampers in fire resistance rating, and also prevent the spread of smoke inside the ducts. When a rise in temperature occurs, the fire damper closes, usually activated by a thermal element which melts at temperatures higher than ambient but low enough to indicate the presence of a fire, allowing springs to close the damper blades. Fire dampers can also close following receipt of an electrical signal from a fire alarm system utilising detectors remote from the damper, indicating the sensing of heat or smoke in the building occupied spaces or in the HVAC duct system.

<span class="mw-page-title-main">Honeywell Gent</span> British manufacturer of life safety equipment

Honeywell Gent, formerly Gents' of Leicester, is a British manufacturer of life safety equipment based in Leicester, England. Established by John Thomas Gent, the company is thought to have started in 1872 however it could have been trading as early as the 1860s. The company had a workforce of several hundred at its height.

<span class="mw-page-title-main">Optical beam smoke detector</span>

An optical beam smoke detector is a device that uses a projected beam of light to detect smoke across large areas, typically as an indicator of fire. They are used to detect fires in buildings where standard point smoke detectors would either be uneconomical or restricted for use by the height of the building. Optical beam smoke detectors are often installed in warehouses as a cost-effective means of protecting large open spaces.

BS 5839 Part 1Fire detection and fire alarm systems for buildings – Part 1: Code of practice for design, installation, commissioning and maintenance of systems in non-domestic premises is a standard published by the British Standards Institution. BS 5839-1:2013 supersedes BS 5839-1:2002+A2:2008, which has been withdrawn. It s the first of 9 parts in a series on national standards relating to fire alarms.

EN 16034 refers to a set of European standards which specify the technical performance characteristics for fire resisting and/or smoke control products, or better known in common language as fire/smoke doors or fire/smoke proof doors. Compliance with this standard requires to fulfill the requirements of the Construction Product Regulation for construction products, which are placed on the EU market with the intention to become permanent parts of a construction.

<span class="mw-page-title-main">Fire Industry Association</span>

The Fire Industry Association (FIA) is a not-for-profit organisation formed originally by the merger of the Fire Extinguishing Trades Association (FETA) and the British Fire Protection Systems Association (BFPSA).

References

  1. "BS EN 2:1992, Classification of fires".
  2. "BS EN 3 - Portable fire extinguishers".
  3. "BS 5445-1:1977, EN 54-1:1976".
  4. "BS 5445-5:1977, EN 54-5:1976".
  5. "CEN". cen.eu.
  6. "EUROPA - European Commission - Enterprise - Regulatory policy - NANDO". Archived from the original on 9 July 2011. Retrieved 5 August 2011.
  7. Becky Reid. "BS EN 54 Standards". the Fire Industry Association ("FIA") .
  8. "BSI Shop - Buy British Standards".
  9. "ISO/TS 7240-9:2012, Fire detection and alarm systems — Part 9: Test fires for fire detectors". ISO.
  10. "EN 54 Test fires (in German)" (PDF). BHE.