Intrinsic safety

Last updated
Directive 2014/34/EU
European Union directive
Text with EEA relevance
Flag of Europe.svg
TitleEquipment and protective systems intended for use in potentially explosive atmospheres
Current legislation
60079-11:2023
EN standard
Reference60079-11:2023
StatusCurrent
TitleExplosive atmospheres - Part 11: Equipment protection by intrinsic safety "i"

Intrinsic safety (IS) is a protection technique for safe operation of electrical equipment in hazardous areas by limiting the energy, electrical and thermal, available for ignition. In signal and control circuits that can operate with low currents and voltages, the intrinsic safety approach simplifies circuits and reduces installation cost over other protection methods. Areas with dangerous concentrations of flammable gases or dust are found in applications such as petrochemical refineries and mines. As a discipline, it is an application of inherent safety in instrumentation. High-power circuits such as electric motors or lighting cannot use intrinsic safety methods for protection.

Contents

Intrinsic safety devices, can be sub-dividend in to:

Intrinsically safe apparatus

Intrinsically safe apparatuses are electrical devices that have connected circuits that are intrinsically safe circuits whilst in the hazardous area.

Associated apparatus

Associated apparatuses are electrical devices that have both intrinsically safe and non-intrinsically safe circuits and is designed in a way that the non-intrinsically safe circuits cannot negatively affect the intrinsically safe circuits. The apparatus is normally

Intrinsically safe circuit

An intrinsically safe circuit is designed to not be capable of causing ignition of a given explosive atmosphere, by any spark or any thermal effect. under normal operation and specified fault conditions.

Operating and design principles

In normal use, electrical equipment often creates tiny electric arcs (internal sparks) in switches, motor brushes, connectors, and in other places. Compact electrical equipment generates heat as well, which under some circumstances can become an ignition source.

There are multiple ways to make equipment safe for use in explosive-hazardous areas. Intrinsic safety (denoted by "i" in the ATEX and IECEx Explosion Classifications) is one of several available methods for electrical equipment. see Types of protection for more info.

For handheld electronics, intrinsic safety is the only realistic method that allows a functional device to be explosion protected. A device which is termed "intrinsically safe" has been designed to be incapable of producing heat or spark sufficient to ignite an explosive atmosphere, even if the device has experienced deterioration or has been damaged.

There are several considerations in designing intrinsically safe electronics devices:

Elimination of spark potential within components is accomplished by limiting the available energy in any given circuit and the system as a whole.

Temperature, under certain fault conditions such as an internal short in a semiconductor device, becomes an issue as the temperature of a component can rise to a level that can ignite some explosive gasses, even in normal use.

Safeguards, such as current limiting by resistors and fuses, must be employed to ensure that in no circumstance can a component reach a temperature that could cause autoignition of a combustible atmosphere. In the highly compact electronic devices used today PCBs often have component spacing that create the possibility of an arc between components if dust or other particulate matter works into the circuitry, thus component spacing, siting and isolation become important to the design.

The primary concept behind intrinsic safety is the restriction of available electrical and thermal energy in the system so that ignition of a hazardous atmosphere (explosive gas or dust) cannot occur. This is achieved by ensuring that only low voltages and currents enter the hazardous area, and that no significant energy storage is possible.

One of the most common methods for protection is to limit electric current by using series resistors (using types of resistors that always fail open); and limit the voltage with multiple zener diodes. In zener barriers dangerous incoming potentials are grounded, with galvanic isolation barriers there is no direct connection between the safe- and hazardous-area circuits by interposing a layer of insulation between the two. Certification standards for intrinsic safety designs (mainly IEC 60079-11 but since 2015 also IEC TS 60079-39) generally require that the barrier do not exceed approved levels of voltage and current with specified damage to limiting components.

Equipment or instrumentation for use in a hazardous area will be designed to operate with low voltage and current, and will be designed without any large capacitors or inductors that could discharge in a spark. The instrument will be connected, using approved wiring methods, back to a control panel in a non-hazardous area that contains safety barriers. The safety barriers ensure that, in normal operation, and with the application of faults according to the equipment protection level (EPL), even if accidental contact occurs between the instrument circuit and other power sources, no more than the approved voltage and current enters the hazardous area.

For example, during marine transfer operations when flammable products are transferred between the marine terminal and tanker ships or barges, two-way radio communication needs to be constantly maintained in case the transfer needs to stop for unforeseen reasons such as a spill. The United States Coast Guard requires that the two way radio must be certified as intrinsically safe.

Another example is intrinsically safe or explosion-proof mobile phones used in explosive atmospheres, such as refineries. Intrinsically safe mobile phones must meet special battery design criteria in order to achieve UL, ATEX directive, or IECEx certification for use in explosive atmospheres.

Only properly designed battery-operated, self-contained devices can be intrinsically safe by themselves. Other field devices and wiring are intrinsically safe only when employed in a properly designed IS system. Requirements for intrinsically safe electrical systems are given in the IEC 60079 series of standards.

Certifying agencies

Standards for intrinsic protection are mainly developed by International Electrotechnical Commission (IEC), [1] but different agencies also develop standards for intrinsic safety. Agencies may be run by governments or may be composed of members from insurance companies, manufacturers, and industries with an interest in safety standards. Certifying agencies allow manufacturers to affix a label or mark to identify that the equipment has been designed to the relevant product safety standards. Examples of such agencies in North America are the Factory Mutual Research Corporation, which certifies radios, Underwriters Laboratories (UL) that certifies mobile phones, and in Canada the Canadian Standards Association. [2] In the EU the standard for intrinsic safety certification is the CENELEC [3] standard EN 60079-11 and shall be certified according to the ATEX directive, while in other countries around the world the IEC standards are followed. To facilitate world trade, standards agencies around the world engage in harmonization activity so that intrinsically safe equipment manufactured in one country eventually might be approved for use in another without redundant, expensive testing and documentation.

See also

Related Research Articles

<span class="mw-page-title-main">Electrostatic discharge</span> Sudden flow of electric current between two electrically charged objects by contact

Electrostatic discharge (ESD) is a sudden and momentary flow of electric current between two differently-charged objects when brought close together or when the dielectric between them breaks down, often creating a visible spark associated with the static electricity between the objects.

<span class="mw-page-title-main">Static electricity</span> Imbalance of electric charges within or on the surface of a material

Static electricity is an imbalance of electric charges within or on the surface of a material. The charge remains until it can move away by an electric current or electrical discharge. The word "static" is used to differentiate it from current electricity, where an electric charge flows through an electrical conductor.

<span class="mw-page-title-main">Surge protector</span> Protects electrical devices from voltage spikes

A surge protector (or spike suppressor, surge suppressor, surge diverter, surge protection device or transient voltage surge suppressor is an appliance or device intended to protect electrical devices in alternating current circuits from voltage spikes with very short duration measured in microseconds, which can arise from a variety of causes including lightning strikes in the vicinity.

Appliance classes specify measures to prevent dangerous contact voltages on unenergized parts, such as the metallic casing, of an electronic device. In the electrical appliance manufacturing industry, the following appliance classes are defined in IEC 61140 and used to differentiate between the protective-earth connection requirements of devices.

<span class="mw-page-title-main">Electrical wiring</span> Electrical installation of cabling

Electrical wiring is an electrical installation of cabling and associated devices such as switches, distribution boards, sockets, and light fittings in a structure.

Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.

<span class="mw-page-title-main">High voltage</span> Electrical potential which is large enough to cause damage or injury

High voltage electricity refers to electrical potential large enough to cause injury or damage. In certain industries, high voltage refers to voltage above a certain threshold. Equipment and conductors that carry high voltage warrant special safety requirements and procedures.

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

<span class="mw-page-title-main">Extra-low voltage</span> Electrical standard designed to protect against electric shock

Extra-low voltage (ELV) is an electricity supply voltage and is a part of the low-voltage band in a range which carries a low risk of dangerous electrical shock. There are various standards that define extra-low voltage. The International Electrotechnical Commission (IEC) and the UK IET define an ELV device or circuit as one in which the electrical potential between two conductors or between an electrical conductor and earth (ground) does not exceed 120 volts (V) for ripple-free direct current (DC) or 50 VRMS for alternating current (AC).

<span class="mw-page-title-main">Electrical equipment in hazardous areas</span> Electrical equipment in places where fire or explosion hazards may exist

In electrical and safety engineering, hazardous locations are places where fire or explosion hazards may exist. Sources of such hazards include gases, vapors, dust, fibers, and flyings, which are combustible or flammable. Electrical equipment installed in such locations can provide an ignition source, due to electrical arcing, or high temperatures. Standards and regulations exist to identify such locations, classify the hazards, and design equipment for safe use in such locations.

<span class="mw-page-title-main">ATEX directive</span> EU ATEX Directive on workplaces with an explosive atmosphere

The ATEX directives are two EU directives describing the minimum safety requirements for workplaces and equipment used in explosive atmospheres. The name is an initialization of the term ATmosphères EXplosibles.

<span class="mw-page-title-main">Escape breathing apparatus</span> Self contained breathing apparatus providing gas to escape from a hazardous environment

Escape breathing apparatus, also called escape respirators, escape sets, self-rescuer masks, emergency life saving apparatus (ELSA), emergency escape breathing devices (EEBD), and Respiratory Protective Smoke Escape Devices (RPED), are portable breathing apparatus that provide the wearer with respiratory protection for a limited period, intended for escape from or through an environment where there is no breathable ambient atmosphere. This includes escape through water and in areas containing harmful gases or fumes or other atmospheres immediately dangerous to life or health (IDLH).

<span class="mw-page-title-main">High-voltage switchgear</span>

High voltage switchgear is any switchgear used to connect or disconnect a part of a high-voltage power system. This equipment is essential for the protection and safe operation, without interruption, of a high voltage power system, and is important because it is directly linked to the quality of the electricity supply.

<span class="mw-page-title-main">Positive pressure enclosure</span> A chamber in which fresh air is pumped in to help remove dangerous fumes

A positive pressure enclosure, also known as a welding habitat or hot work habitat, is a chamber used to provide a safe working environment for performing hot work in the presence of explosive gases or vapors. They are commonly used in welding environments and are associated with the offshore oil industry.

Functional safety is the part of the overall safety of a system or piece of equipment that depends on automatic protection operating correctly in response to its inputs or failure in a predictable manner (fail-safe). The automatic protection system should be designed to properly handle likely systematic errors, hardware failures and operational/environmental stress.

IEC 60204-1 / EN 60204 Safety of machinery – Electrical equipment of machines – Part 1: General requirements

CompEx is a global certification scheme for electrical and mechanical craftspersons and designers working in potentially explosive atmospheres. The scheme is operated by JTLimited, UK and is accredited by UKAS to ISO/IEC 17024.

The Association of Electrical and Mechanical Trades (AEMT) is a United Kingdom trade association representing engineering companies in the service and repair industry.

Ethernet Advanced Physical Layer (Ethernet-APL) describes a physical layer for the Ethernet communication technology which is especially developed for the requirements of the process industries. The development of Ethernet-APL was determined by the need for communication at high speeds and over long distances, the supply of power and communications signals via common single, twisted-pair (2-wire) cable as well as protective measures for the safe use within explosion hazardous areas.

References

  1. "Homepage". www.iec.ch.
  2. "Intrinsic Safety Approvals for Radio Communications Equipment". Intrinsic Safety (IS) Approvals. American Communication Systems, Inc. Retrieved 25 Sep 2012.
  3. "CEN-CENELEC". CEN-CENELEC.

Further reading