Isolated ground

Last updated

An isolated ground (IG) (or Functional Earth (FE) in European literature) is a ground connection to a local earth electrode from equipment where the main supply uses a different earthing arrangement, one of the common earthing arrangements used with domestic mains supplies. It is distinct from a TT earthing system where the system electrode is also part of the safety earthing and not neutral bonded. In most countries where regulation permits it, TT is preferred for such systems as conventional wiring techniques can be used. Examples where an IG may be required include radio transmitters where it is not desired for RF currents associated with the antenna and its earthing to enter the mains supply wiring, and in reverse, for sensitive apparatus that should be protected from supply borne interference. Great care has to be taken to maintain system safety with such systems, and each case has to be carefully considered.

Contents

Description

The primary reason for the use of isolated grounds (IG) is to provide a noise-free ground return, separate from the equipment grounding (EG) return. The EG circuit includes all of the metal conduit, outlet boxes, and metal enclosures that contain the wiring and must be grounded to provide a safe return path in case of fault currents. The IG provides an insulated, separate ground path for the ground reference in electronic equipment, such as computers, hospital equipment, and audio equipment. IG does not break ground loops, which can damage equipment like computers, printers, etc.. Interconnected computer equipment often benefits from single-point grounding.

IG is only used with special equipment that requires it. The IG is typically insulated and separate all the way back to the point of earth grounding rod outside of the building. The IG is NOT connected to a neutral or any other earthing network. Due to the installation of a separate, insulated conductor and the associated special outlets required, IG circuits are more expensive to install than standard power circuits. [1]

Its main downside is that an isolated grounding connection has higher impedance than a non-isolated grounding connection, and no redundancy, so safety is reduced. Isolated ground receptacles are allowed in patient care areas, but only when installed outside the immediate patient care vicinity. [2]

Domestic supplies

Until the 1950s, isolated ground domestic mains supplies tended to have no Residual-Current Device (RCD) or Earth Leakage Circuit Breaker (ELCB), and too high a ground impedance to blow a fuse if a live-to-earth fault occurred. This could leave metalwork in the house live. The use of Residual Current Devices (RCDs) or formerly ELCBs with such installs solved this problem. Such installs are called EEBAD (Earthed Equipotential Bonding and Automatic Disconnection).


Noise

An isolated ground, if installed correctly, can reduce some electrical noise. [3] However, complete power conditioning and protection usually requires additional devices such as a surge protector or an uninterruptible power supply. [4] If the receptacle is not installed correctly, it can create a dangerous installation. [3]

See also

Related Research Articles

Ground (electricity) Reference point in an electrical circuit from which voltages are measure

In electrical engineering, ground or earth is the reference point in an electrical circuit from which voltages are measured, a common return path for electric current, or a direct physical connection to the earth.

Single-wire earth return

Single-wire earth return (SWER) or single-wire ground return is a single-wire transmission line which supplies single-phase electric power from an electrical grid to remote areas at low cost. Its distinguishing feature is that the earth is used as the return path for the current, to avoid the need for a second wire to act as a return path.

Electrical wiring in North America follows regulations and standards for installation of building wiring which ultimately provides mains electricity.

Residual-current device Electrical safety device used in household wiring

A residual-current device (RCD), or residual-current circuit breaker (RCCB), is a device that quickly breaks an electrical circuit to prevent serious harm from an ongoing electric shock. Injury may still occur in some cases, for example if a human falls after receiving a shock, or if the person touches both conductors at the same time.

Earth leakage circuit breaker

An Earth-leakage circuit breaker (ELCB) is a safety device used in electrical installations with high Earth impedance to prevent shock. It detects small stray voltages on the metal enclosures of electrical equipment, and interrupts the circuit if a dangerous voltage is detected. Once widely used, more recent installations instead use residual-current devices which instead detect leakage current directly.

National Electrical Code

The National Electrical Code (NEC), or NFPA 70, is a regionally adoptable standard for the safe installation of electrical wiring and equipment in the United States. It is part of the National Fire Code series published by the National Fire Protection Association (NFPA), a private trade association. Despite the use of the term "national", it is not a federal law. It is typically adopted by states and municipalities in an effort to standardize their enforcement of safe electrical practices. In some cases, the NEC is amended, altered and may even be rejected in lieu of regional regulations as voted on by local governing bodies.

A distribution board is a component of an electricity supply system that divides an electrical power feed into subsidiary circuits while providing a protective fuse or circuit breaker for each circuit in a common enclosure. Normally, a main switch, and in recent boards, one or more residual-current devices (RCDs) or residual current breakers with overcurrent protection (RCBOs) are also incorporated.

In the electrical appliance manufacturing industry, the following IEC protection classes are defined in IEC 61140 and used to differentiate between the protective-earth connection requirements of devices.

Ground and neutral are circuit conductors used in alternating current electrical systems. The ground circuit is connected to earth, and neutral circuit is usually connected to ground. As the neutral point of an electrical supply system is often connected to earth ground, ground and neutral are closely related. Under certain conditions, a conductor used to connect to a system neutral is also used for grounding (earthing) of equipment and structures. Current carried on a grounding conductor can result in objectionable or dangerous voltages appearing on equipment enclosures, so the installation of grounding conductors and neutral conductors is carefully defined in electrical regulations. Where a neutral conductor is used also to connect equipment enclosures to earth, care must be taken that the neutral conductor never rises to a high voltage with respect to local ground.

Electrical wiring Electrical installation of cabling

Electrical wiring is an electrical installation of cabling and associated devices such as switches, distribution boards, sockets, and light fittings in a structure.

Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.

The prospective short-circuit current (PSCC), available fault current, or short-circuit making current is the highest electric current which can exist in a particular electrical system under short-circuit conditions. It is determined by the voltage and impedance of the supply system. It is of the order of a few thousand amperes for a standard domestic mains electrical installation, but may be as low as a few milliamperes in a separated extra-low voltage (SELV) system or as high as hundreds of thousands of amps in large industrial power systems.

An earthing system or grounding system (US) connects specific parts of an electric power system with the ground, typically the Earth's conductive surface, for safety and functional purposes. The choice of earthing system can affect the safety and electromagnetic compatibility of the installation. Regulations for earthing systems vary considerably among countries, though most follow the recommendations of the International Electrotechnical Commission. Regulations may identify special cases for earthing in mines, in patient care areas, or in hazardous areas of industrial plants.

Electrical bonding is the practice of intentionally electrically connecting all exposed metal items not designed to carry electricity in a room or building as protection from electric shock. If a failure of electrical insulation occurs, all bonded metal objects in the room will have substantially the same electrical potential, so that an occupant of the room cannot touch two objects with significantly different potentials. Even if the connection to a distant earth is lost, the occupant will be protected from dangerous potential differences.

NEMA connector

NEMA connectors are power plugs and receptacles used for AC mains electricity in North America and other countries that use the standards set by the US National Electrical Manufacturers Association. NEMA wiring devices are made in current ratings from 15 to 60 amperes (A), with voltage ratings from 125 to 600 volts (V). Different combinations of contact blade widths, shapes, orientations, and dimensions create non-interchangeable connectors that are unique for each combination of voltage, electric current carrying capacity, and grounding system.

In an electric power system, a fault or fault current is any abnormal electric current. For example, a short circuit is a fault in which current bypasses the normal load. An open-circuit fault occurs if a circuit is interrupted by some failure. In three-phase systems, a fault may involve one or more phases and ground, or may occur only between phases. In a "ground fault" or "earth fault", current flows into the earth. The prospective short-circuit current of a predictable fault can be calculated for most situations. In power systems, protective devices can detect fault conditions and operate circuit breakers and other devices to limit the loss of service due to a failure.

Earth potential rise The rise of voltage of local earth when a large current flows through an earth grid impedance

In electrical engineering, earth potential rise (EPR) also called ground potential rise (GPR) occurs when a large current flows to earth through an earth grid impedance. The potential relative to a distant point on the Earth is highest at the point where current enters the ground, and declines with distance from the source. Ground potential rise is a concern in the design of electrical substations because the high potential may be a hazard to people or equipment.

Electrical outlet tester Device to verify the function of an electrical outlet

An electrical outlet tester, receptacle tester, or socket tester is a small device containing a power plug and three indicator lights, used for quickly detecting some types of incorrectly-wired electrical wall outlets. The tester is easily carried in a pocket, can be used with little training, and can identify some common wiring problems, but can fail to indicate other types of wiring defects.

In building wiring installed with separate neutral and protective ground bonding conductors, a bootleg ground is a connection between the neutral side of a receptacle or light fixture and the ground lug or enclosure of the wiring device. This connects the neutral side of the receptacle to the casing of an appliance or lamp. It can be a hazard because the neutral wire is a current-carrying conductor, which means the casing can become energized. In addition, a fault condition to a bootleg ground will not trip a GFCI breaker or receptacle that is wired from the load side of a GFCI receptacle.

A GCM or ground continuity monitor is an electrical safety device that monitors the impedance to ground of a temporary electrical circuit and can provide indication in the event impedance rises to an unsafe value. A GCM is either an external testing device or a cord mounted device that measures the electrical continuity of a circuit’s path to ground.

References

  1. 2017 NEC 250.146 (D)
  2. 2017 NEC 517.16
  3. 1 2 Holt, Mike (1 October 2001), "The Basics of Isolated Grounding Receptacles", EC&M, retrieved 25 March 2011
  4. Maxcy, Dan (6 January 2003), Isolated Ground Circuits (PDF), p. 3, archived from the original (PDF) on 23 September 2010, retrieved 25 March 2011