In an electrical system, a ground loop or earth loop occurs when two points of a circuit are intended to have the same ground reference potential but instead have a different potential between them. [1] This is typically caused when enough current is flowing in the connection between the two ground points to produce a voltage drop and cause two points to be at different potentials. Current may be produced in a circular ground connection (ground loop) by electromagnetic induction.

Contents

Ground loops are a major cause of noise, hum, and interference in audio, video, and computer systems. Wiring practices that protect against ground loops include ensuring that all vulnerable signal circuits are referenced to one point as ground. The use of differential signaling can provide rejection of ground-induced interference. Removal of safety ground connections to equipment in an effort to eliminate ground loops also eliminates the protection the safety ground connection is intended to provide.

Description

A ground loop is caused by the interconnection of electrical devices that results in multiple paths to ground, thereby forming closed conductive loops through the ground connections. A common example is two electrical devices each connected to a mains power outlet by a three-conductor cable and plug containing a protective ground conductor for safety. When signal cables are connected between both devices, the shield of the signal cable is typically connected to the grounded chassis of both devices. This forms a closed loop through the ground conductors of the power cords, which are connected through the building wiring.

In the vicinity of electric power wiring there will always be stray magnetic fields, particularly from utility lines oscillating at 50 or 60  hertz. These ambient magnetic fields passing through the ground loop will induce a current in the loop by electromagnetic induction. The ground loop acts as a single-turn secondary winding of a transformer, the primary being the summation of all current-carrying conductors nearby. The amount of current induced will depend on the magnitude and proximity of nearby currents. The presence of high-power equipment such as industrial motors or transformers can increase the interference. Since the conductors comprising the ground loop usually have very low resistance, often below one ohm, even weak magnetic fields can induce significant currents.

Since the ground conductor of the signal cable linking the two devices is part of the signal path of the cable, the alternating ground current flowing through the cable can introduce electrical interference in the signal. The induced alternating current flowing through the resistance of the cable ground conductor will cause a small AC voltage drop across the cable ground. This is added to the signal applied to the input of the next stage. In audio equipment, the 50 or 60 Hz interference may be heard as a hum in the speakers. In a video system it may cause distortion or syncing problems. In computer cables it can cause slowdowns or failures of data transfer.

Ground loops can also exist within the internal circuits of electronic equipment, as design flaws.

Addition of signal interconnection cables to a system where equipment enclosures are already required to be bonded to ground can create ground loops. Proper design of such a system will satisfy both safety grounding requirements and signal integrity. For this reason, in some large professional installations such as recording studios, it is sometimes the practice to provide two completely separate ground connections to equipment bays. One is the normal safety ground that connects to exposed metalwork, the other is a technical ground for cable screens and the like. [2]

Representative circuit

Simplified circuit illustrating a ground loop Ground loop.svg
Simplified circuit illustrating a ground loop

The circuit diagram illustrates a simple ground loop. Circuit 1 (left) and circuit 2 (right) share a common path to ground of resistance . Ideally, this ground conductor would have no resistance (), yielding no voltage drop across it (), keeping the connection point between the circuits at a constant ground potential. In that case, the output of circuit 2 is simply .

However, if this ground conductor has some resistance (), then it forms a voltage divider with . As a result, if a current () is flowing through from circuit 1, then a voltage drop across of occurs, causing the shared ground connection to no longer be at the actual ground potential. This voltage across the ground conductor is applied to circuit 2 and added to its output:

Thus the two circuits are no longer isolated from each other and circuit 1 can introduce interference into the output of circuit 2. If circuit 2 is an audio system and circuit 1 has large AC currents flowing in it, the interference may be heard as a 50 or 60 Hz hum in the speakers. Also, both circuits have voltage on their grounded parts that may be exposed to contact, possibly presenting a shock hazard. This is true even if circuit 2 is turned off.

Although ground loops occur most often in the ground conductors of electrical equipment, similar loops can occur wherever two or more circuits share a common current path, which can cause a similar problematic voltage drop along the conductor if enough current flows.

Common ground loops

A common type of ground loop is due to faulty interconnections between electronic components, such as laboratory or recording studio equipment, or home component audio, video, and computer systems. This creates inadvertent closed loops in the ground wiring circuit, which can allow stray 50/60 Hz AC current to be induced and flow through the ground conductors of signal cables. [3] [4] [5] [6] The voltage drops in the ground system caused by these currents are added to the signal path, introducing noise and hum into the output. The loops can include the building's utility wiring ground system when more than one component is grounded through the protective earth (third wire) in their power cords.

Ground currents on signal cables

Fig. 1: A typical signal cable S between electronic components, with a current I flowing through the shield conductor Signal cable with ground current.svg
Fig. 1: A typical signal cable S between electronic components, with a current I flowing through the shield conductor

The symptoms of a ground loop, ground noise and hum in electrical equipment, are caused by current flowing in the ground or shield conductor of a cable. Fig. 1 shows a signal cable S linking two electronic components, including the typical line driver and receiver amplifiers (triangles). [5] The cable has a ground or shield conductor which is connected to the chassis ground of each component. The driver amplifier in component 1 (left) applies signal V1 between the signal and ground conductors of the cable. At the destination end (right), the signal and ground conductors are connected to a differential amplifier. This produces the signal input to component 2 by subtracting the shield voltage from the signal voltage to eliminate common-mode noise picked up by the cable

If a current I from a separate source is flowing through the ground conductor, the resistance R of the conductor will create a voltage drop along the cable ground of IR, so the destination end of the ground conductor will be at a different potential than the source end

Since the differential amplifier has high impedance, little current flows in the signal wire, therefore there is no voltage drop across it: The ground voltage appears to be in series with the signal voltage V1 and adds to it

If I is an AC current this can result in noise added to the signal path in component 2.

Sources of ground current

The diagrams in this section show a typical ground loop caused by a signal cable S connecting two grounded electronic components C1 and C2. The loop consists of the signal cable's ground conductor, which is connected through the components' metal chassis to the ground wires P in their power cords, which are plugged into outlet grounds which are connected through the building's utility ground wire system G.

Such loops in the ground path can cause currents in signal cable grounds by two main mechanisms:

Solutions

The solution to ground loop noise is to break the ground loop, or otherwise prevent the current from flowing. Several approaches are available.

A hazardous technique sometimes used by amateurs is to break the third wire ground conductor P in one of the component's power cords, by removing the ground pin on the plug, or using a cheater plug. This creates an electric shock hazard by leaving one of the components ungrounded. [4] [5]

Balanced lines

A more comprehensive solution is to use equipment that employs differential signaling. Ground noise can only get into the signal path in single-ended signaling, in which the ground or shield conductor serves as one side of the signal path. When the signal is sent as a differential signal along a pair of wires, neither of which are connected to ground, any noise from the ground system induced in the signal lines is a common-mode signal, identical in both wires. Since the line receiver at the destination end only responds to differential signals, a difference in voltage between the two lines, the common-mode noise is canceled out. Thus these systems are very immune to electrical noise, including ground noise. Professional and scientific equipment often uses differential signaling with balanced lines.

In low frequency audio and instrumentation systems

If, for example, a domestic HiFi system has a grounded turntable and a grounded preamplifier connected by a thin screened cable (or cables, in a stereo system) using phono connectors, the cross-section of copper in the cable screen(s) is likely to be less than that of the protective ground conductors for the turntable and the preamplifier. So, when a current is induced in the loop, there will be a voltage drop along the signal ground return. This is directly additive to the wanted signal and will result in objectionable hum. For instance, if a current of 1 mA at the local power frequency is induced in the ground loop, and the resistance of the screen of the signal cable is 100 mΩ, the voltage drop will be = 100 µV. This is a significant fraction of the output voltage of a moving coil pickup cartridge, and imposes an objectionable hum on the cartridge output. [lower-alpha 1]

In a more complex situation, such as sound reinforcement systems, public address systems, music instrument amplifiers, recording studio and broadcast studio equipment, there are many signal sources in mains-powered equipment feeding many inputs on other equipment and interconnection may result in hum problems. Attempting to cure these problems by removing the protective ground conductor creates a shock hazard. Solving hum problems must be done in the signal interconnections, and this is done in two main ways, which may be combined.

Isolation

Isolation is the quickest, quietest and most foolproof method of resolving hum problems. The signal is isolated by a small transformer, such that the source and destination equipment each retain their own protective ground connections, but there is no through connection from one to the other in the signal path. By transformer isolating all unbalanced connections, the unbalanced connections are converted to balanced connections. In analog applications such as audio, the physical limitations of the transformers cause some signal degradation, by limiting bandwidth and adding some distortion.

Balanced interconnection

Balanced connections see the spurious noise due to ground loop current as common-mode interference while the signal is differential, enabling them to be separated at the destination by circuits having a high common-mode rejection ratio. This rejection can be accomplished with transformers or semiconductor output drivers and line receivers.

With the increasing trend towards digital processing and transmission of audio signals, the full range of isolation by small pulse transformers, optocouplers or fiber optics become more useful. Standard protocols such as S/PDIF, AES3 or TOSLINK are available in relatively inexpensive equipment and allow full isolation, so ground loops need not arise, especially when connecting between audio systems and computers.

In instrumentation systems, the use of differential inputs with high common-mode rejection ratio, to minimize the effects of induced AC signals on the parameter to be measured, is widespread. It may also be possible to introduce narrow notch filters at the power frequency and its lower harmonics; however, this can not be done in audio systems due to the objectionable audible effects on the wanted signal.

In analog video systems

In analog video, mains hum can be seen as hum bars (bands of slightly different brightness) scrolling vertically up the screen. These are frequently seen with video projectors where the display device has its case grounded via a 3-prong plug, and the other components have a floating ground connected to the CATV coax. In this situation the video cable is grounded at the projector end to the home electrical system, and at the other end to the cable TV's ground, inducing a current through the cable which distorts the picture. The problem is best solved with an isolation transformer in the CATV RF feed, a feature included in some CATV box designs.

Ground loop issues with television coaxial cable can affect any connected audio device such as a receiver. Even if all of the audio and video equipment in, for example, a home theatre system is plugged into the same power outlet, and thus all share the same ground, the coaxial cable entering the TV may be grounded by the cable company to a different point than that of the house's electrical ground creating a ground loop, and causing undesirable mains hum in the system's speakers.

In digital and RF systems

In digital systems, which commonly transmit data serially (RS-232, RS-485, USB, FireWire, DVI, HDMI etc.) the signal voltage is often much larger than induced power frequency AC on the connecting cable screens. Of those protocols listed, only RS-232 is single-ended with ground return, but it is a large signal, typically + and - 12V, all the others being differential.

Differential signaling must use a balanced line to ensure that the signal does not radiate and that induced noise from a ground loop is a common-mode signal and can be removed at the differential receiver.

Many data communications systems such as Ethernet 10BASE-T, 100BASE-TX and 1000BASE-T, use DC-balanced encoding such as Manchester code. The ground loop(s) which would occur in most installations are avoided by using signal-isolating transformers.

Other systems break the ground loop at data frequencies by fitting small ferrite cores around the connecting cables near each end or just inside the equipment boundary. These form a common-mode choke which inhibits unbalanced current flow, without affecting the differential signal.

Coaxial cables used at radio frequencies may be wound several times through a ferrite core to add a useful amount of common-mode inductance. This limits the flow of unwanted high-frequency common-mode current along the cable shield.

Where no power need be transmitted, only digital data, the use of fiber optics can remove many ground loop problems, and sometimes safety problems too. Optical isolators or optocouplers are frequently used to provide ground loop isolation, and often safety isolation and can help prevent fault propagation.

Internal ground loops in equipment

Generally, the analog and digital parts of the circuit are in separate areas of the PCB, with their own ground planes to obtain the necessary low inductance grounding and avoid ground bounce. These are tied together at a carefully chosen star point. Where analog-to-digital converters (ADCs) are in use, the star point may have to be at or very close to the ground terminals of the ADC(s). Phase lock loop circuits are particularly vulnerable because the VCO loop filter circuit is working with sub-microvolt signals when the loop is locked, and any disturbance will cause frequency jitter and possible loss of lock.

In circuit design

Grounding and the potential for ground loops are also important considerations in circuit design. In many circuits, large currents may exist through the ground plane, leading to voltage differences of the ground reference in different parts of the circuit, which can lead to hum and other problems. Techniques exist to avoid ground loops, and otherwise, guarantee good grounding:

See also

Notes

  1. In practice, this case usually does not happen because the pickup cartridge, an inductive voltage source, need have no connection to the turntable metalwork, and so the signal ground is isolated from the chassis or protective ground at that end of the link. Therefore, there is no current loop, and no hum problem due directly to the grounding arrangements.

Related Research Articles

In telecommunications and professional audio, a balanced line or balanced signal pair is an electrical circuit consisting of two conductors of the same type, both of which have equal impedances along their lengths, to ground, and to other circuits. The primary advantage of the balanced line format is good rejection of common-mode noise and interference when fed to a differential device such as a transformer or differential amplifier.

<span class="mw-page-title-main">Ground (electricity)</span> Reference point in an electrical circuit from which voltages are measured

In electrical engineering, ground or earth may be a reference point in an electrical circuit from which voltages are measured, a common return path for electric current, or a direct physical connection to the Earth.

<span class="mw-page-title-main">Coaxial cable</span> Electrical cable type with concentric inner conductor, insulator, and conducting shield

Coaxial cable, or coax, is a type of electrical cable consisting of an inner conductor surrounded by a concentric conducting shield, with the two separated by a dielectric ; many coaxial cables also have a protective outer sheath or jacket. The term coaxial refers to the inner conductor and the outer shield sharing a geometric axis.

Balanced audio is a method of interconnecting audio equipment using balanced interfaces. This type of connection is very important in sound recording and production because it allows the use of long cables while reducing susceptibility to external noise caused by electromagnetic interference. The balanced interface guarantees that induced noise appears as common-mode voltages at the receiver which can be rejected by a differential device.

<span class="mw-page-title-main">Balun</span> Electrical device

A balun is an electrical device that allows balanced and unbalanced lines to be interfaced without disturbing the impedance arrangement of either line. A balun can take many forms and may include devices that also transform impedances but need not do so. Sometimes, in the case of transformer baluns, they use magnetic coupling but need not do so. Common-mode chokes are also used as baluns and work by eliminating, rather than rejecting, common mode signals.

In electrical engineering, partial discharge (PD) is a localized dielectric breakdown (DB) of a small portion of a solid or fluid electrical insulation (EI) system under high voltage (HV) stress. While a corona discharge (CD) is usually revealed by a relatively steady glow or brush discharge (BD) in air, partial discharges within solid insulation system are not visible.

<span class="mw-page-title-main">Isolation transformer</span> Electrical component

An isolation transformer is a transformer used to transfer electrical power from a source of alternating current (AC) power to some equipment or device while isolating the powered device from the power source, usually for safety reasons or to reduce transients and harmonics. Isolation transformers provide galvanic isolation; no conductive path is present between source and load. This isolation is used to protect against electric shock, to suppress electrical noise in sensitive devices, or to transfer power between two circuits which must not be connected. A transformer sold for isolation is often built with special insulation between primary and secondary, and is specified to withstand a high voltage between windings.

<span class="mw-page-title-main">Ground and neutral</span> In mains electricity, part of a circuit connected to ground or earth

In electrical engineering, ground and neutral are circuit conductors used in alternating current (AC) electrical systems. The neutral conductor returns current to the supply. To limit the effects of leakage current from higher-voltage systems, the neutral conductor is often connected to earth ground at the point of supply. A ground conductor is not intended to carry current for normal operation of the circuit, but instead connects exposed metallic components to earth ground. A ground conductor only carries significant current if there is a circuit fault that would otherwise energize exposed conductive parts and present a shock hazard. Circuit protection devices may detect a fault to a grounded metal enclosure and automatically de-energize the circuit, or may provide a warning of a ground fault.

<span class="mw-page-title-main">Differential signalling</span> Method for electrically transmitting information

Differential signalling is a method for electrically transmitting information using two complementary signals. The technique sends the same electrical signal as a differential pair of signals, each in its own conductor. The pair of conductors can be wires in a twisted-pair or ribbon cable or traces on a printed circuit board.

<span class="mw-page-title-main">Shielded cable</span> Electric cable with metal jacket (shield) to prevent magnetic interference

A shielded cable or screened cable is an electrical cable that has a common conductive layer around its conductors for electromagnetic shielding. This shield is usually covered by an outermost layer of the cable. Common types of cable shielding can most broadly be categorized as foil type, contraspiralling wire strands or both. A longitudinal wire may be necessary with dielectric spiral foils to short out each turn.

Mains hum, electric hum, cycle hum, or power line hum is a sound associated with alternating current which is twice the frequency of the mains electricity. The fundamental frequency of this sound is usually double that of fundamental 50/60 Hz, i.e. 100/120 Hz, depending on the local power-line frequency. The sound often has heavy harmonic content above 50/60 Hz. Because of the presence of mains current in mains-powered audio equipment as well as ubiquitous AC electromagnetic fields from nearby appliances and wiring, 50/60 Hz electrical noise can get into audio systems, and is heard as mains hum from their speakers. Mains hum may also be heard coming from powerful electric power grid equipment such as utility transformers, caused by mechanical vibrations induced by magnetostriction in magnetic core. Onboard aircraft the frequency heard is often higher pitched, due to the use of 400 Hz AC power in these settings because 400 Hz transformers are much smaller and lighter.

An earthing system or grounding system (US) connects specific parts of an electric power system with the ground, typically the Earth's conductive surface, for safety and functional purposes. The choice of earthing system can affect the safety and electromagnetic compatibility of the installation. Regulations for earthing systems vary among countries, though most follow the recommendations of the International Electrotechnical Commission (IEC). Regulations may identify special cases for earthing in mines, in patient care areas, or in hazardous areas of industrial plants.

A radio transmitter or receiver is connected to an antenna which emits or receives the radio waves. The antenna feed system or antenna feed is the cable or conductor, and other associated equipment, which connects the transmitter or receiver with the antenna and makes the two devices compatible. In a radio transmitter, the transmitter generates an alternating current of radio frequency, and the feed system feeds the current to the antenna, which converts the power in the current to radio waves. In a radio receiver, the incoming radio waves excite tiny alternating currents in the antenna, and the feed system delivers this current to the receiver, which processes the signal.

<span class="mw-page-title-main">Noise (electronics)</span> Random fluctuation in an electrical signal

In electronics, noise is an unwanted disturbance in an electrical signal.

<span class="mw-page-title-main">Transformer types</span> Overview of electrical transformer types

A variety of types of electrical transformer are made for different purposes. Despite their design differences, the various types employ the same basic principle as discovered in 1831 by Michael Faraday, and share several key functional parts.

In electrical engineering, a balanced circuit is electronic circuitry for use with a balanced line, or the balanced line itself. Balanced lines are a common method of transmitting many types of electrical signals between two points on two wires. In a balanced line, the two signal lines are of a matched impedance to help ensure that interference, induced in the line, is common-mode and can be removed at the receiving end by circuitry with good common-mode rejection. To maintain the balance, circuit blocks which interface to the line or are connected in the line must also be balanced.

In electrical engineering, a common-mode signal is the identical component of voltage present at both input terminals of an electrical device. In telecommunication, the common-mode signal on a transmission line is also known as longitudinal voltage.

A floating ground is a reference point for electrical potential in a circuit which is galvanically isolated from actual earth ground.

<span class="mw-page-title-main">Sheath current filter</span> Electronic components

Sheath current filters are electronic components that can prevent noise signals travelling in the sheath of sheathed cables, which can cause interference. Using sheath current filters, ground loops causing mains hum and high frequency common-mode signals can be prevented.

This glossary of electrical and electronics engineering is a list of definitions of terms and concepts related specifically to electrical engineering and electronics engineering. For terms related to engineering in general, see Glossary of engineering.

References

  1. "Ground Loop", IEEE Std. 100 - Authoritative Dictionary of Standards Terms (Seventh ed.), IEEE Press, p. 494, 2000, ISBN   0738126012
  2. 1 2 3 Vijayaraghavan, G.; Mark Brown; Malcolm Barnes (December 30, 2008). "8.11 Avoidance of earth loop". Electrical noise and mitigation - Part 3: Shielding and grounding (cont.), and filtering harmonics. EDN Network, UBM Tech. Retrieved March 24, 2014.
  3. 1 2 3 4 Whitlock, Bill (2005). "Understanding, finding, and eliminating ground loops in audio and video systems" (PDF). Seminar Template. Jensen Transformers, Inc. Archived from the original (PDF) on August 24, 2009. Retrieved March 24, 2014.
  4. 1 2 3 4 5 6 7 Robinson, Larry (2012). "About Ground Loops". MidiMagic. Larry Robinson personal website. Retrieved March 24, 2014.
  5. Ballou, Glen (2008). Handbook for Sound Engineers (4 ed.). Taylor and Francis. pp. 1194–1196. ISBN   978-1136122538.
  6. Vijayaraghavan, G.; Mark Brown; Malcolm Barnes (December 30, 2008). "8.8.3 Magnetic or inductive coupling". Electrical noise and mitigation - Part 3: Shielding and grounding (cont.), and filtering harmonics. EDN Network, UBM Tech. Retrieved March 24, 2014.
  7. 1 2 3 This type is often called "common impedance coupling", Ballou 2008 Handbook for Sound Engineers, 4th Ed., p. 1198-1200

PD-icon.svg This article incorporates public domain material from Federal Standard 1037C. General Services Administration. Archived from the original on 2022-01-22.