Bus SCS

Last updated

SCS is an acronym for "Sistema Cablaggio Semplificato" ("Simplified Cable Solution"). It uses a fieldbus network protocol and has applications in the field of home automation and building automation. It is used mainly in bTicino and Legrand installations.

Contents

General features

An SCS bus is based on a sheathed twisted pair formed of two flexible conductors; these are braided and unshielded with isolation 300/500V, SELV as double isolation is required – according to the rules adopted by CEI (International Electrotechnical Committee). The bus is unpolarized, devices are required to support the DC power supply in both polarity.

Wiring

Two kind of wiring are possible:

Communication

Across the SCS bus four different types of signals are transmitted in frequency modulation:

The transmission protocol is the CSMA/CA.

Functions

Through the SCS bus you have the following functions:

All the listed functions share the same technology and the same procedures for configuration / installation.

Configuration

All devices connected to SCS bus must be manually configured, no autolearn is possible, apart Alarm system and extenders. Configuration assign an address and an operating mode. Two kind of configurations are possible:

Addressing details

Device addressing use three different 'digits' A|PL|GR. The A mean the room, the PL is the Point of Load in the room, and GR is the group. Group join loads in same or different rooms in a logical manner. Not all devices has group addressing. All devices must answer to room broadcast called AMB. All devices must answer to general broadcast called GEN. Physical and Virtual addressing has different limitations:

digits Physical Virtual note
A 0-9 0-10 11 rooms max in a single SCS domain
PL 1-9 0-15 A=0,PL=0 is forbidden, so 175 loads are addressable in a single SCS domain
GR 1-9 0-255 group

Writing physical addresses use 2 digits. Writing virtual addresses use 4 digits. In big houses and buildings, SCS address extension is possible, were different address domains are connected via some bridges. Only some kind of messages can cross a bridge. Here the values of physical configuration jumpers:

marking color value code description
<empty> --- infinite --- default to virtual
0 green 4659 kOhm 3501/0 digit
1 green 817 kOhm 3501/1 digit
2 green 673 kOhm 3501/2 digit
3 green 556 kOhm 3501/3 digit
4 green 471 kOhm 3501/4 digit
5 green 389 kOhm 3501/5 digit
6 green 329 kOhm 3501/6 digit
7 green 271 kOhm 3501/7 digit
8 green 218 kOhm 3501/8 digit
9 green 179 kOhm 3501/9 digit
GEN blue 100 kOhm 3501/GEN general broadcast
GR blue 68 kOhm 3501/GR group broadcast
AMB blue 33 kOhm 3501/AMB room broadcast
AUX blue 2.2 kOhm 3501/AUX auxiliary channel
ON blue 120 kOhm 3501/ON send ON command
OFF blue 150 kOhm 3501/OFF send OFF command
0/1 blue 180 kOhm 3501/01 send toggle command
PUL blue 2.2 kOhm 3501/PUL button command monostable
SLA blue 120 kOhm 3501/SLA slave of another control
CEN blue 33 kOhm 3501/CEN advanced scenarios mode
↑↓ blue 100 kOhm 3501/T up/down for shutters
↑↓M blue 68 kOhm 3501/TM up/down for shutters monostable

Note: It looks like the values of the configurators are measured, not from any official table. Resistor values are not between short difference. E.g. "4", it is in this table 471 kohm; if resistor is 1%, it is about 470 k ... 479 k. The original table from year 1999/2000 says: 0 = 4,7M, 1 = 825k, 2 = 681k, 3 = 562k, 4 = 475k, 5 = 392k, 6 = 332k, 7 = 274 k, 8 = 221k and 9 = 182k. All these values are found in the standard "E"-resistor value table (EIA E96) but not uniformly spaced (is that correct?). Resistor values in this list are official. However the table values above are useful because all the values fall inside the 1% resistor tolerance area specified by E96 (except value 3501/9 measured at 179k - a second example tested also gave a reading of 179k).

Certifications

Devices connected to the SCS bus are IMQ-certified and comply with these product standards (International Electrotechnical Commission (IEC) EN 50428 - IEC EN 60669-1/A1 - IEC EN 60669-2-1 - IEC EN 50090-2-2 - IEC EN 50090-2-3 ).

Integration

You can interact with the SCS bus through a gateway and an open high-level protocol called OpenWebNet. Two kind of gateway exist:

These gateways are bidirectional; they translate SCS frames into OpenWebNet frames, and the other way round. The open protocol OpenWebNet shared by MyOpen community, let everybody to build software that interact with SCS devices. SCS protocol is a proprietary bTicino protocol. Interaction with other field bus must happen only writing software that use OpenWebNet.

See also

Related Research Articles

<span class="mw-page-title-main">Electronic color code</span> Color code to indicate values of electronic components

An electronic color code or electronic colour code is used to indicate the values or ratings of electronic components, usually for resistors, but also for capacitors, inductors, diodes and others. A separate code, the 25-pair color code, is used to identify wires in some telecommunications cables. Different codes are used for wire leads on devices such as transformers or in building wiring.

<span class="mw-page-title-main">IEEE-488</span> General Purpose Interface Bus (GPIB) specification

IEEE 488 is a short-range digital communications 8-bit parallel multi-master interface bus specification developed by Hewlett-Packard as HP-IB. It subsequently became the subject of several standards, and is generically known as GPIB.

<span class="mw-page-title-main">KNX</span> Standard in building automation

KNX is an open standard for commercial and residential building automation. KNX devices can manage lighting, blinds and shutters, HVAC, security systems, energy management, audio video, white goods, displays, remote control, etc. KNX evolved from three earlier standards; the European Home Systems Protocol (EHS), BatiBUS, and the European Installation Bus.

A Controller Area Network is a vehicle bus standard designed to allow microcontrollers and devices to communicate with each other's applications without a host computer. It is a message-based protocol, designed originally for multiplex electrical wiring within automobiles to save on copper, but it can also be used in many other contexts. For each device, the data in a frame is transmitted serially but in such a way that if more than one device transmits at the same time, the highest priority device can continue while the others back off. Frames are received by all devices, including by the transmitting device.

<span class="mw-page-title-main">Profibus</span> Communications protocol

Profibus is a standard for fieldbus communication in automation technology and was first promoted in 1989 by BMBF and then used by Siemens. It should not be confused with the Profinet standard for Industrial Ethernet. Profibus is openly published as type 3 of IEC 61158/61784-1.

Modbus is a data communications protocol originally published by Modicon in 1979 for use with its programmable logic controllers (PLCs). Modbus has become a de facto standard communication protocol and is now a commonly available means of connecting industrial electronic devices.

EN 50090 is a European standard for Home and Building Electronic Systems (HBES) open communications, issued by CENELEC. It covers any combination of electronic devices linked via a digital transmission network to provide automated, decentralised and distributed process control for domestic and commercial and building applications; for example the control of lighting, heating, food preparation, washing, energy management, water, fire alarms, blinds, security, etc.

A fieldbus is a member of a family of industrial digital communication networks used for real-time distributed control. Fieldbus profiles are standardized by the International Electrotechnical Commission (IEC) as IEC 61784/61158.

IEC 61850 is an international standard defining communication protocols for intelligent electronic devices at electrical substations. It is a part of the International Electrotechnical Commission's (IEC) Technical Committee 57 reference architecture for electric power systems. The abstract data models defined in IEC 61850 can be mapped to a number of protocols. Current mappings in the standard are to Manufacturing Message Specification (MMS), GOOSE [see section 3, Terms and definitions, term 3.65 on page 14], SV or SMV, and soon to web services. In the previous version of the standard, GOOSE stood for "Generic Object Oriented Substation Event", but this old definition is still very common in IEC 61850 documentation. These protocols can run over TCP/IP networks or substation LANs using high speed switched Ethernet to obtain the necessary response times below four milliseconds for protective relaying.

Foundation Fieldbus is an all-digital, serial, two-way communications system that serves as the base-level network in a plant or factory automation environment. It is an open architecture, developed and administered by FieldComm Group.

Actuator Sensor Interface is an industrial networking solution used in PLC, DCS and PC-based automation systems. It is designed for connecting simple field I/O devices in discrete manufacturing and process applications using a single two-conductor cable.

EtherCAT is an Ethernet-based fieldbus system developed by Beckhoff Automation. The protocol is standardized in IEC 61158 and is suitable for both hard and soft real-time computing requirements in automation technology.

Digital Addressable Lighting Interface (DALI) is a trademark for network-based products that control lighting. The underlying technology was established by a consortium of lighting equipment manufacturers as a successor for 1-10 V/0–10 V lighting control systems, and as an open standard alternative to several proprietary protocols. The DALI, DALI-2 and D4i trademarks are owned by the lighting industry alliance, DiiA.

NMEA 2000, abbreviated to NMEA2k or N2K and standardized as IEC 61162-3, is a plug-and-play communications standard used for connecting marine sensors and display units within ships and boats. Communication runs at 250 kilobits-per-second and allows any sensor to talk to any display unit or other device compatible with NMEA 2000 protocols.

A protocol converter is a device used to convert standard or proprietary protocol of one device to the protocol suitable for the other device or tools to achieve the desired interoperability. Protocols are software installed on the routers, which convert the data formats, data rate and protocols of one network into the protocols of the network in which data is navigating. There are varieties of protocols used in different fields like power generation, transmission and distribution, oil and gas, automation, utilities, and remote monitoring applications. The major protocol translation messages involve conversion of data messages, events, commands, and time synchronization.

IEC 60870 part 6 in electrical engineering and power system automation, is one of the IEC 60870 set of standards which define systems used for telecontrol in electrical engineering and power system automation applications. The IEC Technical Committee 57 have developed part 6 to provide a communication profile for sending basic telecontrol messages between two systems which is compatible with ISO standards and ITU-T recommendations.

Sercos III is the third generation of the Sercos interface, a standardized open digital interface for the communication between industrial controls, motion devices, input/output devices (I/O), and Ethernet nodes, such as PCs. Sercos III applies the hard real-time features of the Sercos interface to Ethernet. It is based upon and conforms to the Ethernet standard. Work began on Sercos III in 2003, with vendors releasing first products supporting it in 2005.

OpenWebNet is a communications protocol developed by Bticino since 2000.

WirelessHART within telecommunications and computing, is a wireless sensor networking technology. It is based on the Highway Addressable Remote Transducer Protocol (HART). Developed as a multi-vendor, interoperable wireless standard, WirelessHART was defined for the requirements of process field device networks.

<span class="mw-page-title-main">E series of preferred numbers</span> Series of preferred values for passive electrical components

The E series is a system of preferred numbers derived for use in electronic components. It consists of the E3, E6, E12, E24, E48, E96 and E192 series, where the number after the 'E' designates the quantity of logarithmic value "steps" per decade. Although it is theoretically possible to produce components of any value, in practice the need for inventory simplification has led the industry to settle on the E series for resistors, capacitors, inductors, and zener diodes. Other types of electrical components are either specified by the Renard series or are defined in relevant product standards.