Parallel Redundancy Protocol (PRP) is a network protocol standard for Ethernet that provides seamless failover against failure of any network component. This redundancy is invisible to the application.
PRP nodes have two ports and are attached to two separated networks of similar topology. PRP can be implemented entirely in software, i.e. integrated in the network driver. Nodes with single attachment can be attached to one network only. This is in contrast to the companion standard HSR (IEC 62439-3 Clause 5), with which PRP shares the operating principle.
PRP and HSR are independent of the application-protocol and can be used by most Industrial Ethernet protocols in the IEC 61784 suite. PRP and HSR are standardized by the IEC 62439-3:2016 [1] ). They have been adopted for substation automation in the framework of IEC 61850.
PRP and HSR are suited for applications that request high availability and short switchover time, [2] such as: protection for electrical substation, [3] synchronized drives, for instance in printing machines or high power inverters. For such applications, the recovery time of commonly used protocols such as the Rapid Spanning Tree Protocol (RSTP) is too long. [4]
The cost of PRP is a duplication of all network elements that require it. Cost impact is low since it makes little difference if the spares lie on the shelf or are actually working in the plant. The maintenance interval is shortened since more components can fail in use, but such outage will remain invisible to the application.
PRP does not cover end node failures, but redundant nodes may be connected via a PRP network.
Each PRP network node (DANP) has two Ethernet ports attached to two separate local area networks of arbitrary, but similar topology. The two LANs have no links connecting them and are assumed to be fail-independent, to avoid common mode failures.
Nodes with single attachment (such as a printer) are either attached to one network only (and therefore can communicate only with other nodes attached to the same network), or are attached through a RedBox, a device that behaves like a doubly attached node. [5]
Since HSR and PRP use the same duplicate identification mechanism, PRP and HSR networks can be connected without single point of failure and the same nodes can be built to be used in both PRP and HSR networks.
A source node (DANP) sends simultaneously two copies of a frame, one over each port. The two frames travel through their respective LANs until they reach a destination node (DANP) with a certain time skew. The destination node accepts the first frame of a pair and discards the second (if it arrives). Therefore, as long as one LAN is operational, the destination application always receives one frame. PRP provides zero-time recovery and allows to check the redundancy continuously to detect lurking failures.
To simplify the detection of duplicates, the frames are identified by their source address and a sequence number that is incremented for each frame sent according to the PRP protocol. The sequence number, the frame size, the path identifier and an Ethertype are appended just before the Ethernet checksum in a 6-octet PRP trailer. This trailer is ignored (considered as padding) by all nodes that are unaware of the PRP protocol, and therefore these singly attached nodes (SAN) can operate in the same network.
NOTE: all legacy devices should accept Ethernet frames up to 1528 octets, this is below the theoretical limit of 1535 octets.
The two Ethernet interfaces of a node use the same MAC address. This is allowed since the two LANs have no connection. Therefore, PRP is a layer 2 redundancy, which allows higher layer network protocols to operate without modification. A PRP node needs only one IP address. Especially, the ARP protocol will correctly relate the MAC to the IP address.
IEC 62439-3 Annex C specifies the Precision Time Protocol Industry Profile that support a clock synchronization over PRP with an accuracy of 1 μs after 15 network elements, as profile of IEEE Std 1588 Precision Time Protocol.
Clocks can be doubly attached according to PRP, but since the correction is different according to the path, the duplicate discard method of PRP is not applicable. Also, delay measurement messages (Pdelay_Req & Pdelay_Resp) are not duplicated since they are link-local.
About every second, a master clock sends two copies of a Sync message, but not at exactly the same time since the ports are separate, therefore the original Syncs have already different time stamps.
A slave receives the two Sync messages at different times and applies the Best Master Clock Algorithm (BMCA), and when the two Sync come from the same grandmaster, the clock quality is used as a tie-breaker. A slave will normally listen to one port and supervise the other, rather than switching back and forth or using both Syncs.
This method works for several options in 1588, with Layer 2 / Layer 3 operation, and with peer-to-peer / end-to-end delay measurement. IEC 62439-3 defines these two profiles as:
The original standard IEC 62439:2010 incremented the sequence number of the Redundancy Control Trailer (RCT) in the PRP frames on a per-connection basis. This gave a good error detection coverage but made difficult the transition from PRP to the High-availability Seamless Redundancy (HSR) protocol, which uses a ring topology instead of parallel networks.
The revised standard IEC 62439-3:2012 aligned PRP with HSR using the same duplicate discard algorithm. This allowed building transparent PRP-HSR connection bridges and nodes that can operate both as PRP (DANP) and HSR (DANH).
The old IEC 62439:2010 standard is sometimes referred to as PRP-0 as it is still used in some control systems, and PRP 2012 as "PRP". [7]
An interesting application of PRP was found in the area of wireless communication as "Timing Combiner" [ [8] ], yielding significant improvement in packet loss and timing behaviour over parallel redundant wireless links.
Ethernet is a family of wired computer networking technologies commonly used in local area networks (LAN), metropolitan area networks (MAN) and wide area networks (WAN). It was commercially introduced in 1980 and first standardized in 1983 as IEEE 802.3. Ethernet has since been refined to support higher bit rates, a greater number of nodes, and longer link distances, but retains much backward compatibility. Over time, Ethernet has largely replaced competing wired LAN technologies such as Token Ring, FDDI and ARCNET.
A virtual local area network (VLAN) is any broadcast domain that is partitioned and isolated in a computer network at the data link layer. In this context, virtual, refers to a physical object recreated and altered by additional logic, within the local area network. VLANs work by applying tags to network frames and handling these tags in networking systems – creating the appearance and functionality of network traffic that is physically on a single network but acts as if it is split between separate networks. In this way, VLANs can keep network applications separate despite being connected to the same physical network, and without requiring multiple sets of cabling and networking devices to be deployed.
The data link layer, or layer 2, is the second layer of the seven-layer OSI model of computer networking. This layer is the protocol layer that transfers data between nodes on a network segment across the physical layer. The data link layer provides the functional and procedural means to transfer data between network entities and may also provide the means to detect and possibly correct errors that can occur in the physical layer.
Fieldbus is the name of a family of industrial computer networks used for real-time distributed control. Fieldbus profiles are standardized by the International Electrotechnical Commission (IEC) as IEC 61784/61158.
IEC 61850 is an international standard defining communication protocols for intelligent electronic devices at electrical substations. It is a part of the International Electrotechnical Commission's (IEC) Technical Committee 57 reference architecture for electric power systems. The abstract data models defined in IEC 61850 can be mapped to a number of protocols. Current mappings in the standard are to MMS, GOOSE [see section 3, Terms and definitions, term 3.65 on page 14], SV or SMV, and soon to Web Services. In the previous version of the standard, GOOSE stood for "Generic Object Oriented Substation Event", but this old definition is still very common in IEC 61850 documentation. These protocols can run over TCP/IP networks or substation LANs using high speed switched Ethernet to obtain the necessary response times below four milliseconds for protective relaying.
The Precision Time Protocol (PTP) is a protocol used to synchronize clocks throughout a computer network. On a local area network, it achieves clock accuracy in the sub-microsecond range, making it suitable for measurement and control systems. PTP is currently employed to synchronize financial transactions, mobile phone tower transmissions, sub-sea acoustic arrays, and networks that require precise timing but lack access to satellite navigation signals.
Profinet is an industry technical standard for data communication over Industrial Ethernet, designed for collecting data from, and controlling equipment in industrial systems, with a particular strength in delivering data under tight time constraints. The standard is maintained and supported by Profibus and Profinet International, an umbrella organization headquartered in Karlsruhe, Germany.
EtherCAT is an Ethernet-based fieldbus system invented by Beckhoff Automation. The protocol is standardized in IEC 61158 and is suitable for both hard and soft real-time computing requirements in automation technology.
Sercos III is the third generation of the Sercos interface, a standardized open digital interface for the communication between industrial controls, motion devices, input/output devices (I/O), and Ethernet nodes, such as PCs. Sercos III applies the hard real-time features of the Sercos interface to Ethernet. It is based upon and conforms to the Ethernet standard. Work began on Sercos III in 2003, with vendors releasing first products supporting it in 2005.
Data center bridging (DCB) is a set of enhancements to the Ethernet local area network communication protocol for use in data center environments, in particular for use with clustering and storage area networks.
Synchronous Ethernet, also referred as SyncE, is an ITU-T standard for computer networking that facilitates the transference of clock signals over the Ethernet physical layer. This signal can then be made traceable to an external clock.
Shortest Path Bridging (SPB), specified in the IEEE 802.1aq standard, is a computer networking technology intended to simplify the creation and configuration of networks, while enabling multipath routing.
High-availability Seamless Redundancy (HSR) is a network protocol for Ethernet that provides seamless failover against failure of any single network component. PRP and HSR are independent of the application-protocol and can be used by most Industrial Ethernet protocols in the IEC 61784 suite. HSR does not cover the failure of end nodes, but redundant nodes can be connected via HSR.
RAPIEnet is Korea's first Ethernet international standard for real-time data transmission.
Media Redundancy Protocol (MRP) is a data network protocol standardized by the International Electrotechnical Commission as IEC 62439-2. It allows rings of Ethernet switches to overcome any single failure with recovery time much faster than achievable with Spanning Tree Protocol. It is suitable to most industrial Ethernet applications.
Time-Sensitive Networking (TSN) is a set of standards under development by the Time-Sensitive Networking task group of the IEEE 802.1 working group. The TSN task group was formed in November 2012 by renaming the existing Audio Video Bridging Task Group and continuing its work. The name changed as a result of the extension of the working area of the standardization group. The standards define mechanisms for the time-sensitive transmission of data over deterministic Ethernet networks.
IEC/IEEE 61850-9-3 or PUP is an international standard for precise time distribution and clock synchronization in electrical grids with an accuracy of 1 μs.
It supports precise time stamping of voltage and current measurement for differential protection, wide area monitoring and protection, busbar protection and event recording.
It can be used to ensure deterministic operation of critical functions in the automation system.
It belongs to the IEC 61850 standard suite for communication networks and systems for power utility automation.
Industrial automation systems consisting of several distributed controllers need a precise synchronization for commands, events and process data. For instance, motors for newspaper printing are synchronized within some 5 microseconds to ensure that the color pixels in the different cylinders come within 0.1 mm at a paper speed of some 20 m/s. Similar requirements exist in high-power semiconductors and in drive-by-wire vehicles. This synchronisation is provided by the communication network, in most cases Industrial Ethernet. Many ad-hoc synchronization schemes exist, so IEEE published a standard Precision Time Protocol IEEE 1588 or "PTP", which allows sub-microsecond synchronization of clocks. PTP is formulated generally, so concrete applications need a stricter profile. In particular, PTP does not specify how the clocks should operate when the network is duplicated for better resilience to failures.
Deterministic Networking (DetNet) is an effort by the IETF DetNet Working Group to study implementation of deterministic data paths for real-time applications with extremely low data loss rates, packet delay variation (jitter), and bounded latency, such as audio and video streaming, industrial automation, and vehicle control.
Audio Video Bridging (AVB) is a common name for the set of technical standards which provide improved synchronization, low-latency, and reliability for switched Ethernet networks. AVB embodies the following technologies and standards: