Premium efficiency, when used in reference to specific types of Electric Motors (with a rotating shaft), is a class of motor efficiency.
As part of a concerted effort worldwide to reduce energy consumption, CO2 emissions and the impact of industrial operations on the environment, various regulatory authorities in many countries have introduced, or are planning, legislation to encourage the manufacture and use of higher efficiency electrically powered motors. This article looks at the development of the premium efficiency standard (IE3) and premium efficiency motors (PEMs) and associated environmental, legal and energy-related topics.
The oil crisis and the worldwide need for more power, more electrical power, and consequently more power stations have raised energy conservation awareness.
In 1992 the U.S. Congress, as part of the Energy Policy Act (EPAct) set minimum efficiency levels (see Table B-1)[ vague ] for electric motors. [1]
In 1998 the European Committee of Manufacturers of Electrical Machines and Power systems (CEMEP) issued a voluntary agreement of motor manufacturers on efficiency classification, with three efficiency classes: [2]
The term premium efficiency as discussed here relates to a class of motor efficiency. It is thought necessary to introduce this term associated with motors because of forthcoming legislation in the EU, USA and other countries regarding the future mandatory use of premium-efficiency squirrel cage induction type motors in defined equipment.
Several statements have been made regarding motor use and the advantages of using premium-efficiency or higher efficiency motors. These include:
Based on U.S. Department of Energy data, it is estimated that the National Electrical Manufacturers Association (NEMA) premium-efficiency motor program would save 5.8 terawatts of electricity and prevent the release of nearly 80 million metric tons of carbon into the atmosphere over the next ten years. This is equivalent to keeping 16 million cars off the road. [3]
Roughly 30 million new electric motors are sold each year for industrial purposes. Some 300 million motors are in use in industry, infrastructure and large buildings. These electric motors are responsible for 40% of global electricity used to drive pumps, fans, compressors and other mechanical traction equipment. Motor technology has evolved over the last few decades. Superior so-called "premium" products are now available, ready to change the market toward energy efficiency and to contribute in lowering greenhouse gas emissions worldwide. [4]
With using best practice energy efficiency of electrical motors can be improved by 20% to 30% on average. Most improvements have a pay back time of 1 to 3 years. This in addition means a big potential impact on reduction of global greenhouse gas emissions. [5]
Electric motor systems consume large amounts of electrical energy and can provide an opportunity for significant energy savings. Energy represents more than 97 percent of total motor operating costs over the motor's lifetime. However, the purchase of a new motor often tends to be driven by the price, not the electricity it will consume. Even a small improvement in efficiency could result in significant energy and cost savings. Investing a little more money upfront for a more efficient motor is often paid back in energy savings. Improving energy efficiency reduces greenhouse gas emissions that contribute to climate change. [6]
The efficiency of an electric motor is represented by the Greek letter Eta and defined as the ratio of output mechanical power to electric input power and can be calculated using this formula:
Since the efficiency is a ratio, as long as the unit of measure is the same for both the output and input power, any unit of measure can be used for this calculation.
The shaft power is transferred to the machine driven; the electric input power is what is metered and charged for. Loss in motor efficiency is determined by the difference between the input power and output or shaft power.
Ploss = Pin - Pshaft
Ploss = losses of electric motor [kW]
Motor energy loss is mainly heat caused by many factors, including loss from the coil winding (resistance), loss in the rotor bars and slip rings, loss due to magnetising of the iron core, and loss from friction of bearings.
On December 19, 2007, President Bush signed the Energy Independence and Security Act of 2007 (EISA) into law (Public Law 140-110). The National Electrical Manufacturers Association (NEMA) actively participated in crafting major provisions on EISA. A critical provision that NEMA focused on was increased motor efficiency levels. The Motor Generator section of NEMA joined forces with the American Council for an Energy Efficient Economy to draft and recommend new motor efficiency regulations covering both general purpose and some categories of definite and special purpose electrical motors.
The Motor and Generator Section of NEMA established the NEMA Premium program for four main reasons:
Visit NEMA Premium Motors for more information. [7]
A summary of EISA standards for motors: [8]
In June, 2005, the European Union enacted a Directive on establishing a framework for setting Eco-design requirements (such as energy efficiency requirements) for all energy using products in the residential, tertiary and industrial sectors. [9] Coherent EU-wide rules for eco-design will ensure that disparities among national regulations do not become obstacles to intra-EU trade. The directive does not introduce directly binding requirements for specific products, but does define conditions and criteria for setting requirements regarding environmentally relevant product characteristics (such as energy consumption) and allows them to be improved quickly and efficiently. It will be followed by implementing measures which will establish the eco-design requirements. In principle, the Directive applies to all energy using products (except transport vehicles) and covers all energy sources. [10]
IEC 60034-30 specifies electrical efficiency classes for single-speed, three-phase, 50 Hz and 60 Hz, cage-induction motors that:
The table below shows the IEC 60034-30 (2008) efficiency classes and comparable efficiency levels.
Efficiency Levels | Comparison | |
---|---|---|
IE1 | Standard efficiency | |
IE2 | High efficiency | For 50 Hz considerably higher than EFF2 of CEMEP and identical to the U.S. EPAct for 60 Hz |
IE3 | Premium efficiency | New efficiency class in Europe for 50 Hz, higher than EFF1 on CEMEP and with some exceptions identical to NEMA Premium in the United States for 60 Hz. |
The standard also reserves an IE4 class (Super Premium Efficiency) for the future. The following motors are excluded from the new efficiency standard:
Graph is showing as example 50 Hz, 4-pole motors
For 60 Hz operation, the IE2 and IE3 minimum full-load efficiency values are virtually identical to the North American National Electrical Manufacturers Association (NEMA) [11] Energy Efficient and Premium Efficiency motor standards, respectively. (NEMA does specify different full-load efficiency values for motors with Totally Enclosed Fan-Cooled and Open Drip-proof enclosures and from 200HP IEC IE3 efficiency is slightly higher than NEMA Premium Efficiency). The IEC minimum full-load efficiency standards are higher for 60 Hz motors than for 50 Hz motors. This is because as long as the motor torque is constant, I2R or winding resistance losses are the same at 50 Hz and 60 Hz. The motor output power, however, increases linearly with speed, increasing by 20% when the frequency is increased from 50 Hz to 60 Hz. In general, the 60 Hz efficiency is about 2.5% to 0.5% greater than the 50 Hz values. The efficiency gain is greater for smaller motor power ratings.
To show compliance with these new efficiency standards, motors must be tested in accordance with the newly adopted IEC 60034-2–1 testing protocol. This procedure provides test results that are largely compatible with those obtained by the North American IEEE 112B and CSA 390 test methods. The new standard also requires that the motor efficiency class and nominal motor efficiency be labeled on the motor nameplate and given in product literature and motor catalogues in the following format:
IE3 94.5%
On 22 July 2009, Commission Regulation (EC) No. 640/2009 implementing Directive 2005/32/EC states that in the EU, with the exception of some special applications, motors shall not be less efficient than the IE3 efficiency level as from 1 January 2015.
In detail:
EC 60034–30, IE3 Premium Efficiency (%) is presented in the table.
IE3 Premium Efficiency
kW | 2-pole | 4-pole | 6-pole | |||
---|---|---|---|---|---|---|
50 Hz | 60 Hz | 50 Hz | 60 Hz | 50 Hz | 60 Hz | |
0.75 | 80.7 | 77.0 | 82.5 | 85.5 | 78.9 | 82.5 |
1.1 | 82.7 | 84.0 | 84.1 | 86.5 | 81.0 | 87.5 |
1.5 | 84.2 | 85.5 | 85.3 | 86.5 | 82.5 | 88.5 |
2.2 | 85.9 | 86.5 | 86.7 | 89.5 | 84.3 | 89.5 |
3 | 87.1 | – | 87.7 | – | 85.6 | – |
3.7 | – | 88.5 | – | 89.5 | – | 89.5 |
4 | 88.1 | – | 88.6 | – | 86.8 | – |
5.5 | 89.2 | 89.5 | 89.6 | 91.7 | 88.0 | 91.0 |
7.5 | 90.1 | 90.2 | 90.4 | 91.7 | 89.1 | 91.0 |
11 | 91.2 | 90.0 | 91.4 | 92.4 | 90.3 | 91.7 |
15 | 91.9 | 91.0 | 92.1 | 93.0 | 91.2 | 91.7 |
18.5 | 92.4 | 91.7 | 92.6 | 93.6 | 91.7 | 93.0 |
22 | 92.7 | 91.7 | 93.0 | 93.6 | 92.2 | 93.0 |
30 | 93.3 | 92.4 | 93.6 | 94.1 | 92.9 | 94.1 |
37 | 93.7 | 93.0 | 93.9 | 94.5 | 93.3 | 94.1 |
45 | 94.0 | 93.6 | 94.2 | 95.0 | 93.7 | 94.5 |
55 | 94.3 | 93.6 | 94.6 | 94.4 | 94.1 | 94.5 |
75 | 94.7 | 94.1 | 95.0 | 95.4 | 94.6 | 95.0 |
90 | 95.0 | 95.0 | 95.2 | 95.4 | 94.9 | 95.0 |
110 | 95.2 | 95.0 | 95.4 | 95.8 | 95.1 | 95.8 |
132 | 95.4 | – | 95.6 | – | 95.4 | – |
150 | – | 95.4 | – | 96.2 | – | 95.8 |
160 | 95.6 | – | 95.8 | – | 95.6 | – |
185 | – | 95.8 | – | 96.2 | – | 95.8 |
200 | 95.8 | – | 96.0 | – | 95.8 | – |
220 | 95.8 | 95.8 | 96.0 | 96.2 | 95.8 | 95.8 |
250 | 95.8 | 95.8 | 96.0 | 96.2 | 95.8 | 95.8 |
300 | 95.8 | 95.8 | 96.0 | 96.2 | 95.8 | 95.8 |
330 | 95.8 | 95.8 | 96.0 | 96.2 | 95.8 | 95.8 |
375 | 95.8 | 95.8 | 96.0 | 96.2 | 95.8 | 95.8 |
Design of Premium Efficiency Motors needs special knowledge, experience and test facilities, equipped with precision instrumentation. The task of design is, to get the efficiency up by minimizing and balancing the single losses, especially those created in the stator coils, the stator iron (magnetizing) and the losses within the rotor by slip. In comparison to standard (e.g. IE1) electrical motors, more iron and copper material are used. IE3 motors are heavier and physically bigger than IE1 motors.
Typically use of higher slot fill in the copper winding, use of thinner laminations of improved steel properties, reducing the air gap, better design of cooling fan, use of special and improved bearings etc. can ensure higher efficiency in the motors.
The high electrical conductivity of copper versus other metallic conductors enhances the electrical energy efficiency of motors. [12] Increasing the mass and cross section of conductors in a coil increases the electrical energy efficiency of the motor. Where energy savings are prime design objectives, [13] [14] induction motors can be designed to meet and exceed National Electrical Manufacturers Association (NEMA) premium efficiency standards. [13] [14] [7]
The U.S. Senate Energy and Natural Resources Committee adopted a NEMA-advocated provision that created a premium energy-efficient motor rebate program, also known as a "crush for credit" program, according to the National Electrical Manufacturers Association (NEMA). The program provided a $25 per horsepower rebate and a $5 per horsepower rebate for the disposal of the old motor. The latter program was needed to offset the cost difference between new, more expensive, efficient motors and the lesser cost to repair the older, more inefficient motors, NEMA says. This program allowed the federal government to spend $350 million in incentives for the widespread adoption of NEMA Premium motors.
The "Crush for Credit" provision contained in the Senate's version of the "Energy Policy and Conservation Act" (EPCA) ran for five years, and included the following proposed funding: [15]
Within the EU, various Capital Allowance Schemes encourage companies to purchase equipment incorporating premium-efficiency motors. For example, in the UK, the Enhanced Capital Allowances Scheme [16] provides a tax incentive to businesses that invest in equipment that meets published energy-saving criteria. The Energy Technology List (ETL) details the criteria for each type of technology, and lists those products in each category that meet them. It is managed by the Carbon Trust, on behalf of the Government, and has two parts:
The ETPL also contains details of the maximum claim values [18] for qualifying products which comprise a component in a larger piece of plant and machinery, which does not itself qualify for ECAs.
Key Features of the ECA scheme are
A similar scheme in Ireland, Accelerated Capital Allowance (ACA) run by Sustainable Energy Ireland (SEI) [20] lets a company cut its taxable income by 100% of the capital cost of eligible energy-efficient equipment in the first year of purchase. This compares to just 12.5% for ineligible plant and machinery.
With the existing Capital Allowances tax structure, when money is spent on "capital equipment" companies can deduct the cost of this equipment from their profits proportionally over a period of 8 years, i.e. the annual taxable profit is only reduced by 1/8 of the total equipment cost.
With new ACA, when money is spent on "Eligible energy efficient capital equipment", the company can deduct the full cost of this equipment from their profits in the year of purchase, i.e. the taxable profit in year one is reduced by the full cost of the equipment.
An uninterruptible power supply (UPS) or uninterruptible power source is a type of continual power system that provides automated backup electric power to a load when the input power source or mains power fails. A UPS differs from a traditional auxiliary/emergency power system or standby generator in that it will provide near-instantaneous protection from input power interruptions by switching to energy stored in battery packs, supercapacitors or flywheels. The on-battery run-times of most UPSs are relatively short but sufficient to "buy time" for initiating a standby power source or properly shutting down the protected equipment. Almost all UPSs also contain integrated surge protection to shield the output appliances from voltage spikes.
Mains electricity or utility power, power grid, domestic power, and wall power, or, in some parts of Canada, hydro, is a general-purpose alternating-current (AC) electric power supply. It is the form of electrical power that is delivered to homes and businesses through the electrical grid in many parts of the world. People use this electricity to power everyday items by plugging them into a wall outlet.
A power supply is an electrical device that supplies electric power to an electrical load. The main purpose of a power supply is to convert electric current from a source to the correct voltage, current, and frequency to power the load. As a result, power supplies are sometimes referred to as electric power converters. Some power supplies are separate standalone pieces of equipment, while others are built into the load appliances that they power. Examples of the latter include power supplies found in desktop computers and consumer electronics devices. Other functions that power supplies may perform include limiting the current drawn by the load to safe levels, shutting off the current in the event of an electrical fault, power conditioning to prevent electronic noise or voltage surges on the input from reaching the load, power-factor correction, and storing energy so it can continue to power the load in the event of a temporary interruption in the source power.
A switched-mode power supply (SMPS), also called switching-mode power supply, switch-mode power supply, switched power supply, or simply switcher, is an electronic power supply that incorporates a switching regulator to convert electrical power efficiently.
An induction motor or asynchronous motor is an AC electric motor in which the electric current in the rotor that produces torque is obtained by electromagnetic induction from the magnetic field of the stator winding. An induction motor therefore needs no electrical connections to the rotor. An induction motor's rotor can be either wound type or squirrel-cage type.
IEC 60320 Appliance couplers for household and similar general purposes is a set of standards from the International Electrotechnical Commission (IEC) specifying non-locking connectors for connecting power supply cords to electrical appliances of voltage not exceeding 250 V (a.c.) and rated current not exceeding 16 A. Different types of connector are specified for different combinations of current, temperature and earthing requirements. Unlike IEC 60309 connectors, they are not coded for voltage; users must ensure that the voltage rating of the equipment is compatible with the mains supply. The standard uses the term coupler to encompass connectors on power cords and power inlets and outlets built into appliances.
The efficiency of a system in electronics and electrical engineering is defined as useful power output divided by the total electrical power consumed, typically denoted by the Greek small letter eta.
In mechanical engineering, mechanical efficiency is a dimensionless ratio that measures the efficiency of a mechanism or machine in transforming the power input to the device to power output. A machine is a mechanical linkage in which force is applied at one point, and the force does work moving a load at another point. At any instant the power input to a machine is equal to the input force multiplied by the velocity of the input point, similarly the power output is equal to the force exerted on the load multiplied by the velocity of the load. The mechanical efficiency of a machine is a dimensionless number between 0 and 1 that is the ratio between the power output of the machine and the power input
Railway electrification is the use of electric power for the propulsion of rail transport. Electric railways use either electric locomotives, electric multiple units or both. Electricity is typically generated in large and relatively efficient generating stations, transmitted to the railway network and distributed to the trains. Some electric railways have their own dedicated generating stations and transmission lines, but most purchase power from an electric utility. The railway usually provides its own distribution lines, switches, and transformers.
A DC-to-DC converter is an electronic circuit or electromechanical device that converts a source of direct current (DC) from one voltage level to another. It is a type of electric power converter. Power levels range from very low to very high.
In electrical engineering and mechanical engineering, the power rating of equipment is the highest power input allowed to flow through particular equipment. According to the particular discipline, the term power may refer to electrical or mechanical power. A power rating can also involve average and maximum power, which may vary depending on the kind of equipment and its application.
An AC adapter or AC/DC adapter is a type of external power supply, often enclosed in a case similar to an AC plug. AC adapters deliver electric power to devices that lack internal components to draw voltage and power from mains power themselves. The internal circuitry of an external power supply is often very similar to the design that would be used for a built-in or internal supply.
Induction cooking is performed using direct electrical induction heating of cooking vessels, rather than relying on indirect radiation, convection, or thermal conduction. Induction cooking allows high power and very rapid increases in temperature to be achieved: changes in heat settings are instantaneous.
A variable-frequency drive is a type of AC motor drive that controls speed and torque by varying the frequency of the input electricity. Depending on its topology, it controls the associated voltage or current variation.
In the United States, the efficiency of air conditioners is often rated by the seasonal energy efficiency ratio (SEER) which is defined by the Air Conditioning, Heating, and Refrigeration Institute, a trade association, in its 2008 standard AHRI 210/240, Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment. A similar standard is the European seasonal energy efficiency ratio (ESEER).
A rotary phase converter, abbreviated RPC, is an electrical machine that converts power from one polyphase system to another, converting through rotary motion. Typically, single-phase electric power is used to produce three-phase electric power locally to run three-phase loads in premises where only single-phase is available.
A grid-tie inverter converts direct current (DC) into an alternating current (AC) suitable for injecting into an electrical power grid, at the same voltage and frequency of that power grid. Grid-tie inverters are used between local electrical power generators: solar panel, wind turbine, hydro-electric, and the grid.
Voltage optimisation is a term given to the systematic controlled reduction in the voltages received by an energy consumer to reduce energy use, power demand and reactive power demand. While some voltage 'optimisation' devices have a fixed voltage adjustment, others electronically regulate the voltage automatically.
A fractional-horsepower motor (FHP) is an electric motor with a rated output power of less than one horsepower (745.7 W). There is no defined minimum output, however, it is generally accepted that a motor with a frame size of less than 35mm square can be referred to as a 'micro-motor'.
IEC 60034 is an international standard of the International Electrotechnical Commission for rotating electrical machinery.