In electrical engineering utilization categories are defined by IEC standards [1] and indicate the type of electrical load and duty cycle of the loads to ease selection of contactors and relays.
The utilization categories category for low-voltage switchgear defines the characteristic operating conditions for switchgear such as contactors, circuit-breakers, circuit-breaker-fuse units, contactor relays, etc. These devices are dimensioned for different electrical loads and for different operating conditions.
The characteristic of the load to be switched or controlled determines the requirements for the switchgear and its correct selection for the intended application. In particular, the stress on the switching path caused by current and voltage during switching on and off is of enormous importance. For example, the switch-on and switch-off current at resistance load corresponds to the continuous operating current, while, for example, squirrel cage motors consumes multiple of the rated operating current during switch-on and in the acceleration phase.
Contact load in amperes for heaters (AC1) and motors (AC3) can be found directly on the contactor. The "Utilization category" are mainly categorized in IEC 60947 in the following volume:
In addition, IEC/EN 61095 also defines categories for "household and similar applications".
The following table provides an overview of the various abbreviations. Within a utilization category, the suitable size may be selected for the respective type. This depends on the rated current, the rated voltage and the electrical load to be switched.
Utilization category | Typical application [2] [3] | Applicable IEC norm [3] |
---|---|---|
AC-1 | Non-inductive or slightly inductive loads, example: resistive furnaces, heaters | 60947-4-1 |
AC-2 | Slip-ring motors: switching off | 60947-4-1 |
AC-3 | Squirrel-cage motors: starting, switches off motors during running time | 60947-4-1 |
AC-4 | Squirrel-cage motors: starting, plugging, inching | 60947-4-1 |
AC-5a | Switching of discharge lamps | 60947-4-1 |
AC-5b | Switching of incandescent lamps | 60947-4-1 |
AC-6a | Switching of transformers | 60947-4-1 |
AC-6b | Switching of capacitor banks | 60947-4-1 |
AC-7a | Slightly inductive loads in household appliances: examples: mixers, blenders | 60947-4-1 61095 |
AC-7b | Motor-loads for household appliances: examples: fans, central vacuum | 60947-4-1 61095 |
AC-8a | Hermetic refrigerant compressor motor control with manual resetting overloads | 60947-4-1 |
AC-8b | Hermetic refrigerant compressor motor control with automatic resetting overloads | 60947-4-1 |
AC-12 | Control of resistive loads and solid state loads with opto-coupler isolation | 60947-5-2 |
AC-13 | Control of solid state loads with transformer isolation | 60947-5-1 |
AC-14 | Control of small electromagnetic loads | 60947-5-1 |
AC-15 | Control of A.C. electromagnetic loads | 60947-5-1 |
AC-20 | Connecting and disconnecting under no-load conditions | 60947-3 |
AC-21 | Switching of resistive loads, including moderate overloads | 60947-3 |
AC-22 | Switching of mixed resistive and inductive loads, including moderate overloads | 60947-3 |
AC-23 | Switching of motor loads or other highly inductive loads | 60947-3 |
AC-31A AC-31B ³) | Non-inductive or weakly inductive loads | 60947-6-1 |
AC-33A AC33B³) | Motor loads or mixed loads including motors, resistors and up to 30% incandescent lamp load | 60947-6-1 |
AC-35A AC-35B ³) | Gas discharge lamp load | 60947-6-1 |
AC-36A AC36B ³) | Incandescent lamp load | 60947-6-1 |
AC-40 | Distribution circuits of mixed resistive and inductive loads | 60947-6-2 |
AC-41 | Non-inductive or weakly inductive loads, resistance furnaces | 60947-6-2 |
AC-42 | Slip ring motors: Starting, switching off | 60947-6-2 |
AC-43 | Squirrel cage motors: Starting, switching off during operation | 60947-6-2 |
AC-44 | Squirrel cage motors: Starting, counter-current braking ¹) or reversing ¹), typing ²) | 60947-6-2 |
AC-45a | Switching of gas discharge lamps | 60947-6-2 |
AC-45b | Switching incandescent lamps | 60947-6-2 |
AC-51 | Induction-free or slightly inductive loads, resistance furnaces | 60947-4-3 |
AC-52a | Control of the stator winding of a slip-ring motor: 8-hour operation with starting currents for starting processes, maneuvering, operation | 60947-4-2 |
AC-52b | Control of the stator winding of a slip ring motor: Intermittent operation | 60947-4-2 |
AC-53a | Control of a squirrel cage motor: 8-hour operation with starting currents for starting processes, maneuvering, operation | 60947-4-2 |
AC-53b | Control of a squirrel cage motor: Intermittent operation | 60947-4-2 |
AC-55a | Switching of electrical controls of discharge lamps | 60947-4-3 |
AC-55b | Switching incandescent lamps | 60947-4-3 |
AC-56a | Switching transformers | 60947-4-3 |
AC-56b | Switching of capacitor batteries | 60947-4-3 |
AC-58a | Control of a hermetically sealed refrigeration compressor motor with automatic reset of overload releases: 8-hour operation with starting currents for starting, maneuvering, operation | 60947-4-2 |
AC-58b | The control of a hermetically sealed refrigeration compressor motor with automatic reset of the overload trips: Intermittent operation | 60947-4-2 |
AC-140 | Control of small electromagnetic loads with holding current ≤ 0.2 A; e.g. contactor relays | 60947-5-2 |
A | Protection of circuits, with no rated short-time withstand current | 60947-3 |
B | Protection of circuits, with a rated short-time withstand current | 60947-3 |
DC-1 | Non Inductive or slightly inductive loads, resistance furnaces, heaters | 60947-4-1 |
DC-3 | Shunt-motors, starting, plugging(1), inching(2), dynamic braking of motors | 60947-4-1 |
DC-5 | Series-motors, starting, plugging(1), inching(2), dynamic braking of motors | 60947-4-1 |
DC-6 | Switching of incandescent lamps | 60947-4-1 |
DC-12 | Control of resistive loads and solid state loads with opto-coupler isolation | 60947-5-1 60947-5-2 |
DC-13 | Control of D.C. electromagnetics | 60947-5-1 60947-5-2 |
DC-14 | Control of D.C. electromagnetic loads having economy resistors in the circuit | 60947-5-1 |
DC-20 | Connecting and disconnecting under no-load conditions | 60947-5-1 |
DC-21 | Switching of resistive loads, including moderate overloads | 60947-5-1 |
DC-22 | Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors) | 60947-5-1 |
DC-23 | Switching of highly inductive loads (i.e. series motors) | 60947-5-1 |
A relay is an electrically operated switch. It consists of a set of input terminals for a single or multiple control signals, and a set of operating contact terminals. The switch may have any number of contacts in multiple contact forms, such as make contacts, break contacts, or combinations thereof.
A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by overcurrent. Its basic function is to interrupt current flow to protect equipment and to prevent the risk of fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.
A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. There are 55,000 substations in the United States.
A motor controller is a device or group of devices that can coordinate in a predetermined manner the performance of an electric motor. A motor controller might include a manual or automatic means for starting and stopping the motor, selecting forward or reverse rotation, selecting and regulating the speed, regulating or limiting the torque, and protecting against overloads and electrical faults. Motor controllers may use electromechanical switching, or may use power electronics devices to regulate the speed and direction of a motor.
In electronics and electrical engineering, a fuse is an electrical safety device that operates to provide overcurrent protection of an electrical circuit. Its essential component is a metal wire or strip that melts when too much current flows through it, thereby stopping or interrupting the current. It is a sacrificial device; once a fuse has operated, it is an open circuit, and must be replaced or rewired, depending on its type.
Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.
A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary.
In electric power distribution, automatic circuit reclosers (ACRs) are a class of switchgear designed for use on overhead electricity distribution networks to detect and interrupt transient faults. Also known as reclosers or autoreclosers, ACRs are essentially rated circuit breakers with integrated current and voltage sensors and a protection relay, optimized for use as a protection asset. Commercial ACRs are governed by the IEC 62271-111/IEEE Std C37.60 and IEC 62271-200 standards. The three major classes of operating maximum voltage are 15.5 kV, 27 kV and 38 kV.
In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.
In electrical engineering, a disconnector, disconnect switch or isolator switch is a type of switching device with visible contacts, used to ensure that an electrical circuit is completely de-energized for service or maintenance. They are often found in electrical distribution and industrial applications, where machinery must have its source of driving power removed for adjustment or repair. Disconnectors can be operated manually or by a motor, and may be paired with an earthing switch to ground the portion that has been isolated from the system for ensuring the safety of equipment and the personnel working on it.
Extra-low voltage (ELV) is an electricity supply voltage and is a part of the low-voltage band in a range which carries a low risk of dangerous electrical shock. There are various standards that define extra-low voltage. The International Electrotechnical Commission (IEC) and the UK IET define an ELV device or circuit as one in which the electrical potential between two conductors or between an electrical conductor and earth (ground) does not exceed 50 V AC or 120 V DC.
A contactor is an electrically controlled switch used for switching an electrical power circuit. A contactor is typically controlled by a circuit which has a much lower power level than the switched circuit, such as a 24-volt coil electromagnet controlling a 230-volt motor switch.
A magnetic starter is an electromagnetically operated switch which provides a safe method for starting an electric motor with a large load. Magnetic starters also provide under-voltage and overload protection and an automatic cutoff in the event of a power failure.
High voltage switchgear is any switchgear used to connect or disconnect a part of a high-voltage power system. This equipment is essential for the protection and safe operation, without interruption, of a high voltage power system, and is important because it is directly linked to the quality of the electricity supply.
An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The electrical grid can be broadly divided into the generators that supply the power, the transmission system that carries the power from the generating centers to the load centers, and the distribution system that feeds the power to nearby homes and industries.
In electrical engineering, IEC 60269 is a set of technical standards for low-voltage power fuses. The standard is in four volumes, which describe general requirements, fuses for industrial and commercial applications, fuses for residential applications, and fuses to protect semiconductor devices. The IEC standard unifies several national standards, thereby improving the interchangeability of fuses in international trade. All fuses of different technologies tested to meet IEC standards will have similar time-current characteristics, which simplifies design and maintenance.
In electrical engineering, the Korndorfer starter is a technique used for reduced voltage soft starting of induction motors. The circuit uses a three-phase autotransformer and three three-phase switches. This motor starting method has been updated and improved by Hilton Raymond Bacon.
IEC 60204-1 / EN 60204 Safety of machinery – Electrical equipment of machines – Part 1: General requirements
This glossary of electrical and electronics engineering is a list of definitions of terms and concepts related specifically to electrical engineering and electronics engineering. For terms related to engineering in general, see Glossary of engineering.