Utilization categories

Last updated
Usually utilization category is mentioned in most of the switch gear, with the above contactor stating to be used under AC1 - resistive load & AC3 for motor usage Contact Swiss AB Gebrauchskategorie.jpg
Usually utilization category is mentioned in most of the switch gear, with the above contactor stating to be used under AC1 - resistive load & AC3 for motor usage

In electrical engineering utilization categories are defined by IEC standards [1] and indicate the type of electrical load and duty cycle of the loads to ease selection of contactors and relays.

Contents

Definition

The utilization categories category for low-voltage switchgear defines the characteristic operating conditions for switchgear such as contactors, circuit-breakers, circuit-breaker-fuse units, contactor relays, etc. These devices are dimensioned for different electrical loads and for different operating conditions.

The characteristic of the load to be switched or controlled determines the requirements for the switchgear and its correct selection for the intended application. In particular, the stress on the switching path caused by current and voltage during switching on and off is of enormous importance. For example, the switch-on and switch-off current at resistance load corresponds to the continuous operating current, while, for example, squirrel cage motors consumes multiple of the rated operating current during switch-on and in the acceleration phase.

Utilization categories in IEC standard

Contact load in amperes for heaters (AC1) and motors (AC3) can be found directly on the contactor. The "Utilization category" are mainly categorized in IEC 60947 in the following volume:

In addition, IEC/EN 61095 also defines categories for "household and similar applications".

Table

The following table provides an overview of the various abbreviations. Within a utilization category, the suitable size may be selected for the respective type. This depends on the rated current, the rated voltage and the electrical load to be switched.

Utilization categoryTypical application [2] [3] Applicable IEC norm [3]
AC-1Non-inductive or slightly inductive loads, example: resistive furnaces, heaters60947-4-1
AC-2 Slip-ring motors: switching off60947-4-1
AC-3 Squirrel-cage motors: starting, switches off motors during running time60947-4-1
AC-4Squirrel-cage motors: starting, plugging, inching60947-4-1
AC-5aSwitching of discharge lamps 60947-4-1
AC-5bSwitching of incandescent lamps 60947-4-1
AC-6aSwitching of transformers 60947-4-1
AC-6bSwitching of capacitor banks60947-4-1
AC-7aSlightly inductive loads in household appliances: examples: mixers, blenders60947-4-1
61095
AC-7bMotor-loads for household appliances: examples: fans, central vacuum60947-4-1
61095
AC-8aHermetic refrigerant compressor motor control with manual resetting overloads60947-4-1
AC-8bHermetic refrigerant compressor motor control with automatic resetting overloads60947-4-1
AC-12Control of resistive loads and solid state loads with opto-coupler isolation 60947-5-2
AC-13Control of solid state loads with transformer isolation60947-5-1
AC-14Control of small electromagnetic loads60947-5-1
AC-15Control of A.C. electromagnetic loads60947-5-1
AC-20Connecting and disconnecting under no-load conditions60947-3
AC-21Switching of resistive loads, including moderate overloads60947-3
AC-22Switching of mixed resistive and inductive loads, including moderate overloads60947-3
AC-23Switching of motor loads or other highly inductive loads60947-3
AC-31A
AC-31B ³)
Non-inductive or weakly inductive loads60947-6-1
AC-33A
AC33B³)
Motor loads or mixed loads including motors, resistors and up to 30% incandescent lamp load60947-6-1
AC-35A
AC-35B ³)
Gas discharge lamp load60947-6-1
AC-36A
AC36B ³)
Incandescent lamp load60947-6-1
AC-40Distribution circuits of mixed resistive and inductive loads60947-6-2
AC-41Non-inductive or weakly inductive loads, resistance furnaces60947-6-2
AC-42Slip ring motors: Starting, switching off60947-6-2
AC-43Squirrel cage motors: Starting, switching off during operation60947-6-2
AC-44Squirrel cage motors: Starting, counter-current braking ¹) or reversing ¹), typing ²)60947-6-2
AC-45aSwitching of gas discharge lamps60947-6-2
AC-45bSwitching incandescent lamps60947-6-2
AC-51Induction-free or slightly inductive loads, resistance furnaces60947-4-3
AC-52aControl of the stator winding of a slip-ring motor: 8-hour operation with starting currents for starting processes, maneuvering, operation60947-4-2
AC-52bControl of the stator winding of a slip ring motor: Intermittent operation60947-4-2
AC-53aControl of a squirrel cage motor: 8-hour operation with starting currents for starting processes, maneuvering, operation60947-4-2
AC-53bControl of a squirrel cage motor: Intermittent operation60947-4-2
AC-55aSwitching of electrical controls of discharge lamps60947-4-3
AC-55bSwitching incandescent lamps60947-4-3
AC-56aSwitching transformers60947-4-3
AC-56bSwitching of capacitor batteries60947-4-3
AC-58aControl of a hermetically sealed refrigeration compressor motor with automatic reset of overload releases: 8-hour operation with starting currents for starting, maneuvering, operation60947-4-2
AC-58bThe control of a hermetically sealed refrigeration compressor motor with automatic reset of the overload trips: Intermittent operation60947-4-2
AC-140Control of small electromagnetic loads with holding current ≤ 0.2 A; e.g. contactor relays60947-5-2
AProtection of circuits, with no rated short-time withstand current60947-3
BProtection of circuits, with a rated short-time withstand current60947-3
DC-1Non Inductive or slightly inductive loads, resistance furnaces, heaters60947-4-1
DC-3Shunt-motors, starting, plugging(1), inching(2), dynamic braking of motors60947-4-1
DC-5Series-motors, starting, plugging(1), inching(2), dynamic braking of motors60947-4-1
DC-6Switching of incandescent lamps60947-4-1
DC-12Control of resistive loads and solid state loads with opto-coupler isolation60947-5-1
60947-5-2
DC-13Control of D.C. electromagnetics60947-5-1
60947-5-2
DC-14Control of D.C. electromagnetic loads having economy resistors in the circuit60947-5-1
DC-20Connecting and disconnecting under no-load conditions60947-5-1
DC-21Switching of resistive loads, including moderate overloads60947-5-1
DC-22Switching of mixed resistive and inductive loads, including moderate overloads (i.e. shunt motors)60947-5-1
DC-23Switching of highly inductive loads (i.e. series motors)60947-5-1

See also

Related Research Articles

<span class="mw-page-title-main">Relay</span> Electrically-operated switch

A relay is an electrically operated switch. It consists of a set of input terminals for a single or multiple control signals, and a set of operating contact terminals. The switch may have any number of contacts in multiple contact forms, such as make contacts, break contacts, or combinations thereof.

<span class="mw-page-title-main">Circuit breaker</span> Automatic circuit protection device

A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by overcurrent. Its basic function is to interrupt current flow to protect equipment and to prevent the risk of fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.

<span class="mw-page-title-main">Electrical substation</span> Part of an electrical transmission, and distribution system

A substation is a part of an electrical generation, transmission, and distribution system. Substations transform voltage from high to low, or the reverse, or perform any of several other important functions. Between the generating station and consumer, electric power may flow through several substations at different voltage levels. A substation may include transformers to change voltage levels between high transmission voltages and lower distribution voltages, or at the interconnection of two different transmission voltages. They are a common component of the infrastructure. There are 55,000 substations in the United States.

A motor controller is a device or group of devices that can coordinate in a predetermined manner the performance of an electric motor. A motor controller might include a manual or automatic means for starting and stopping the motor, selecting forward or reverse rotation, selecting and regulating the speed, regulating or limiting the torque, and protecting against overloads and electrical faults. Motor controllers may use electromechanical switching, or may use power electronics devices to regulate the speed and direction of a motor.

<span class="mw-page-title-main">Fuse (electrical)</span> Electrical safety device that provides overcurrent protection

In electronics and electrical engineering, a fuse is an electrical safety device that operates to provide overcurrent protection of an electrical circuit. Its essential component is a metal wire or strip that melts when too much current flows through it, thereby stopping or interrupting the current. It is a sacrificial device; once a fuse has operated, it is an open circuit, and must be replaced or rewired, depending on its type.

Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.

<span class="mw-page-title-main">Current transformer</span> Transformer used to scale alternating current, used as sensor for AC power

A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary.

<span class="mw-page-title-main">Recloser</span>

In electric power distribution, automatic circuit reclosers (ACRs) are a class of switchgear designed for use on overhead electricity distribution networks to detect and interrupt transient faults. Also known as reclosers or autoreclosers, ACRs are essentially rated circuit breakers with integrated current and voltage sensors and a protection relay, optimized for use as a protection asset. Commercial ACRs are governed by the IEC 62271-111/IEEE Std C37.60 and IEC 62271-200 standards. The three major classes of operating maximum voltage are 15.5 kV, 27 kV and 38 kV.

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

<span class="mw-page-title-main">Disconnector</span> Electromechanical switch

In electrical engineering, a disconnector, disconnect switch or isolator switch is a type of switching device with visible contacts, used to ensure that an electrical circuit is completely de-energized for service or maintenance. They are often found in electrical distribution and industrial applications, where machinery must have its source of driving power removed for adjustment or repair. Disconnectors can be operated manually or by a motor, and may be paired with an earthing switch to ground the portion that has been isolated from the system for ensuring the safety of equipment and the personnel working on it.

<span class="mw-page-title-main">Extra-low voltage</span> Electrical standard designed to protect against electric shock

Extra-low voltage (ELV) is an electricity supply voltage and is a part of the low-voltage band in a range which carries a low risk of dangerous electrical shock. There are various standards that define extra-low voltage. The International Electrotechnical Commission (IEC) and the UK IET define an ELV device or circuit as one in which the electrical potential between two conductors or between an electrical conductor and earth (ground) does not exceed 50 V AC or 120 V DC.

<span class="mw-page-title-main">Contactor</span> Electronic circuit element serving as a switch

A contactor is an electrically controlled switch used for switching an electrical power circuit. A contactor is typically controlled by a circuit which has a much lower power level than the switched circuit, such as a 24-volt coil electromagnet controlling a 230-volt motor switch.

<span class="mw-page-title-main">Magnetic starter</span>

A magnetic starter is an electromagnetically operated switch which provides a safe method for starting an electric motor with a large load. Magnetic starters also provide under-voltage and overload protection and an automatic cutoff in the event of a power failure.

<span class="mw-page-title-main">High-voltage switchgear</span>

High voltage switchgear is any switchgear used to connect or disconnect a part of a high-voltage power system. This equipment is essential for the protection and safe operation, without interruption, of a high voltage power system, and is important because it is directly linked to the quality of the electricity supply.

<span class="mw-page-title-main">Electric power system</span> Network of electrical component deployed to generate, transmit & distribute electricity

An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The electrical grid can be broadly divided into the generators that supply the power, the transmission system that carries the power from the generating centers to the load centers, and the distribution system that feeds the power to nearby homes and industries.

In electrical engineering, IEC 60269 is a set of technical standards for low-voltage power fuses. The standard is in four volumes, which describe general requirements, fuses for industrial and commercial applications, fuses for residential applications, and fuses to protect semiconductor devices. The IEC standard unifies several national standards, thereby improving the interchangeability of fuses in international trade. All fuses of different technologies tested to meet IEC standards will have similar time-current characteristics, which simplifies design and maintenance.

<span class="mw-page-title-main">Korndörfer autotransformer starter</span>

In electrical engineering, the Korndorfer starter is a technique used for reduced voltage soft starting of induction motors. The circuit uses a three-phase autotransformer and three three-phase switches. This motor starting method has been updated and improved by Hilton Raymond Bacon.

IEC 60204-1 / EN 60204 Safety of machinery – Electrical equipment of machines – Part 1: General requirements

This glossary of electrical and electronics engineering is a list of definitions of terms and concepts related specifically to electrical engineering and electronics engineering. For terms related to engineering in general, see Glossary of engineering.

References

  1. IEC 60947 Standards for low-voltage switchgear and controlgear
  2. "IEC Utilization Categories" (PDF). Archived from the original (PDF) on 2019-01-30. Retrieved 2011-06-14.