Area of refuge

Last updated

An area of refuge or safe room [1] is a place in a building designed to hold occupants during a fire or other emergency when evacuation may not be safe or possible. Occupants can wait there until rescued or relieved by firefighters. [1]

Contents

In some instances, an area of refuge or refuge area may refer to a designated space in a multi-unit residential building that can provide relief from unsafe or uncomfortable conditions in individual units.

Beneficiaries

People who use refuge areas may include:

Technical requirements

An area of refuge is typically supplied with a steady supply of fresh or filtered outside air.

A two way communication system is provided on each floor above or below the main floor. A call box is required in each area of refuge, which can call into a central location called a base station. If the station is not attended 24 hours a day, the call must automatically call to an outside location and have two-way voice person to person communication capabilities.

Typical areas of refuge

Such locations are usually required to be bounded by fire-resistant walls and floors.

Other uses of refuge areas

In the context of climate change, where older buildings may not be designed for changing climate conditions, refuge spaces are sometimes discussed in terms of providing communal areas in multi-unit buildings for when temperature and air quality is not safe or comfortable in individual units. [3] [4]

See also

Related Research Articles

<span class="mw-page-title-main">Heating, ventilation, and air conditioning</span> Technology of indoor and vehicular environmental comfort

Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.

<span class="mw-page-title-main">Fire alarm notification appliance</span>

A fire alarm notification appliance is an active fire protection component of a fire alarm system. A notification appliance may use audible, visible, or other stimuli to alert the occupants of a fire or other emergency condition requiring action. Audible appliances have been in use longer than any other method of notification. Initially, all appliances were either electromechanical horns or electric bells, which would later be replaced by electronic sounders. Most of today's appliances produce sound levels between 70 and 100 decibels at three feet.

<span class="mw-page-title-main">Storm cellar</span>

A storm shelter or storm cellar is a type of underground bunker designed to protect the occupants from violent severe weather, particularly tornadoes. They are most frequently seen in the Midwest and Southeastern United States where tornadoes are generally frequent and the low water table permits underground structures.

<span class="mw-page-title-main">Onagawa, Miyagi</span> Town in Tōhoku, Japan

Onagawa is a town located in Miyagi Prefecture, Japan. As of 30 April 2020, the town had an estimated population of 6,319, and a population density of 97 persons per km2 in 3,110 households. The total area of the town is 65.35 square kilometres (25.23 sq mi).

<span class="mw-page-title-main">Emergency exit</span> Pathway out of a structure designed for use during emergency evacuations

An emergency exit in a structure is a special exit for emergencies such as a fire or other emergencies; the combined use of regular and special exits allows for faster evacuation, while it also provides an alternative if the route to the regular exit is blocked.

<span class="mw-page-title-main">Emergency evacuation</span> Urgent removal of people from an area of imminent or ongoing threat

Emergency evacuation is the urgent immediate egress or escape of people away from an area that contains an imminent threat, an ongoing threat or a hazard to lives or property.

Firefighting jargon includes a diverse lexicon of both common and idiosyncratic terms. One problem that exists in trying to create a list such as this is that much of the terminology used by a particular department is specifically defined in their particular standing operating procedures, such that two departments may have completely different terms for the same thing. For example, depending on whom one asks, a safety team may be referred to as a standby, a RIT or RIG or RIC, or a FAST. Furthermore, a department may change a definition within its SOP, such that one year it may be RIT, and the next RIG or RIC.

<span class="mw-page-title-main">Fire alarm control panel</span> Controlling component of a fire alarm system

A fire alarm control panel (FACP), fire alarm control unit (FACU), fire indicator panel (FIP), or simply fire alarm panel is the controlling component of a fire alarm system. The panel receives information from devices designed to detect and report fires, monitors their operational integrity, and provides for automatic control of equipment, and transmission of information necessary to prepare the facility for fire based on a predetermined sequence. The panel may also supply electrical energy to operate any associated initiating device, notification appliance, control, transmitter, or relay. There are four basic types of panels: coded panels, conventional panels, addressable panels, and multiplex systems.

<span class="mw-page-title-main">Fire escape</span> Type of emergency exit for tall buildings

A fire escape is a special kind of emergency exit, usually mounted to the outside of a building or occasionally inside but separate from the main areas of the building. It provides a method of escape in the event of a fire or other emergency that makes the stairwells inside a building inaccessible. Fire escapes are most often found on multiple-story residential buildings, such as apartment buildings.

<span class="mw-page-title-main">Control room</span> Room where a large or physically dispersed facility or service can be monitored and controlled

A control room or operations room is a central space where a large physical facility or physically dispersed service can be monitored and controlled. It is often part of a larger command center.

<span class="mw-page-title-main">Containment building</span> Structure surrounding a nuclear reactor to prevent radioactive releases

A containment building is a reinforced steel, concrete or lead structure enclosing a nuclear reactor. It is designed, in any emergency, to contain the escape of radioactive steam or gas to a maximum pressure in the range of 275 to 550 kPa. The containment is the fourth and final barrier to radioactive release, the first being the fuel ceramic itself, the second being the metal fuel cladding tubes, the third being the reactor vessel and coolant system.

<span class="mw-page-title-main">Manual fire alarm activation</span> Button or lever to activate fire alarms

Manual fire alarm activation is the process of triggering a fire alarm through a call point, pull station, or other device. This usually causes the alarm to sound the evacuation signal for the relevant building or zone. Manual fire alarm activation requires human intervention, as distinct from automatic fire alarm activation such as that provided through the use of heat detectors and smoke detectors. It is, however, possible for call points/pull stations to be used in conjunction with automatic detection as part of the overall fire detection and alarm system. Systems in completed buildings tend to be wired in and include a control panel. Wireless activators are common during construction.

<span class="mw-page-title-main">Fire alarm system</span> A system, that works using multiple devices to warn of a fire or other types of emergencies

A fire alarm system is a building system designed to detect and alert occupants and emergency forces of the presence of smoke, fire, carbon monoxide, or other fire-related emergencies. Fire alarm systems are required in most commercial buildings. They may include smoke detectors, heat detectors, and manual fire alarm activation devices, all of which are connected to a Fire Alarm Control Panel (FACP) normally found in an electrical room or panel room. Fire alarm systems generally use visual and audio signalization to warn the occupants of the building. Some fire alarm systems may also disable elevators, which under most circumstances, are unsafe to use during a fire.

Hospital emergency codes are coded messages often announced over a public address system of a hospital to alert staff to various classes of on-site emergencies. The use of codes is intended to convey essential information quickly and with minimal misunderstanding to staff while preventing stress and panic among visitors to the hospital. Such codes are sometimes posted on placards throughout the hospital or are printed on employee identification badges for ready reference.

<span class="mw-page-title-main">British Columbia Children's Hospital</span> Hospital in British Columbia, Canada

British Columbia Children's Hospital is a medical facility located in Vancouver, British Columbia, and is an agency of the Provincial Health Services Authority. It specializes in health care for patients from birth to 16 years of age. It is also a teaching and research facility for children's medicine. The hospital includes the Sunny Hill Health Centre, which provides specialized services to children and youth with developmental disabilities aged birth to 18 years.

Shelter-in-place is the act of seeking safety within the building one already occupies, rather than evacuating the area or seeking a community emergency shelter. The American Red Cross says the warning is issued when "chemical, biological, or radiological contaminants may be released accidentally or intentionally into the environment" and residents should "select a small, interior room, with no or few windows, taking refuge there."

A mine rescue chamber is an emergency shelter installed in hazardous environments, typically underground. It is also known as refuge chamber, refuge bay, or refuge alternative. Refuge chambers come in multiple types and models, and are used in multiple industries including metalliferous mining, coal, tunnelling and petrochemical facilities.

<span class="mw-page-title-main">Office space planning</span> Process of organizing workspace layout

Office space planning is the process of organizing the workplace layout, furniture and office functions to work effectively together, while using space efficiently. Floor plans should consider the workgroup function, building codes and regulations, lighting, teaming requirements, inter-communication and storage, as well as zoning for employee workstations, task space needs, support rooms and reception areas to make the best use of available space. Optimising office spaces with effective space planning can aid circulation, productivity and improve workplace wellness, as well as the health and safety of occupants.

Passive survivability refers to a building's ability to maintain critical life-support conditions in the event of extended loss of power, heating fuel, or water. This idea proposes that designers should incorporate ways for a building to continue sheltering inhabitants for an extended period of time during and after a disaster situation, whether it be a storm that causes a power outage, a drought which limits water supply, or any other possible event.

<span class="mw-page-title-main">Gossberg (Hunsrück)</span>

The Gossberg is a hill with the highest point of 483 m in the municipality of Wüschheim close to the border with Hundheim in the district of Rhein-Hunsrück-Kreis in the low mountain range of Hunsrück in the state of Rhineland-Palatinate, Germany. The summit was excavated 30 m deep in the period of 1984–1989 and transformed into the NBC bunker operated by U.S. Forces to serve as a fortified center of highly-secure communication among all NATO troops in Europe and a potential missile launch control center for the nearby missile base Pydna in case of anticipated World War III.

References

  1. 1 2 3 Roberts (2005 , p. 155)
  2. Roberts (2005 , p. 159)
  3. Schünemann, Christoph; Olfert, Alfred; Schiela, David; Gruhler, Karin; Ortlepp, Regine (2020). "Mitigation and adaptation in multifamily housing: overheating and climate justice". Buildings & Cities. 1 (1): 36–55. doi: 10.5334/bc.12 .
  4. "The Design Guide Supplement on Overheating and Air Quality" (PDF). BC Housing. p. 35. Retrieved 13 July 2021.

Bibliography