Coefficient of performance

Last updated

The coefficient of performance or COP (sometimes CP or CoP) of a heat pump, refrigerator or air conditioning system is a ratio of useful heating or cooling provided to work (energy) required. [1] [2] Higher COPs equate to higher efficiency, lower energy (power) consumption and thus lower operating costs. The COP is used in thermodynamics.

Contents

The COP usually exceeds 1, especially in heat pumps, because instead of just converting work to heat (which, if 100% efficient, would be a COP of 1), it pumps additional heat from a heat source to where the heat is required. Most air conditioners have a COP of 3.5 to 5. [3] Less work is required to move heat than for conversion into heat, and because of this, heat pumps, air conditioners and refrigeration systems can have a coefficient of performance greater than one.

The COP is highly dependent on operating conditions, especially absolute temperature and relative temperature between sink and system, and is often graphed or averaged against expected conditions. [4]

Performance of absorption refrigerator chillers is typically much lower, as they are not heat pumps relying on compression, but instead rely on chemical reactions driven by heat. [5]

Equation

The equation is:

where

The COP for heating and cooling are different because the heat reservoir of interest is different. When one is interested in how well a machine cools, the COP is the ratio of the heat taken up from the cold reservoir to input work. However, for heating, the COP is the ratio of the magnitude of the heat given off to the hot reservoir (which is the heat taken up from the cold reservoir plus the input work) to the input work:

where

Note that the COP of a heat pump depends on its direction. The heat rejected to the hot sink is greater than the heat absorbed from the cold source, so the heating COP is greater by one than the cooling COP.

Theoretical performance limits

According to the first law of thermodynamics, after a full cycle of the process and thus .
Since , we obtain

For a heat pump operating at maximum theoretical efficiency (i.e. Carnot efficiency), it can be shown [7] [6] that

and thus

where and are the thermodynamic temperatures of the hot and cold heat reservoirs, respectively.

At maximum theoretical efficiency, therefore

which is equal to the reciprocal of the thermal efficiency of an ideal heat engine, because a heat pump is a heat engine operating in reverse. [8]

Similarly, the COP of a refrigerator or air conditioner operating at maximum theoretical efficiency,

applies to heat pumps and applies to air conditioners and refrigerators. Measured values for actual systems will always be significantly less than these theoretical maxima.

In Europe, the standard test conditions for ground source heat pump units use 308 K (35 °C; 95 °F) for and 273 K (0 °C; 32 °F) for . According to the above formula, the maximum theoretical COPs would be


Test results of the best systems are around 4.5. When measuring installed units over a whole season and accounting for the energy needed to pump water through the piping systems, seasonal COP's for heating are around 3.5 or less. This indicates room for further improvement.

The EU standard test conditions for an air source heat pump is at dry-bulb temperature of 20 °C (68 °F) for and 7 °C (44.6 °F) for . [9] Given sub-zero European winter temperatures, real world heating performance is significantly poorer than such standard COP figures imply.

Improving the COP

As the formula shows, the COP of a heat pump system can be improved by reducing the temperature gap at which the system works. For a heating system this would mean two things:

  1. Reducing the output temperature to around 30 °C (86 °F) which requires piped floor, wall or ceiling heating, or oversized water to air heaters.
  2. Increasing the input temperature (e.g. by using an oversized ground source or by access to a solar-assisted thermal bank [10] ).

Accurately determining thermal conductivity will allow for much more precise ground loop [11] or borehole sizing, [12] resulting in higher return temperatures and a more efficient system. For an air cooler, the COP could be improved by using ground water as an input instead of air, and by reducing the temperature drop on the output side by increasing the air flow. For both systems, also increasing the size of pipes and air canals would help to reduce noise and the energy consumption of pumps (and ventilators) by decreasing the speed of the fluid, which in turn lowers the Reynolds number and hence the turbulence (and noise) and the head loss (see hydraulic head). The heat pump itself can be improved by increasing the size of the internal heat exchangers, which in turn increases the efficiency (and the cost) relative to the power of the compressor, and also by reducing the system's internal temperature gap over the compressor. Obviously, this latter measure makes some heat pumps unsuitable to produce high temperatures, which means that a separate machine is needed for producing, e.g., hot tap water.

The COP of absorption chillers can be improved by adding a second or third stage. Double and triple effect chillers are significantly more efficient than single effect chillers, and can surpass a COP of 1. They require higher pressure and higher temperature steam, but this is still a relatively small 10 pounds of steam per hour per ton of cooling. [13]


Seasonal efficiency

A realistic indication of energy efficiency over an entire year can be achieved by using seasonal COP or seasonal coefficient of performance (SCOP) for heat. Seasonal energy efficiency ratio (SEER) is mostly used for air conditioning. SCOP is a new methodology that gives a better indication of expected real-life performance, using COP can be considered using the "old" scale. Seasonal efficiency gives an indication on how efficiently a heat pump operates over an entire cooling or heating season. [14]

See also

Notes

  1. "Archived copy" (PDF). Archived from the original (PDF) on 2013-01-24. Retrieved 2013-10-16.{{cite web}}: CS1 maint: archived copy as title (link)
  2. "COP (Coefficient of performance)". us.grundfos.com. Archived from the original on 2014-06-28. Retrieved 2019-04-08.
  3. "Air Conditioning EER and COP" . Retrieved 9 October 2024.
  4. "Archived copy" (PDF). Archived from the original (PDF) on 2009-01-07. Retrieved 2013-10-16.{{cite web}}: CS1 maint: archived copy as title (link)
  5. "Coefficient of Performance - Measuring Efficiency in HVAC Systems". Fargo Heating and Cooling. 6 November 2023. Retrieved November 6, 2023.
  6. 1 2 Planck, M. (1945). Treatise on Thermodynamics. Dover Publications. p. §90 & §137. eqs.(39), (40), & (65).
  7. Fermi, E. (1956). Thermodynamics. Dover Publications (still in print). p. 48. eq.(64).
  8. Borgnakke, C., & Sonntag, R. (2013). The Second Law of Thermodynamics. In Fundamentals of Thermodynamics (8th ed., pp. 244-245). Wiley.
  9. According to European Union COMMISSION DELEGATED REGULATION (EU) No 626/2011 ANNEX VII Table 2
  10. "Thermal Banks store heat between seasons | Seasonal Heat Storage | Rechargeable Heat Battery | Energy Storage | Thermogeology | UTES | Solar recharge of heat batteries". www.icax.co.uk. Retrieved 2019-04-08.
  11. "Soil Thermal Conductivity Testing". Carbon Zero Consulting. Retrieved 2019-04-08.
  12. "GSHC Viability and Design". Carbon Zero Consulting. Retrieved 2019-04-08.
  13. Department of Energy Advanced Manufacturing office. Paper DOE/GO-102012-3413. January 2012
  14. "A new era of Seasonal Efficiency has begun" (PDF). Daikin.co.uk. Daikin. Archived from the original (PDF) on 31 July 2014. Retrieved 31 March 2015.

Related Research Articles

<span class="mw-page-title-main">Carnot heat engine</span> Theoretical engine

A Carnot heat engine is a theoretical heat engine that operates on the Carnot cycle. The basic model for this engine was developed by Nicolas Léonard Sadi Carnot in 1824. The Carnot engine model was graphically expanded by Benoît Paul Émile Clapeyron in 1834 and mathematically explored by Rudolf Clausius in 1857, work that led to the fundamental thermodynamic concept of entropy. The Carnot engine is the most efficient heat engine which is theoretically possible. The efficiency depends only upon the absolute temperatures of the hot and cold heat reservoirs between which it operates.

<span class="mw-page-title-main">Heat engine</span> System that converts heat or thermal energy to mechanical work

A heat engine is a system that converts heat to usable energy, particularly mechanical energy, which can then be used to do mechanical work. While originally conceived in the context of mechanical energy, the concept of the heat engine has been applied to various other kinds of energy, particularly electrical, since at least the late 19th century. The heat engine does this by bringing a working substance from a higher state temperature to a lower state temperature. A heat source generates thermal energy that brings the working substance to the higher temperature state. The working substance generates work in the working body of the engine while transferring heat to the colder sink until it reaches a lower temperature state. During this process some of the thermal energy is converted into work by exploiting the properties of the working substance. The working substance can be any system with a non-zero heat capacity, but it usually is a gas or liquid. During this process, some heat is normally lost to the surroundings and is not converted to work. Also, some energy is unusable because of friction and drag.

<span class="mw-page-title-main">Thermodynamic temperature</span> Measure of temperature relative to absolute zero

Thermodynamic temperature is a quantity defined in thermodynamics as distinct from kinetic theory or statistical mechanics.

<span class="mw-page-title-main">Heat pump</span> System that transfers heat from one space to another

A heat pump is a device that consumes energy to transfer heat from a cold heat sink to a hot heat sink. Specifically, the heat pump transfers thermal energy using a refrigeration cycle, cooling the cool space and warming the warm space. In cold weather, a heat pump can move heat from the cool outdoors to warm a house ; the pump may also be designed to move heat from the house to the warmer outdoors in warm weather. As they transfer heat rather than generating heat, they are more energy-efficient than other ways of heating or cooling a home.

In the study of heat transfer, Newton's law of cooling is a physical law which states that the rate of heat loss of a body is directly proportional to the difference in the temperatures between the body and its environment. The law is frequently qualified to include the condition that the temperature difference is small and the nature of heat transfer mechanism remains the same. As such, it is equivalent to a statement that the heat transfer coefficient, which mediates between heat losses and temperature differences, is a constant.

<span class="mw-page-title-main">Second law of thermodynamics</span> Physical law for entropy and heat

The second law of thermodynamics is a physical law based on universal empirical observation concerning heat and energy interconversions. A simple statement of the law is that heat always flows spontaneously from hotter to colder regions of matter. Another statement is: "Not all heat can be converted into work in a cyclic process."

<span class="mw-page-title-main">Carnot's theorem (thermodynamics)</span> Maximum attainable efficiency of any heat engine

Carnot's theorem, also called Carnot's rule, is a principle of thermodynamics developed by Nicolas Léonard Sadi Carnot in 1824 that specifies limits on the maximum efficiency that any heat engine can obtain.

<span class="mw-page-title-main">Rankine cycle</span> Model that is used to predict the performance of steam turbine systems

The Rankine cycle is an idealized thermodynamic cycle describing the process by which certain heat engines, such as steam turbines or reciprocating steam engines, allow mechanical work to be extracted from a fluid as it moves between a heat source and heat sink. The Rankine cycle is named after William John Macquorn Rankine, a Scottish polymath professor at Glasgow University.

In the United States, the efficiency of air conditioners is often rated by the seasonal energy efficiency ratio (SEER) which is defined by the Air Conditioning, Heating, and Refrigeration Institute, a trade association, in its 2008 standard AHRI 210/240, Performance Rating of Unitary Air-Conditioning and Air-Source Heat Pump Equipment. A similar standard is the European seasonal energy efficiency ratio (ESEER).

A binary cycle is a method for generating electrical power from geothermal resources and employs two separate fluid cycles, hence binary cycle. The primary cycle extracts the geothermal energy from the reservoir, and secondary cycle converts the heat into work to drive the generator and generate electricity.

<span class="mw-page-title-main">Thermodynamic cycle</span> Linked cyclic series of thermodynamic processes

A thermodynamic cycle consists of linked sequences of thermodynamic processes that involve transfer of heat and work into and out of the system, while varying pressure, temperature, and other state variables within the system, and that eventually returns the system to its initial state. In the process of passing through a cycle, the working fluid (system) may convert heat from a warm source into useful work, and dispose of the remaining heat to a cold sink, thereby acting as a heat engine. Conversely, the cycle may be reversed and use work to move heat from a cold source and transfer it to a warm sink thereby acting as a heat pump. If at every point in the cycle the system is in thermodynamic equilibrium, the cycle is reversible. Whether carried out reversible or irreversibly, the net entropy change of the system is zero, as entropy is a state function.

<span class="mw-page-title-main">Thermal efficiency</span> Performance measure of a device that uses thermal energy

In thermodynamics, the thermal efficiency is a dimensionless performance measure of a device that uses thermal energy, such as an internal combustion engine, steam turbine, steam engine, boiler, furnace, refrigerator, ACs etc.

<span class="mw-page-title-main">Clausius theorem</span> Version of the second law of thermodynamics

The Clausius theorem (1855), also known as the Clausius inequality, states that for a thermodynamic system exchanging heat with external thermal reservoirs and undergoing a thermodynamic cycle, the following inequality holds.

<span class="mw-page-title-main">Carnot cycle</span> Idealized thermodynamic cycle

A Carnot cycle is an ideal thermodynamic cycle proposed by French physicist Sadi Carnot in 1824 and expanded upon by others in the 1830s and 1840s. By Carnot's theorem, it provides an upper limit on the efficiency of any classical thermodynamic engine during the conversion of heat into work, or conversely, the efficiency of a refrigeration system in creating a temperature difference through the application of work to the system.

<span class="mw-page-title-main">Ground source heat pump</span> System to transfer heat to/from the ground

A ground source heat pump is a heating/cooling system for buildings that use a type of heat pump to transfer heat to or from the ground, taking advantage of the relative constancy of temperatures of the earth through the seasons. Ground-source heat pumps (GSHPs) – or geothermal heat pumps (GHP), as they are commonly termed in North America – are among the most energy-efficient technologies for providing HVAC and water heating, using far less energy than can be achieved by burning a fuel in a boiler/furnace or by use of resistive electric heaters.

<span class="mw-page-title-main">Heat pump and refrigeration cycle</span> Mathematical models of heat pumps and refrigeration

Thermodynamic heat pump cycles or refrigeration cycles are the conceptual and mathematical models for heat pump, air conditioning and refrigeration systems. A heat pump is a mechanical system that transmits heat from one location at a certain temperature to another location at a higher temperature. Thus a heat pump may be thought of as a "heater" if the objective is to warm the heat sink, or a "refrigerator" or “cooler” if the objective is to cool the heat source. The operating principles in both cases are the same; energy is used to move heat from a colder place to a warmer place.

<span class="mw-page-title-main">Heat</span> Type of energy transfer

In thermodynamics, heat is the thermal energy transferred between systems due to a temperature difference. In colloquial use, heat sometimes refers to thermal energy itself. Thermal energy is the kinetic energy of vibrating and colliding atoms in a substance.

In heat transfer, thermal engineering, and thermodynamics, thermal conductance and thermal resistance are fundamental concepts that describe the ability of materials or systems to conduct heat and the opposition they offer to the heat current. The ability to manipulate these properties allows engineers to control temperature gradient, prevent thermal shock, and maximize the efficiency of thermal systems. Furthermore, these principles find applications in a multitude of fields, including materials science, mechanical engineering, electronics, and energy management. Knowledge of these principles is crucial in various scientific, engineering, and everyday applications, from designing efficient temperature control, thermal insulation, and thermal management in industrial processes to optimizing the performance of electronic devices.

The Glossary of Geothermal Heating and Cooling provides definitions of many terms used within the Geothermal heat pump industry. The terms in this glossary may be used by industry professionals, for education materials, and by the general public.

<span class="mw-page-title-main">Thermoelectric acclimatization</span>

Thermoelectric acclimatization depends on the possibility of a Peltier cell of absorbing heat on one side and rejecting heat on the other side. Consequently, it is possible to use them for heating on one side and cooling on the other and as a temperature control system.