Service drop

Last updated
A three phase 400Y/220 volt service drop in China. Service drop.jpg
A three phase 400Y/220 volt service drop in China.

In electric power distribution, a service drop is an overhead electrical line running from a utility pole, to a customer's building or other premises. It is the point where electric utilities provide power to their customers. [1] The customer connection to an underground distribution system is usually called a "service lateral". Conductors of a service drop or lateral are usually owned and maintained by the utility company, but some industrial drops are installed and owned by the customer. [2]

Contents

At the customer's premises, the wires usually enter the building through a weatherhead that protects against entry of rain and snow, and drop down through conduit to an electric meter which measures and records the power used for billing purposes, then enters the main service panel. The utility's portion of the system ends, and the customer's wiring begins, at the output socket of the electric meter. The service panel will contain a "main" fuse or circuit breaker, which controls all of the electric current entering the building at once, and a number of smaller fuses/breakers, which protect individual branch circuits. There is always provision for all power to be cut off by operating either a single switch or small number of switches (maximum of six in the United States, for example); when circuit breakers are used this is provided by the main circuit breaker.

Residential

North American

A 240/120 V split-phase service drop providing power to a residence in USA. The three wires from the utility pole enter through a weatherhead (top) into a vertical conduit, which routes them to the electric meter (bottom). From there they pass through the wall of the house to the electric panel and Main Fuses or Circuit Breakers inside. Residence service drop.JPG
A 240/120 V split-phase service drop providing power to a residence in USA. The three wires from the utility pole enter through a weatherhead (top) into a vertical conduit, which routes them to the electric meter (bottom). From there they pass through the wall of the house to the electric panel and Main Fuses or Circuit Breakers inside.

In North America, the 120/240 V split phase system is used for residential service drops. [3] [4] A pole-mounted single phase distribution transformer usually provides power for one or two residences. The secondary winding of the transformer provides 240 volts between its ends and is center tapped. The service drop, to a weatherhead on the premises being supplied, is made up of a neutral line connected to the transformer's center tap and two lines connected to the ends of the winding which provide 120V with respect to the neutral line. When these lines are insulated and twisted together, they are referred to as a triplex cable which may contain a supporting messenger cable in the middle of the neutral conductor to provide strength for long spans. The neutral line from the pole is connected to a ground near the service panel; often a conductive rod driven into the earth. The service drop provides the building with two 120 V lines of opposite phase, so 240 V can be obtained by connecting a load between the two 120 V conductors, while 120 V loads are connected between either of the two 120 V lines and the neutral line. 240 V circuits are used for high-demand devices, such as air conditioners, water heaters, clothes dryers, ovens and boilers, while 120 V circuits are used for lighter loads such as lighting and ordinary small appliance outlets.

European

In many European countries and other countries that use European systems, three-phase service drops are often used for domestic residences. The use of three-phase power allows longer service drops to serve multiple residences, which is economical with the higher density of housing in Europe. The service drop consists of three phase wires and a neutral wire which is grounded. Each phase wire provides around 230 V to loads connected between it and the neutral. Each of the phase wires carries 50 Hz alternating current which is 120° out of phase with the other two. Several slightly different voltage standards have been used in the past as well: 220Y380, 230Y400 and 240Y415, with plans for future "harmonization" towards 230Y400. In this notation, the first number is the voltage between a phase wire and neutral, and the second number, after the "Y", is the line voltage (between any two-phase wires).

Other countries, such as the UK and Ireland, generally provide a single phase and neutral per house, with every third house on the same phase.

Australian

Australian three-phase fused "point of attachment" for electrical service to a premises Fused 'Point of Attachment' Three Phase.jpg
Australian three-phase fused "point of attachment" for electrical service to a premises

In Australian service drops, to avoid having unprotected cables within the building up to the service panel main switch, a fuse for each phase is provided at the point-of-attachment, at the weatherhead - called a "raiser bracket" in Australia - or on the outside of the building.

One or more removable ceramic "fuse holders", containing an appropriately sized service fuse for each phase protects all cables beyond this point. These fuses may be removed and replaced by the supply authority in the event of a fault causing them to "operate".

This box is termed a "Fused Overhead Line Connector Box" (FOLCB).

Commercial and industrial

Commercial and industrial service drops can be much bigger, and are usually three phase. In the US, common services are 120Y/208 (three 120 V circuits 120 degrees out of phase, with 208 V line-to-line), 240 V three-phase, and 480 V three-phase. 600 V three-phase is common in Canada, and 380-415 V or 690 V three-phase is found in European and many other countries. Generally, higher voltages are used for heavy industrial loads, and lower voltages for commercial applications.

In North America where single-phase distribution transformers for service drops are the norm, three-phase service drops are often constructed using three single-phase transformers, wired in a Y configuration. This is called a transformer bank.

Underground

Service conductors for a customer may be run underground, from a padmount transformer to a customer's meter.

Related Research Articles

<span class="mw-page-title-main">Three-phase electric power</span> Common electrical power generation, transmission and distribution method for alternating currents

Three-phase electric power is a common type of alternating current (AC) used in electricity generation, transmission, and distribution. It is a type of polyphase system employing three wires and is the most common method used by electrical grids worldwide to transfer power.

<span class="mw-page-title-main">Alternating current</span> Electric current that periodically reverses direction

Alternating current (AC) is an electric current which periodically reverses direction and changes its magnitude continuously with time, in contrast to direct current (DC), which flows only in one direction. Alternating current is the form in which electric power is delivered to businesses and residences, and it is the form of electrical energy that consumers typically use when they plug kitchen appliances, televisions, fans and electric lamps into a wall socket. The abbreviations AC and DC are often used to mean simply alternating and direct, respectively, as when they modify current or voltage.

<span class="mw-page-title-main">Mains electricity</span> Type of lower-voltage electricity most commonly provided by utilities

Mains electricity or utility power, power grid, domestic power, and wall power, or, in some parts of Canada, hydro, is a general-purpose alternating-current (AC) electric power supply. It is the form of electrical power that is delivered to homes and businesses through the electrical grid in many parts of the world. People use this electricity to power everyday items by plugging them into a wall outlet.

<span class="mw-page-title-main">Electric power distribution</span> Final stage of electricity delivery to individual consumers in a power grid

Electric power distribution is the final stage in the delivery of electricity. Electricity is carried from the transmission system to individual consumers. Distribution substations connect to the transmission system and lower the transmission voltage to medium voltage ranging between 2 kV and 33 kV with the use of transformers. Primary distribution lines carry this medium voltage power to distribution transformers located near the customer's premises. Distribution transformers again lower the voltage to the utilization voltage used by lighting, industrial equipment and household appliances. Often several customers are supplied from one transformer through secondary distribution lines. Commercial and residential customers are connected to the secondary distribution lines through service drops. Customers demanding a much larger amount of power may be connected directly to the primary distribution level or the subtransmission level.

<span class="mw-page-title-main">Single-phase electric power</span> Type of electric power distribution

In electrical engineering, single-phase electric power is the distribution of alternating current electric power using a system in which all the voltages of the supply vary in unison. Single-phase distribution is used when loads are mostly lighting and heating, with few large electric motors. A single-phase supply connected to an alternating current electric motor does not produce a rotating magnetic field; single-phase motors need additional circuits for starting, and such motors are uncommon above 10 kW in rating.

<span class="mw-page-title-main">Single-wire earth return</span> Supply energy using single wire with earth as return

Single-wire earth return (SWER) or single-wire ground return is a single-wire transmission line which supplies single-phase electric power from an electrical grid to remote areas at lowest cost. Its distinguishing feature is that the earth is used as the return path for the current, to avoid the need for a second wire to act as a return path.

Electrical wiring in North America follows the regulations and standards applicable at the installation location. It is also designed to provide proper function, and is also influenced by history and traditions of the location installation.

In electrical engineering, particularly power engineering, voltage regulation is a measure of change in the voltage magnitude between the sending and receiving end of a component, such as a transmission or distribution line. Voltage regulation describes the ability of a system to provide near constant voltage over a wide range of load conditions. The term may refer to a passive property that results in more or less voltage drop under various load conditions, or to the active intervention with devices for the specific purpose of adjusting voltage.

A distribution board is a component of an electricity supply system that divides an electrical power feed into subsidiary circuits while providing a protective fuse or circuit breaker for each circuit in a common enclosure. Normally, a main switch, and in recent boards, one or more residual-current devices (RCDs) or residual current breakers with overcurrent protection (RCBOs) are also incorporated.

<span class="mw-page-title-main">Split-phase electric power</span> Type of single-phase electric power distribution

A split-phase or single-phase three-wire system is a type of single-phase electric power distribution. It is the alternating current (AC) equivalent of the original Edison Machine Works three-wire direct-current system. Its primary advantage is that, for a given capacity of a distribution system, it saves conductor material over a single-ended single-phase system, while only requiring a single phase on the supply side of the distribution transformer.

<span class="mw-page-title-main">Ground and neutral</span> In mains electricity, part of a circuit connected to ground or earth

In electrical engineering, ground and neutral are circuit conductors used in alternating current (AC) electrical systems. The ground circuit is connected to earth, and neutral circuit is usually connected to ground. As the neutral point of an electrical supply system is often connected to earth ground, ground and neutral are closely related. Under certain conditions, a conductor used to connect to a system neutral is also used for grounding (earthing) of equipment and structures. Current carried on a grounding conductor can result in objectionable or dangerous voltages appearing on equipment enclosures, so the installation of grounding conductors and neutral conductors is carefully defined in electrical regulations. Where a neutral conductor is used also to connect equipment enclosures to earth, care must be taken that the neutral conductor never rises to a high voltage with respect to local ground.

<span class="mw-page-title-main">Autotransformer</span> Type of electrical transformer

An autotransformer is an electrical transformer with only one winding. The "auto" prefix refers to the single coil acting alone. In an autotransformer, portions of the same winding act as both the primary winding and secondary winding sides of the transformer. In contrast, an ordinary transformer has separate primary and secondary windings that are not connected by an electrically conductive path. between them.

Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.

<span class="mw-page-title-main">Distribution transformer</span> Final stage in power distribution to users

A distribution transformer or service transformer is a transformer that provides the final voltage transformation in the electric power distribution system, stepping down the voltage used in the distribution lines to the level used by the customer. The invention of a practical efficient transformer made AC power distribution feasible; a system using distribution transformers was demonstrated as early as 1882.

<span class="mw-page-title-main">Utility pole</span> Post used by public utilities to support overhead wires and related equipment

A utility pole is a column or post, usually made out of wood or aluminum alloy, used to support overhead power lines and various other public utilities, such as electrical cable, fiber optic cable, and related equipment such as transformers and street lights. It can be referred to as a transmission pole, telephone pole, telecommunication pole, power pole, hydro pole, telegraph pole, or telegraph post, depending on its application. A Stobie pole is a multi-purpose pole made of two steel joists held apart by a slab of concrete in the middle, generally found in South Australia.

An earthing system or grounding system (US) connects specific parts of an electric power system with the ground, typically the Earth's conductive surface, for safety and functional purposes. The choice of earthing system can affect the safety and electromagnetic compatibility of the installation. Regulations for earthing systems vary among countries, though most follow the recommendations of the International Electrotechnical Commission (IEC). Regulations may identify special cases for earthing in mines, in patient care areas, or in hazardous areas of industrial plants.

In an electric power system, a fault or fault current is any abnormal electric current. For example, a short circuit is a fault in which a live wire touches a neutral or ground wire. An open-circuit fault occurs if a circuit is interrupted by a failure of a current-carrying wire or a blown fuse or circuit breaker. In three-phase systems, a fault may involve one or more phases and ground, or may occur only between phases. In a "ground fault" or "earth fault", current flows into the earth. The prospective short-circuit current of a predictable fault can be calculated for most situations. In power systems, protective devices can detect fault conditions and operate circuit breakers and other devices to limit the loss of service due to a failure.

<span class="mw-page-title-main">High-leg delta</span> Type of electrical connection

High-leg delta is a type of electrical service connection for three-phase electric power installations. It is used when both single and three-phase power is desired to be supplied from a three phase transformer. The three-phase power is connected in the delta configuration, and the center point of one phase is grounded. This creates both a split-phase single phase supply and three-phase. It is called "orange leg" because the L3 wire is often required to be color-coded orange. By convention, the high leg is usually set in the center lug in the involved panel, regardless of the L1-L2-L3 designation at the transformer.

<span class="mw-page-title-main">Electric power system</span> Network of electrical component deployed to generate, transmit & distribute electricity

An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The electrical grid can be broadly divided into the generators that supply the power, the transmission system that carries the power from the generating centers to the load centers, and the distribution system that feeds the power to nearby homes and industries.

<span class="mw-page-title-main">Low-voltage network</span>

A low-voltage network or secondary network is a part of electric power distribution which carries electric energy from distribution transformers to electricity meters of end customers. Secondary networks are operated at a low voltage level, which is typically equal to the mains voltage of electric appliances.

References

  1. Carson Dunlop "Electrical Systems" Dearborn Real Estate, 2003 ISBN   0-7931-7932-7 page 24
  2. National Fire Protection Association (2017). "Article 100 Definitions". NFPA 70 National Electrical Code. 1 Batterymarch Park, Quincy, Massachusetts 02169: NFPA. Retrieved October 9, 2023. Service drop: the overhead conductors between the utility electric supply system and the service point.{{cite book}}: CS1 maint: location (link)
  3. Vadari, Mani (2013). Electric System Operations: Evolving to the Modern Grid. Artech House. p. 11. ISBN   978-1608075492.
  4. Waygood, Adrian (2015). Electrical Science for Technicians. Routledge. pp. 228–230. ISBN   978-1317534914.