EN 54-x | |
---|---|
EN standard | |
Reference | EN 54-x |
Status | Published |
Title | Fire detection and fire alarm systems |
Committee | CEN/TC 72 |
Work Item | various |
Directives | 305/2011, 89/106/EEC |
Citation in OJEU | 305/2011 (C 226, 2015-07-10) |
CE marking | Yes |
The EN 54 Fire detection and fire alarm systems is a series of European standards that includes product standards and application guidelines for fire detection and fire alarm systems as well as voice alarm systems.
The product standards define product characteristics, test methods and performance criteria against which the effectiveness and reliability of every component of fire detection and fire alarm system can be assessed and declared.
Many of the product standards of the EN 54 series are harmonised standards under the Construction Products Regulation (CPR) EU 305/2011. Annex ZA of the harmonised standards specifies which sections of the standard apply for the purposes of the CPR. Annex ZA also describes the two-stage certification:
This standard series is partly used around the world in several countries outside of European Union, for example in Latin American countries, Brasil, African and Asian countries and several islands in the Pacific Ocean.
The standardization topics relating to fire protection were among the first dealt with by CEN. This is obvious since CEN numbers the European standards in numerical ascending order according to the date of project registration. The standard on fire classes is numbered EN 2 [1] and the series of standards on portable fire extinguishers is numbered EN 3. [2] The European standardization on fire detection and fire alarm systems started already in the 1970s. EN 54-1 and EN 54-5 were issued in 1976. [3] [4]
The EN 54 series has been prepared by Technical Committee CEN/TC72 "Fire detection and fire alarm systems" of the European Committee for Standardization (CEN, French: Comité Européen de Normalisation). The figure shows some examples of national mirror technical committees. [5]
The EN 54 series of standards covers the following topics and product groups related to fire detection and fire alarm systems: [6] [7]
The following table lists all parts of the EN 54 series of standards:
Topics, group of products | Number of the standard | Title of the standard | Stand | Harmonized |
---|---|---|---|---|
Introduction | EN 54- | 1Part 1: Introduction [8] | 2021 | No |
Control panels and power supply | EN 54- | 2Part 2: Control and indicating equipment (Fire alarm control panel) | 1997 + A1:2006 + AC:1999 | Yes |
Alarm devices | EN 54- | 3Part 3: Fire alarm devices - Sounders | 2014 + A1:2019 | Yes |
Control panels and power supply | EN 54- | 4Part 4: Power supply equipment | 1997 + A1:2002 + A2:2006 + AC:1999 | Yes |
Detectors | EN 54- | 5Part 5: Heat detectors - Point heat detectors | 2017 + A1:2018 | Yes |
Detectors | EN 54- | 7Part 7: Smoke detectors - Point smoke detectors using scattered light, transmitted light or ionization | 2018 | Yes |
Detectors | EN 54-10 | Part 10: Flame detectors - Point detectors | 2002 + A1:2005 | Yes |
Detectors | EN 54-11 | Part 11: Manual call point | 2001 + A1:2005 | Yes |
Detectors | EN 54-12 | Part 12: Smoke detectors - Line detectors using an optical light beam | 2015 | Yes |
System compatibility | EN 54-13 | Part 13: Compatibility and connectability assessment of system components | 2017 + A1:2019 | No |
Application guidelines | CEN/TS 54-14 | Part 14: Guidelines for planning, design, installation, commissioning, use and maintenance (of fire detection and fire alarm systems) | 2018-10 | No |
Control panels and power supply | EN 54-16 | Part 16: Voice alarm control and indicating equipment | 2008 | Yes |
Other devices | EN 54-17 | Part 17: Short circuit isolators | 2005 + AC:2007 | Yes |
Other devices | EN 54-18 | Part 18: Input/output devices | 2005 + AC:2007 | Yes |
Detectors | EN 54-20 | Part 20: Aspirating smoke detectors | 2006 + AC:2008 | Yes |
Other devices | EN 54-21 | Part 21: Alarm transmission and fault warning routing equipment | 2006 | Yes |
Detectors | EN 54-22 | Part 22: Resettable line type heat detectors | 2015 + A1:2020 | No |
Alarm devices | EN 54-23 | Part 23: Fire alarm devices - Visual alarm devices | 2010 | Yes |
Alarm devices | EN 54-24 | Part 24: Component of voice alarm systems - Loudspeakers | 2008 | Yes |
Other devices | EN 54-25 | Part 25: Components using radio links | 2008 + AC:2012 | Yes |
Detectors | EN 54-26 | Part 26: Point fire detectors using carbon monoxide sensors | 2015 | No |
Detectors | EN 54-27 | Part 27: Duct smoke detectors | 2015 | No |
Detectors | EN 54-28 | Part 28: Non-resettable line-type heat detectors | 2016 | No |
Detectors | EN 54-29 | Part 29: Multi-sensor fire detectors - Point detectors using a combination of smoke and heat sensors | 2015 | No |
Detectors | EN 54-30 | Part 30: Multi-sensor fire detectors - Point detectors using a combination of carbon monoxide and heat sensors | 2015 | No |
Detectors | EN 54-31 | Part 31: Multi-sensor fire detectors - Point detectors using a combination of smoke, carbon monoxide and optionally heat sensors | 2014 + A1:2016 | No |
Application guidelines | CEN/TS 54-32 | Part 32: Guidelines for the planning, design, installation, commissioning, use and maintenance of voice alarm systems | 2015-07 | No |
The test fires TF1 to TF8 are used to test the fire sensitivity of the fire detectors according to the standard series EN 54.
The combustibles selected represent a spectrum of large and small combustion particles for both grey and black smoke. These include burning liquids, plastics and cellulosic (wood) materials, and glowing and smouldering fabrics. [9]
Fire type | Combustible | Heat development | Upward flow | Smoke development | Aerosol spectrum | Visible part | |
---|---|---|---|---|---|---|---|
TF1 | open cellulosic fire | wood | strong | strong | yes | mainly invisible | dark |
TF2 | Smoldering pyrolysis fire | wood | negligible | weak | yes | visible | bright |
TF3 | glowing (smoldering) fire | cotton | negligible | very weak | yes | mainly invisible | bright |
TF4 | open plastics fire | polyurethane | strong | strong | yes | mainly invisible | very dark |
TF5 | liquid fire | n-heptane | strong | strong | yes | mainly invisible | very dark |
TF6 | liquid fire | methylated spirit | strong | strong | no | none | none |
TF8 | liquid fire | decalene | negligible | weak | yes | mainly invisible | very dark |
For smoke detectors according to EN 54-7 and fire detectors with smoke sensor (parts 12, 20 and 30 of EN 54) the test fires TF2, TF3, TF4 and TF5 are used. The EN 54-20 defines the following test fires with reduced fuel quantity for aspirating smoke detectors with enhanced or very high sensitivity (class A or B):
For flame detectors according to EN 54-10, the liquid fires TF5 and TF6 are used. TF5 (n-heptane) produces a yellow sooty flame and TF6 (methylated spirits) produces a clear invisible flame.
For CO fire detectors according to EN 54-26, the smoldering fires TF2 and TF3 are used.
For duct smoke detectors according to EN 54-27 the test fires TF2, TF4 and TF8 are used.
For multi-sensor fire detectors according to EN 54-29 and EN 54-31, the test fires TF1, TF2, TF3, TF4, TF5 and TF8 are used.
British Standards (BS) are the standards produced by the BSI Group which is incorporated under a royal charter and which is formally designated as the national standards body (NSB) for the UK. The BSI Group produces British Standards under the authority of the charter, which lays down as one of the BSI's objectives to:
Set up standards of quality for goods and services, and prepare and promote the general adoption of British Standards and schedules in connection therewith and from time to time to revise, alter and amend such standards and schedules as experience and circumstances require.
Nondestructive testing (NDT) is any of a wide group of analysis techniques used in science and technology industry to evaluate the properties of a material, component or system without causing damage. The terms nondestructive examination (NDE), nondestructive inspection (NDI), and nondestructive evaluation (NDE) are also commonly used to describe this technology. Because NDT does not permanently alter the article being inspected, it is a highly valuable technique that can save both money and time in product evaluation, troubleshooting, and research. The six most frequently used NDT methods are eddy-current, magnetic-particle, liquid penetrant, radiographic, ultrasonic, and visual testing. NDT is commonly used in forensic engineering, mechanical engineering, petroleum engineering, electrical engineering, civil engineering, systems engineering, aeronautical engineering, medicine, and art. Innovations in the field of nondestructive testing have had a profound impact on medical imaging, including on echocardiography, medical ultrasonography, and digital radiography.
The UL enterprise is a global private safety company headquartered in Northbrook, Illinois, composed of three organizations, UL Research Institutes, UL Standards & Engagement and UL Solutions.
A smoke detector is a device that senses smoke, typically as an indicator of fire. Smoke detectors/Alarms are usually housed in plastic enclosures, typically shaped like a disk about 125 millimetres (5 in) in diameter and 25 millimetres (1 in) thick, but shape and size vary. Smoke can be detected either optically (photoelectric) or by physical process (ionization). Detectors may use one or both sensing methods. Sensitive alarms can be used to detect and deter smoking in banned areas. Smoke detectors in large commercial and industrial buildings are usually connected to a central fire alarm system.
A fire alarm notification appliance is an active fire protection component of a fire alarm system. A notification appliance may use audible, visible, or other stimuli to alert the occupants of a fire or other emergency condition requiring action. Audible appliances have been in use longer than any other method of notification. Initially, all appliances were either electromechanical horns or electric bells, which would later be replaced by electronic sounders. Most of today's appliances produce sound levels between 70 and 100 decibels at 3 ft.
A fire door is a door with a fire-resistance rating used as part of a passive fire protection system to reduce the spread of fire and smoke between separate compartments of a structure and to enable safe egress from a building or structure or ship. In North American building codes, it, along with fire dampers, is often referred to as a closure, which can be derated compared against the fire separation that contains it, provided that this barrier is not a firewall or an occupancy separation. In Europe national standards for fire doors have been harmonised with the introduction of the new standard EN 16034, which refers to fire doors as fire-resisting door sets. Starting September 2016, a common CE marking procedure was available abolishing trade barriers within the European Union for these types of products. In the UK, it is Part B of the Building Regulations that sets out the minimum requirements for the fire protection that must be implemented in all dwellings this includes the use of fire doors. All fire doors must be installed with the appropriate fire resistant fittings, such as the frame and door hardware, for it to fully comply with any fire regulations.
Manual fire alarm activation is the process of triggering a fire alarm through a call point, pull station, or other device. This usually causes the alarm to sound the evacuation signal for the relevant building or zone. Manual fire alarm activation requires human intervention, as distinct from automatic fire alarm activation such as that provided through the use of heat detectors and smoke detectors. It is, however, possible for call points/pull stations to be used in conjunction with automatic detection as part of the overall fire detection and alarm system. Systems in completed buildings tend to be wired in and include a control panel. Wireless activators are common during construction.
A helium mass spectrometer is an instrument commonly used to detect and locate small leaks. It was initially developed in the Manhattan Project during World War II to find extremely small leaks in the gas diffusion process of uranium enrichment plants. It typically uses a vacuum chamber in which a sealed container filled with helium is placed. Helium leaks out of the container, and the rate of the leak is detected by a mass spectrometer.
A carbon monoxide detector or CO detector is a device that detects the presence of the carbon monoxide (CO) gas to prevent carbon monoxide poisoning. In the late 1990s, Underwriters Laboratories changed the definition of a single station CO detector with a sound device to carbon monoxide (CO) alarm. This applies to all CO safety alarms that meet UL 2034 standard; however for passive indicators and system devices that meet UL 2075, UL refers to these as carbon monoxide detectors. Most CO detectors use a sensor with a defined, limited lifespan, and will not work indefinitely.
An aspirating smoke detector (ASD) is a system used in active fire protection, consisting of a central detection unit which draws air through a network of pipes to detect smoke. The sampling chamber is based on a nephelometer that detects the presence of smoke particles suspended in air by detecting the light scattered by them in the chamber. ASDs can typically detect smoke before it is visible to the naked eye.
Information security standards are techniques generally outlined in published materials that attempt to protect a user's or organization's cyber environment. This environment includes users themselves, networks, devices, all software, processes, information in storage or transit, applications, services, and systems that can be connected directly or indirectly to networks.
A fire alarm system is a building system designed to detect, alert occupants, and alert emergency forces of the presence of fire, smoke, carbon monoxide, or other fire-related emergencies. Fire alarm systems are required in most commercial buildings. They may include smoke detectors, heat detectors, and manual fire alarm activation devices. All components of a fire alarm system are connected to a fire alarm control panel. Fire alarm control panels are usually found in an electrical or panel room. Fire alarm systems generally use visual and audio signalization to warn the occupants of the building. Some fire alarm systems may also disable elevators, which are unsafe to use during a fire under most circumstances.
The British Standards Institution (BSI) is the national standards body of the United Kingdom. BSI produces technical standards on a wide range of products and services and also supplies standards certification services for business and personnel.
The Keymark is a voluntary European certification mark demonstrating compliance with the European Standard (EN). It is owned by CEN, the European Committee for Standardization, and CENELEC, the European Committee for Electrotechnical Standardization.
Fire dampers are passive fire protection products used in heating, ventilation, and air conditioning (HVAC) ducts to prevent and isolate the spread of fire inside the ductwork through fire-resistance rated walls and floors. Fire/smoke dampers are similar to fire dampers in fire resistance rating, and also prevent the spread of smoke inside the ducts. When a rise in temperature occurs, the fire damper closes, usually activated by a thermal element which melts at temperatures higher than ambient but low enough to indicate the presence of a fire, allowing springs to close the damper blades. Fire dampers can also close following receipt of an electrical signal from a fire alarm system utilising detectors remote from the damper, indicating the sensing of heat or smoke in the building occupied spaces or in the HVAC duct system.
Honeywell Gent, formerly Gents' of Leicester, is a British manufacturer of life safety equipment based in Leicester, England. Established by John Thomas Gent, the company is thought to have started in 1872 however it could have been trading as early as the 1860s. The company had a workforce of several hundred at its height.
An optical beam smoke detector is a device that uses a projected beam of light to detect smoke across large areas, typically as an indicator of fire. They are used to detect fires in buildings where standard point smoke detectors would either be uneconomical or restricted for use by the height of the building. Optical beam smoke detectors are often installed in warehouses as a cost-effective means of protecting large open spaces.
BS 5839 Part 1Fire detection and fire alarm systems for buildings – Part 1: Code of practice for design, installation, commissioning and maintenance of systems in non-domestic premises is a standard published by the British Standards Institution. BS 5839-1:2013 supersedes BS 5839-1:2002+A2:2008, which has been withdrawn. It s the first of 9 parts in a series on national standards relating to fire alarms.
EN 16034 is a set of European standards which specify the technical performance characteristics for fire resistant and smoke control products, such as fire doors. Compliance with this standard requires to fulfill the requirements of the Construction Product Regulation for construction products.
The Fire Industry Association (FIA) is a not-for-profit organisation formed originally by the merger of the Fire Extinguishing Trades Association (FETA) and the British Fire Protection Systems Association (BFPSA).