NeSSI (for New Sampling/Sensor Initiative) is a global and open initiative sponsored by the Center for Process Analysis and Control (CPAC) at the University of Washington, in Seattle.

Contents

The NeSSI initiative was begun to simplify the tasks and reduce the overall costs associated with engineering, installing, and maintaining chemical process analytical systems. Process analytical systems are commonly used by the chemical, oil refining and petrochemical industries to measure and control both chemical composition as well as certain intrinsic physical properties (such as viscosity). The specific objectives of NeSSI are:

  1. Increasing the reliability of these systems through the use of increased automation,
  2. Shrinking their physical size and energy use by means of miniaturization,
  3. Promoting the creation and use of industry standards for process analytical systems,
  4. Helping create the infrastructure needed to support the use of the emerging class of robust and selective microAnalytical sensors.

To date, NeSSI has served as a forum for the adoption and improvement of an industrial standard which specifies the use of miniature and modular Lego-like flow components. NeSSI has also issued a specification which has been instrumental in spurring the development and commercialization of a plug and play low power communication bus (NeSSI-bus) specifically designed for use with process analytical sample systems in electrically hazardous environments. As part of its development road map, NeSSI has defined the electrical and mechanical interfaces, as well as compiled a list of automated (smart) software features, which are now beginning to be used by microanalytical manufacturers for industrial applications.

Background

Conventional sample system in an analyzer house ca. 2006 Analyzer Shelter.jpg
Conventional sample system in an analyzer house ca. 2006

Modern chemical and petrochemical processing plants are complex systems containing many steps (often called unit operations) involved in producing one or more products from various raw materials. In order to control the many processes, for both improved product quality and operational safety, many measurements are made at the different stages of processing. These measurements, either from simple sensors (such as temperature, pressure, flow, etc.) or from sophisticated chemical analyzers (providing composition of one or more components in the chemical stream), are typically used as inputs to process control algorithms to give a "snapshot" of the process operation and to control the process to ensure it is operating efficiently and safely.

Traditionally, most of the measurements (with the exception of temperature, pressure and flow) were performed "off-line" by taking a sample from the process and analyzing it in the laboratory. Beginning in the latter of part of the 1930s, a trend aimed at moving the analysis from the laboratory to the process plant began. With the advent of more sophisticated analyzers, this concept known as Process Analytics become much more prevalent in the 1980s and a new discipline called Process Analytical Chemistry (PAC) emerged which combined chemical engineering and analytical chemistry.

One of the main driving forces for PAC (See also: PAT) is to remove the bottleneck and time lag associated with sending the samples to the lab and waiting for the analysis results. By moving the analysis to the process, results can be obtained closer to real-time which effectively improves the ability for the control action to correct for process changes (i.e., feedback and feed forward control).

By far, the most common implementation of PAC (especially for more complex analyzers) utilizes what is known as extractive sampling. This typically involves the continuous (or sometimes periodic) removal of a small portion of sample from a much larger piping system or process vessel. This sample is then conditioned (filtered, pressure regulated, flow controlled, etc.) and introduced to the analyzer where the chemical composition or the intrinsic physical properties of process fluids (vapours and liquids) are measured. In industrial plants, the majority of sample systems and their related analyzers are installed in analyzer houses.

The hardware (traditionally metal tubing, compression fittings, valves, regulators, rotameters and filters) associated with extractive sampling is collectively referred to as the sampling system. Sample systems are used to condition or adjust the sample conditions (pressure, amount of particulate allowed, temperature and flow) to a level suitable for use with an analytical device (analyzer) such as a gas chromatograph, an oxygen analyzer or an infra red spectrometer. Despite the simple explanation just given, modern sampling systems can be quite large, complex, and expensive. The design features of analytical sample systems have changed little, when the discipline of Process Analytics began in Germany, right through until the present day. An example of an early analyzer and sample system used at the Buna Chemical Works (Schkopau, Germany), is shown in the following photograph. Process analytics remains exceptional in the fact that it is the last outpost of low level automation (retains manual adjustments and visible checks) within the process industries.

Analyzer and associated sample system Schkopau, Germany ca. 1954 Old process analyzer.jpg
Analyzer and associated sample system Schkopau, Germany ca. 1954

History

The rationale for NeSSI originated from focus group meetings held in 1999 at the Center for Process Analytical Chemistry (CPAC) which called out for more reliable sampling and analysis for the manufacturing processes. Early work with NeSSI was started in July, 2000 by Peter van Vuuren (of ExxonMobil Chemical) and Rob Dubois (of Dow Chemical) with the initial aim of adopting new types of modular and miniature hardware which were being addressed in a standard being developed by an ISA (Instrumentation, Systems and Automation Society) technical committee. (Reference 1)

The term NeSSI, along with the futuristic concepts of a communication/power bus specifically designed for process analytical (the NeSSI-bus) and fully automated sampling systems were first introduced outside of CPAC at a presentation given in January 2001 at the International Forum of Process Analytical Chemistry (IFPAC) at Amelia Island, Florida, USA. These new concepts were collected in the NeSSI Generation II Specification and released by CPAC in 2003 as an open publication. The specification is located on the CPAC website. (Reference 2)

NeSSI Technical Objectives

Comparison of Current Technology vs. NeSSI Technology (Extractive Systems)

Current TechnologyNeSSI Technology
(when fully developed)
Analyzer sheltersAnalytical system close to the sampling point (By-Line)
Long, heat-traced transfer linesShort lines, fast response
Extensive design requiredSimplify design by the use of web based design tools, standard component symbol sets, and more common use of modular/functional design blocks
Custom assemblyModular assembly
Field repairModular replacement
Preventive maintenance required, personnel needed to monitor flows, temperatures and pressures, sometimes on a daily round basisPredictive maintenance, diagnostic data is logged automatically, and action taken only when needed
Typically a low level of automation in the sampling systemHigh level automation - pressure, temperature, flow and heaters monitored and controlled
Large amount of sampleSmall amount of sample, less material to condition
Conduits, seals, armoured cable, purging and pressurizationSimple plug-in connector, unarmoured wiring using miniature, flexible cable
Large space requiredSmall, compact, low internal volume
Multiple independent systemsTighter integration of the sampling system with its analyzer and other support infrastructure such as heat tracing and sample disposal

Technology Development Roadmap

Technology Development Roadmap Pyramid End user value.jpg
Technology Development Roadmap Pyramid

The NeSSI Technology Development Roadmap groups the technology into three generations, which are backward compatible. Generation I is a commercial product and proven in numerous industrial and laboratory applications. Generation II products have been proven in the laboratory but have yet to be commercialized. Generation III (microanalytical) is in development.

Technical Development Generations

Generation I Fluid Components

Generation I covers the commercially available mechanical systems associated with the fluid handling components. Generation I has adopted the ANSI/ISA SP76.00.2002 miniature, modular mechanical standard. This standard precisely defines inlet and outlet ports and overall dimensions which allow Lego-like interchangeability of components, between different manufacturers. The ANSI/ISA standard is referenced by the International Electrotechnical Commission in publication IEC 62339-1:2006.

The ANSI/ISA SP76.00.02-2002 standard defines dimensions and porting. ANSI-ISA SP76 mechanical footprint.jpg
The ANSI/ISA SP76.00.02-2002 standard defines dimensions and porting.

Currently three manufacturers produce the mechanical mounting system (known as a substrate) which serves as the platform for attaching various components. Since the components are bolted to the surface of the substrate, sealed by O-rings, they are sometimes referred to as surface mount devices. (The semiconductor industry has a related system; however, the sealing is done by metallic seals rather than elastomeric O-rings.) There are currently over 60 different types of surface mount components available from various suppliers who provide valves, filters and regulators as well as pressure and flow sensing devices. Although the platform for mounting various components is common among the manufacturers, the interconnections below the surface are proprietary. The following figure shows three of the common designs. (From left to right) A Swagelok system which uses various lengths of tube connectors set in rigid channels; a CIRCORTech design which uses a single block with assorted flow-tubes; and a Parker Hannifin design which uses various blocks ported together with small connectors which also serve as flow paths.

Generation II Connectivity using NeSSI-bus and the SAM

The key elements of the NeSSI Generation II Specification are as follows.

Generation II Connectivity Model using NeSSI-bus and SAM NeSSI Gen II connectivity model.jpg
Generation II Connectivity Model using NeSSI-bus and SAM

The first prototype of a multi node/miniature Generation II system was demonstrated by Siemens Process Analytics in 2006. Siemens has adapted an existing bus system called I2C to operate in an intrinsically safe mode. This work was undertaken once it was determined that existing intrinsically safe capable digital communication systems such as Foundation Fieldbus and Profibus could not meet the requirements of reduced physical size as well as the lower cost and power draw defined by the NeSSI-bus. Whether or not this bus will go into wide commercial production is unknown at this time.

An example of a Generation 1.5 system NeSSI Gen I 5.jpg
An example of a Generation 1.5 system

A nonprofit organization, CAN in Automation (CiA) released a 2007 Draft Standard Proposal (DSP-103), that specifies the physical layer of an intrinsically safe bus. [CAN = Controller Area Network] The specification has been developed by members of the CiA organization among them ABB, Pepperl+Fuchs, Texas Instruments, and Siemens. By using a lower voltage (9.5 V) for its power supply, this bus can provide more current (up to 1,000 mA) to power multiple devices in a hazardous environment. This group has standardized upon the 5-pin M8 pico connector for providing both power and signal to the devices. A commercial implementation of a process analytical system using this bus has yet to be demonstrated.

An interim development called Generation 1.5 uses both conventional 4-20 mA analogue sensors and discrete signals to actuate valves. A Programmable Logic Controller (PLC) is used as the Sensor Actuator Manager (SAM).

Generation III - microAnalytical

The introduction of new microAnalytical devices to the process industries can be enabled by employing standard physical, electrical and software interfaces. Generation III will allow tighter integration of the sample conditioning and analytical measurement devices.

An example of an integrated analytical device (oxygen transmitter) and sampling system. NeSSI GenIII.jpg
An example of an integrated analytical device (oxygen transmitter) and sampling system.

Applications

NeSSI is used for process analytical measurements in the petrochemical, chemical and oil refining industries. These measurements may be for quality control of raw material or final product, environmental compliance, safety, energy reduction or process control purposes. Vapour applications may include hydrocarbon feed stocks and intermediates (ethylene, ethane, propylene, etc.), natural gas streams, liquefied petroleum gas (LPG) streams, hydrogen and air gas streams.

Liquid systems suitable for use with the Generation I mechanical portion of NeSSI are hydrocarbons such as diesel fuel as well as aqueous streams. Highly viscous fluids and solids are not suitable for use with NeSSI. Very dirty, high particulate streams need to be filtered. Some liquid service applications may be limited by pressure drops associated with components hooked up in a serial configuration. NeSSI systems have found applications in areas other than the process analytical environments including micro reactor, mini plant and laboratory environments where small size, unskilled assembly and flexible configuration is important.

Role of CPAC

The development of NeSSI has been a collaborative effort between industrial end-users, manufacturers who supply the industries, and academic researchers working in the area of process analytics. CPAC continues as the focal point for NeSSI development, and sponsor of the NeSSI steering team. CPAC provides a neutral umbrella under which interested companies have been able to meet, discuss needs and issues, and make progress towards defining the future of industrial sampling and analyzer systems. The NeSSI name is trademarked by the University of Washington to ensure that it remains freely associated with the open nature of the initiative anyone can use the name NeSSI to refer to products or services that are consistent with the specifications and guidelines of NeSSI as long as they refrain from exclusively tying the name to a proprietary product or service.

Criticism, Impact and Summary

Criticism of NeSSI mechanical systems have included higher initial cost, inability to troubleshoot at a component level (due to compact/intensive spacing), and the lack of performance data associated with the use of elastomeric seals in long term installations. From a design perspective, it may be difficult to design a modular, mechanical system which meets the needs of the diverse process applications found in industry. Development of the NeSSI-bus has been an iterative exercise, and it will need the close cooperation of both component and analyzer manufacturers to make their equipment NeSSI-bus compliant. At this time, there are missing elements such as a low cost, low power flow sensor which is capable of providing a continuous reading of sample system flow as well as a proportional, miniature control valve.

The predicted impact of NeSSI systems are as follows:

Since its debut in 2000, NeSSI the mechanical portion has seen gradual but steady acceptance in industry. Currently, there are three major commercial suppliers of NeSSI compliant mechanical systems along with dozens of components available for mounting on these systems. There is also a growing list of companies implementing NeSSI systems in their manufacturing and pilot-plant facilities. Recently, two of the largest suppliers of process analyzers have committed to supporting NeSSI hardware and the development of the intrinsically safe NeSSI-bus communication into their products. NeSSI is gaining status as a de facto standard for many process sampling system applications.

NeSSI (Generation I) acceptance has spread beyond its initial chemical and petrochemical industry roots to find applications in the automotive, food, and pharmaceutical industries, as well as applications as an analytical development system in research laboratories. Generation II electrical systems are now close to commercialization with the first industrial systems scheduled for operation in 2008.

Related Research Articles

Instrumentation is a collective term for measuring instruments, used for indicating, measuring and recording physical quantities. It is also a field of study about the art and science about making measurement instruments, involving the related areas of metrology, automation, and control theory. The term has its origins in the art and science of scientific instrument-making.

In the seven-layer OSI model of computer networking, the physical layer or layer 1 is the first and lowest layer: the layer most closely associated with the physical connection between devices. The physical layer provides an electrical, mechanical, and procedural interface to the transmission medium. The shapes and properties of the electrical connectors, the frequencies to broadcast on, the line code to use and similar low-level parameters, are specified by the physical layer.

<span class="mw-page-title-main">Data acquisition</span> Process of sampling signals from sensors and converting into digital data

Data acquisition is the process of sampling signals that measure real-world physical conditions and converting the resulting samples into digital numeric values that can be manipulated by a computer. Data acquisition systems, abbreviated by the acronyms DAS,DAQ, or DAU, typically convert analog waveforms into digital values for processing. The components of data acquisition systems include:

Microtechnology deals with technology whose features have dimensions of the order of one micrometre. It focuses on physical and chemical processes as well as the production or manipulation of structures with one-micrometre magnitude.

<span class="mw-page-title-main">Electronic test equipment</span> Testing appliance for electronics systems

Electronic test equipment is used to create signals and capture responses from electronic devices under test (DUTs). In this way, the proper operation of the DUT can be proven or faults in the device can be traced. Use of electronic test equipment is essential to any serious work on electronics systems.

<span class="mw-page-title-main">Automatic test equipment</span> Apparatus used in hardware testing that carries out a series of tests automatically

Automatic test equipment or automated test equipment (ATE) is any apparatus that performs tests on a device, known as the device under test (DUT), equipment under test (EUT) or unit under test (UUT), using automation to quickly perform measurements and evaluate the test results. An ATE can be a simple computer-controlled digital multimeter, or a complicated system containing dozens of complex test instruments capable of automatically testing and diagnosing faults in sophisticated electronic packaged parts or on wafer testing, including system on chips and integrated circuits.

<span class="mw-page-title-main">RapidIO</span> Electrical connection technology

The RapidIO architecture is a high-performance packet-switched electrical connection technology. RapidIO supports messaging, read/write and cache coherency semantics. Based on industry-standard electrical specifications such as those for Ethernet, RapidIO can be used as a chip-to-chip, board-to-board, and chassis-to-chassis interconnect.

<span class="mw-page-title-main">Chemical plant</span> Industrial process plant that manufactures chemicals

A chemical plant is an industrial process plant that manufactures chemicals, usually on a large scale. The general objective of a chemical plant is to create new material wealth via the chemical or biological transformation and or separation of materials. Chemical plants use specialized equipment, units, and technology in the manufacturing process. Other kinds of plants, such as polymer, pharmaceutical, food, and some beverage production facilities, power plants, oil refineries or other refineries, natural gas processing and biochemical plants, water and wastewater treatment, and pollution control equipment use many technologies that have similarities to chemical plant technology such as fluid systems and chemical reactor systems. Some would consider an oil refinery or a pharmaceutical or polymer manufacturer to be effectively a chemical plant.

A piping and instrumentation diagram is a detailed diagram in the process industry which shows the piping and process equipment together with the instrumentation and control devices.

<span class="mw-page-title-main">AutoAnalyzer</span> Automated analyzer using a flow technique

The AutoAnalyzer is an automated analyzer using a flow technique called continuous flow analysis (CFA), or more correctly segmented flow analysis (SFA) first made by the Technicon Corporation. The instrument was invented in 1957 by Leonard Skeggs, PhD and commercialized by Jack Whitehead's Technicon Corporation. The first applications were for clinical analysis, but methods for industrial and environmental analysis soon followed. The design is based on segmenting a continuously flowing stream with air bubbles.

<span class="mw-page-title-main">Polarimeter</span> Instrument for measuring polarization

A polarimeter is a scientific instrument used to measure the angle of rotation caused by passing polarized light through an optically active substance.

An analyser or analyzer is a tool used to analyze data. For example, a gas analyzer tool is used to analyze gases. It examines the given data and tries to find patterns and relationships. An analyser can be a piece of hardware or software.

A particle counter is used for monitoring and diagnosing particle contamination within specific clean media, including air, water and chemicals. Particle counters are used in a variety of applications in support of clean manufacturing practices, industries include: electronic components and assemblies, pharmaceutical drug products and medical devices, and industrial technologies such as oil and gas.

Moisture analysis covers a variety of methods for measuring the moisture content in solids, liquids, or gases. For example, moisture is a common specification in commercial food production. There are many applications where trace moisture measurements are necessary for manufacturing and process quality assurance. Trace moisture in solids must be known in processes involving plastics, pharmaceuticals and heat treatment. Fields that require moisture measurement in gasses or liquids include hydrocarbon processing, pure semiconductor gases, bulk pure or mixed gases, dielectric gases such as those in transformers and power plants, and natural gas pipeline transport. Moisture content measurements can be reported in multiple units, such as: parts per million, pounds of water per million standard cubic feet of gas, mass of water vapor per unit volume or mass of water vapor per unit mass of dry gas.

Smart systems incorporate functions of sensing, actuation, and control in order to describe and analyze a situation, and make decisions based on the available data in a predictive or adaptive manner, thereby performing smart actions. In most cases the “smartness” of the system can be attributed to autonomous operation based on closed loop control, energy efficiency, and networking capabilities.

Partial stroke testing is a technique used in a control system to allow the user to test a percentage of the possible failure modes of a shut down valve without the need to physically close the valve. PST is used to assist in determining that the safety function will operate on demand. PST is most often used on high integrity emergency shutdown valves (ESDVs) in applications where closing the valve will have a high cost burden yet proving the integrity of the valve is essential to maintaining a safe facility. In addition to ESDVs PST is also used on high integrity pressure protection systems or HIPPS. Partial stroke testing is not a replacement for the need to fully stroke valves as proof testing is still a mandatory requirement.

Chemical process miniaturization refers to a philosophical concept within the discipline of process design that challenges the notion of "economy of scale" or "bigger is better". In this context, process design refers to the discipline taught primarily to chemical engineers. However, the emerging discipline of process miniaturization will involve integrated knowledge from many areas; as examples, systems engineering and design, remote measurement and control using intelligent sensors, biological process systems engineering, and advanced manufacturing robotics, etc.

Ultrapure water (UPW), high-purity water or highly purified water (HPW) is water that has been purified to uncommonly stringent specifications. Ultrapure water is a term commonly used in manufacturing to emphasize the fact that the water is treated to the highest levels of purity for all contaminant types, including: organic and inorganic compounds; dissolved and particulate matter; volatile and non-volatile; reactive, and inert; hydrophilic and hydrophobic; and dissolved gases.

<span class="mw-page-title-main">Miniature mass spectrometer</span>

A miniature mass spectrometer (MMS) is a type of mass spectrometer (MS) which has small size and weight and can be understood as a portable or handheld device. Current lab-scale mass spectrometers however, usually weigh hundreds of pounds and can cost on the range from thousands to millions of dollars. One purpose of producing MMS is for in situ analysis. This in situ analysis can lead to much simpler mass spectrometer operation such that non-technical personnel like physicians at the bedside, firefighters in a burning factory, food safety inspectors in a warehouse, or airport security at airport checkpoints, etc. can analyze samples themselves saving the time, effort, and cost of having the sample run by a trained MS technician offsite. Although, reducing the size of MS can lead to a poorer performance of the instrument versus current analytical laboratory standards, MMS is designed to maintain sufficient resolutions, detection limits, accuracy, and especially the capability of automatic operation. These features are necessary for the specific in-situ applications of MMS mentioned above.

References

  1. "ANSI/ISA 76.00.02-2002 Modular Component Interfaces for Surface-Mount Fluid Distribution Components – Part1: Elastomeric Seals," Instrumentation, Systems, and Automation Society (ISA), Compositional Analyzers Committee, (2002), www.isa.org
  2. Dubois, Robert N.; van Vuuren, Peter; Gunnell, Jeffrey J. "NeSSI (New Sampling/Sensor Initiative) Generation II Specification", A Conceptual and Functional Specification Describing the Use of Miniature, Modular Electrical Components for Adaptation to the ANSI/ISA SP76 Substrate in Electrically Hazardous Areas. Center for Process Analytical Chemistry (CPAC), University of Washington, Seattle WA, (2003)