Capability curve

Last updated
D-curve. Active power is on the horizontal axis, reactive power is on the vertical axis. Capability curve of an electrical generator.png
D-curve. Active power is on the horizontal axis, reactive power is on the vertical axis.

Capability curve of an electrical generator describes the limits of the active (MW) and reactive power (MVAr) that the generator can provide. The curve represents a boundary of all operating points in the MW/MVAr plane; it is typically drawn with the real power on the horizontal axis, and, for the synchronous generator, resembles a letter D in shape, thus another name for the same curve, D-curve. In some sources the axes are switched, and the curve gets a dome-shaped appearance.[ citation needed ]

Contents

Synchronous generators

For a traditional synchronous generator the curve consists of multiple segments, each due to some physical constraint:

The corners between the sections of the curve define the limits of the power factor (PF) that the generator can sustain at its nameplate capacity (the illustration has the PF ticks placed at 0.85 lagging and 0.95 leading angles). In practice, the prime mover (a power source that drives the generator) is designed for less active power than the generator is capable of (due to the fact that in real life generator always has to deliver some reactive power [2] ), so a prime mover limit (a vertical dashed line on the illustration) changes the constraints somewhat (in the example, the leading PF limit, now at the intersection of the prime mover limit and core end heating limit, lowers to 0.93. [1]

Due to high cost of a generator, a set of sensors and limiters will trigger the alarm when the generator approaches the capability-set boundary and, if no action is taken by the operator, will disconnect the generator from the grid. [3]

D-curve expands with cooling Capability curve of an electrical generator expanded with cooling.png
D-curve expands with cooling

The D-curve for a particular generator can be expanded by improved cooling. Hydrogen-cooled turbo generator's cooling can be improved by increasing the hydrogen pressure, larger generators, from 300 MVA, use more efficient water cooling. [3]

Capability curve of a synchronous generator with minimum load Capability curve with minimum power level.svg
Capability curve of a synchronous generator with minimum load

The practical D-curve of a typical synchronous generator has one more limitation, minimum load. The minimum real power requirement means that the left-side of a D-curve is detached from the vertical axis. Although some generators are designed to be able to operate at zero load (as synchronous condensers), operation at real power levels between zero and the minimum is not possible even with these designs. [4]

Wind and solar photovoltaics generators

Capability curves for generators with full converters: D-shape (red), rectangular (green), triangular (blue) Capability curves for generators with full converters.svg
Capability curves for generators with full converters: D-shape (red), rectangular (green), triangular (blue)

The inverter-based resources (like solar photovoltaic (PV) generators, doubly-fed induction generators and full-converter wind generators, also known as "Type 3" and "Type 4" turbines [5] ) need to have reactive capabilities in order to contribute to the grid stability, yet their contribution is quite different from the synchronous generators and is limited by internal voltage, temperature, and current constraints. [6] Due to flexibility allowed by the presence of the power converter, the doubly-fed and full-converter wind generators on the market have different shapes of the capability curve: "triangular", "rectangular", "D-shape" [7] (the latter one resembles the D-curve of a synchronous generator). The rectangular and D-shapes of the curve theoretically allow using the generator to provide voltage regulation services even when the unit does not produce any active energy (due to low wind or no sun), essentially working as a STATCOM, but not all designs include this feature. The fixed speed wind turbines without a power converter (also known as "Type 1" and "Type 2" [5] ) cannot be used for voltage control. They simply absorb the reactive power (like any typical induction machine), so a switched capacitor bank is usually used to correct the power factor to unity. [7]

Capability curve of a photovoltaic generator Capability curve for PV.png
Capability curve of a photovoltaic generator

Older PV generators were intended for distribution networks. Since the current state of these networks does not include the voltage regulation, the inverters in these units were operating at the unity power factor. When the PV devices started to appear in the transmission networks, the inverters with reactive power capability appeared on the market. [8] Since the power limit of an invertor is based on the maximum total current, the natural shape of the capability curve is similar to a semicircle, and at full capacity the real power always needs to be lowered if the reactive power is to be produced or absorbed. Theoretically the PV generators can be used as STATCOMs, although in practice the solar plants are disconnected at night. [9]

Effects on electricity pricing

For a synchronous generator operating inside its D-curve, the marginal cost of providing reactive power is close to zero. [10] However, once the generator's operating point reaches the corners of the D-curve, increasing the reactive power output will require reduction of the real (active) power. Since the electricity markets payments are typically based on real power, the generating company will have a disincentive to provide more reactive power if requested by the independent system operator. [11] Therefore the reactive power management (voltage control) is separated into an ancillary service with its own tariffs, like the Reactive Supply and Voltage Control from Generation Sources (GSR) in the US. [12]

Related Research Articles

In electrical engineering, the power factor of an AC power system is defined as the ratio of the real power absorbed by the load to the apparent power flowing in the circuit. Real power is the average of the instantaneous product of voltage and current and represents the capacity of the electricity for performing work. Apparent power is the product of RMS current and voltage. Due to energy stored in the load and returned to the source, or due to a non-linear load that distorts the wave shape of the current drawn from the source, the apparent power may be greater than the real power, so more current flows in the circuit than would be required to transfer real power alone. A power factor magnitude of less than one indicates the voltage and current are not in phase, reducing the average product of the two. A negative power factor occurs when the device generates real power, which then flows back towards the source.

<span class="mw-page-title-main">High-voltage direct current</span> Electric power transmission system

A high-voltage direct current (HVDC) electric power transmission system uses direct current (DC) for electric power transmission, in contrast with the more common alternating current (AC) transmission systems.

Distributed generation, also distributed energy, on-site generation (OSG), or district/decentralized energy, is electrical generation and storage performed by a variety of small, grid-connected or distribution system-connected devices referred to as distributed energy resources (DER).

<span class="mw-page-title-main">Utility frequency</span> Frequency used on standard electricity grid in a given area

The utility frequency, (power) line frequency or mains frequency is the nominal frequency of the oscillations of alternating current (AC) in a wide area synchronous grid transmitted from a power station to the end-user. In large parts of the world this is 50 Hz, although in the Americas and parts of Asia it is typically 60 Hz. Current usage by country or region is given in the list of mains electricity by country.

<span class="mw-page-title-main">HVDC converter station</span> Type of substation

An HVDC converter station is a specialised type of substation which forms the terminal equipment for a high-voltage direct current (HVDC) transmission line. It converts direct current to alternating current or the reverse. In addition to the converter, the station usually contains:

A variable-frequency transformer (VFT) is used to transmit electricity between two alternating current frequency domains. The VFT is a relatively recent development. Most asynchronous grid inter-ties use high-voltage direct current converters, while synchronous grid inter-ties are connected by lines and "ordinary" transformers, but without the ability to control power flow between the systems, or with phase-shifting transformer with some flow control.

<span class="mw-page-title-main">Synchronous condenser</span> Machinery used to adjust conditions on the electric power transmission grid

In electrical engineering, a synchronous condenser is a DC-excited synchronous motor, whose shaft is not connected to anything but spins freely. Its purpose is not to convert electric power to mechanical power or vice versa, but to adjust conditions on the electric power transmission grid. Its field is controlled by a voltage regulator to either generate or absorb reactive power as needed to adjust the grid's voltage, or to improve power factor. The condenser’s installation and operation are identical to large electric motors and generators.

<span class="mw-page-title-main">Load bank</span>

A load bank is a piece of electrical test equipment used to simulate an electrical load, to test an electric power source without connecting it to its normal operating load. During testing, adjustment, calibration, or verification procedures, a load bank is connected to the output of a power source, such as an electric generator, battery, servoamplifier or photovoltaic system, in place of its usual load. The load bank presents the source with electrical characteristics similar to its standard operating load, while dissipating the power output that would normally be consumed by it. The power is usually converted to heat by a heavy duty resistor or bank of resistive heating elements in the device, and the heat removed by a forced air or water cooling system. The device usually also includes instruments for metering, load control, and overload protection. Load banks can either be permanently installed at a facility to be connected to a power source when needed, or portable versions can be used for testing power sources such as standby generators and batteries. They are necessary adjuncts to replicate, prove, and verify the real-life demands on critical power systems. They are also used during operation of intermittent renewable power sources such as wind turbines to shed excess power that the electric power grid cannot absorb.

Doubly fed electric machines, also slip-ring generators, are electric motors or electric generators, where both the field magnet windings and armature windings are separately connected to equipment outside the machine.

An induction generator or asynchronous generator is a type of alternating current (AC) electrical generator that uses the principles of induction motors to produce electric power. Induction generators operate by mechanically turning their rotors faster than synchronous speed. A regular AC induction motor usually can be used as a generator, without any internal modifications. Because they can recover energy with relatively simple controls, induction generators are useful in applications such as mini hydro power plants, wind turbines, or in reducing high-pressure gas streams to lower pressure.

<span class="mw-page-title-main">Static synchronous compensator</span>

A static synchronous compensator (STATCOM), is a shunt-connected, reactive compensation device used on transmission networks. It uses power electronics to form a voltage-source converter that can act as either a source or sink of reactive AC power to an electricity network. It is a member of the FACTS family of devices.

In electrical power engineering, fault ride through (FRT), sometimes under-voltage ride through (UVRT), or low voltage ride through (LVRT), is the capability of electric generators to stay connected in short periods of lower electric network voltage. It is needed at distribution level to prevent a short circuit at HV or EHV level from causing a widespread loss of generation. Similar requirements for critical loads such as computer systems and industrial processes are often handled through the use of an uninterruptible power supply (UPS) or capacitor bank to supply make-up power during these events.

Dynamic voltage restoration (DVR) is a method of overcoming voltage sags and swells that occur in electrical power distribution. These are a problem because spikes consume power and sags reduce efficiency of some devices. DVR saves energy through voltage injections that can affect the phase and wave-shape of the power being supplied.

Ancillary services are the services necessary to support the transmission of electric power from generators to consumers given the obligations of control areas and transmission utilities within those control areas to maintain reliable operations of the interconnected transmission system.

<span class="mw-page-title-main">Copper in renewable energy</span> The use of copper in renewable energy

Renewable energy sources such as solar, wind, tidal, hydro, biomass, and geothermal have become significant sectors of the energy market. The rapid growth of these sources in the 21st century has been prompted by increasing costs of fossil fuels as well as their environmental impact issues that significantly lowered their use.

<span class="mw-page-title-main">Variable speed wind turbine</span> Type of wind turbine

A variable speed wind turbine is one which is specifically designed to operate over a wide range of rotor speeds. It is in direct contrast to fixed speed wind turbine where the rotor speed is approximately constant. The reason to vary the rotor speed is to capture the maximum aerodynamic power in the wind, as the wind speed varies. The aerodynamic efficiency, or coefficient of power, for a fixed blade pitch angle is obtained by operating the wind turbine at the optimal tip-speed ratio as shown in the following graph.

<span class="mw-page-title-main">Synchronverter</span> Type of electrical power inverter

Synchronverters or virtual synchronous generators are inverters which mimic synchronous generators (SG) to provide "synthetic inertia" for ancillary services in electric power systems. Inertia is a property of standard synchronous generators associated with the rotating physical mass of the system spinning at a frequency proportional to the electricity being generated. Inertia has implications towards grid stability as work is required to alter the kinetic energy of the spinning physical mass and therefore opposes changes in grid frequency. Inverter-based generation inherently lacks this property as the waveform is being created artificially via power electronics.

Voltage control and reactive power management are two facets of an ancillary service that enables reliability of the transmission networks and facilitates the electricity market on these networks. Both aspects of this activity are intertwined, so within this article the term voltage control will be primarily used to designate this essentially single activity, as suggested by Kirby & Hirst (1997). Voltage control does not include reactive power injections within one AC cycle; these are a part of a separate ancillary service, so-called system stability service. The transmission of reactive power is limited by its nature, so the voltage control is provided through pieces of equipment distributed throughout the power grid, unlike the frequency control that is based on maintaining the overall active power balance in the system.

An inverter-based resource (IBR) is a source of electricity that is asynchronously connected to the electrical grid via an electronic power converter ("inverter"). The devices in this category, also known as converter interfaced generation (CIG), include the variable renewable energy generators and battery storage power stations. These devices lack the intrinsic behaviors and their features are almost entirely defined by the control algorithms, presenting specific challenges to system stability as their penetration increases, for example, a single software fault can affect all devices of a certain type in a contingency. IBRs are sometimes called non-synchronous generators. The design of inverters for the IBR generally follows the IEEE 1547 and NERC PRC-024-2 standards.

In an electrical grid, the short circuit ratio is the ratio of the short circuit apparent power (SCMVA) in the case of a line-line-line-ground (3LG) fault at the location in the grid where some generator is connected to the power rating of the generator itself (GMW). Since the power that can be delivered by the grid varies by location, frequently a location is indicated, for example, at the point of interconnection (POI):

References

Sources