Extra-low voltage

Last updated
Low voltage installations for low voltage devices Extra low voltages (third safety class).JPG
Low voltage installations for low voltage devices
IEC voltage rangeAC RMS
voltage
(V)
DC voltage (V)Defining risk
High voltage > 1,000> 1,500 Electrical arcing
Low voltage 50 to 1,000120 to 1,500 Electrical shock
Extra-low voltage < 50< 120 Electrical fire

Extra-low voltage (ELV) is an electricity supply voltage and is a part of the low-voltage band [1] in a range which carries a low risk of dangerous electrical shock. [2] [3] [4] [5] There are various standards that define extra-low voltage. The International Electrotechnical Commission (IEC) and the UK IET (BS 7671:2008) define an ELV device or circuit as one in which the electrical potential between two conductors or between an electrical conductor and Earth (ground) does not exceed 120 volts (V) for ripple-free direct current (DC) or 50 V RMS (root mean square volts) for alternating current (AC).

Contents

The IEC and IET go on to define actual types of extra-low voltage systems, for example separated extra-low voltage (SELV), protected extra-low voltage (PELV), functional extra-low voltage (FELV). These can be supplied using sources including motor / fossil fuel generator sets, transformers, switched PSU's or rechargeable battery. SELV, PELV, FELV, are distinguished by various safety properties, supply characteristics and design voltages.

Some types of landscape lighting use SELV / PELV (extra-low voltage) systems. Modern battery operated hand tools fall in the SELV category. In more arduous conditions, 25 VRMS alternating current or 60 V (ripple-free) DC can be specified to further reduce hazard. Lower voltage can apply in wet or conductive conditions where there is even greater potential for electric shock. These systems should still fall under the SELV / PELV (ELV) safety specifications.

Types

Separated or safety extra-low voltage (SELV)

IEC defines a SELV system as "an electrical system in which the voltage cannot exceed ELV under normal conditions, and under single-fault conditions, including earth faults in other circuits". The acronym may variously stand for safety extra-low voltage or separated extra-low voltage. It is generally accepted that the acronym: BS EN 60335 and the IEC refer to it as safety extra-low voltage, while separated extra-low voltage (separated from earth) is used and defined in installation standards (e.g. BS 7671). [6]

A SELV circuit must have:

The safety of a SELV circuit is provided by

The design of a SELV circuit typically involves an isolating transformer, guaranteed minimum distances between conductors and electrical insulation barriers. The electrical connectors of SELV circuits should be designed such that they do not mate with connectors commonly used for non-SELV circuits.

Typical examples for a SELV circuit: decorative out-door lighting, Class III battery charger, fed from a Class II power supply. Modern cordless hand tools are considered SELV equipment.

Protected extra-low voltage (PELV)

IEC 61140 defines a PELV system as "an electrical system in which the voltage cannot exceed ELV under normal conditions, and under single-fault conditions, except earth faults in other circuits".

A PELV circuit only requires protective-separation from all circuits other than SELV and PELV (i.e., all circuits that might carry higher voltages), but it may have connections to other PELV systems and earth (ground).

In contrast to a SELV circuit, a PELV circuit can have a protective earth (ground) connection. A PELV circuit, just as with SELV, requires a design that guarantees a low risk of accidental contact with a higher voltage. For a transformer, this can mean that the primary and secondary windings must be separated by reinforced insulation, or by a conductive shield with a protective earth connection, or that the secondary winding itself has an earthed terminal, so that any primary to secondary fault will cause automatic disconnection. (The principle of double fault to danger requires either basic and additional insulation to fail or basic insulation and the connection to the protective earth to fail simultaneously before danger arises.)

A typical example for a PELV circuit is a metal cased computer with a Class I power supply.

Functional extra-low voltage (FELV)

The term functional extra-low voltage (FELV) describes any other extra-low-voltage circuit that does not fulfill the requirements for an SELV or PELV circuit. Although the FELV part of a circuit uses an extra-low voltage, it is not adequately protected from accidental contact with higher voltages in other parts of the circuit. Therefore, the protection requirements for the higher voltage have to be applied to the entire circuit.

Examples for FELV circuits include those that generate an extra low voltage through a semiconductor device or a potentiometer or an autotransformer. A typical example is an electronically controlled toaster where the electronic timer circuit runs off an extra low voltage derived from a tap on the heating element. Another might be ELV signalling between mains powered smoke alarms, with the signalling voltage referred to supply neutral. In such cases the extra low voltage parts must be enclosed or insulated as to the standard of the mains voltage.

UK Reduced low voltage (RLV)

The IET / BSI (BS 7671) also define Reduced Low Voltage (RLV) which can be either single-phase or three-phase AC This system has been used for many years on construction sites, in both single- and three-phase configurations. The single-phase voltage is 110 V a.c. though having a "centre tapped Earth" reducing the voltage to earth to 55 V AC. The three-phase system is 110 V phase-to-phase and 63 V to neutral / earth. This system voltage is slightly above the ELV limit, but is still very commonly used for cord-powered hand tools and temporary lighting in hazardous areas. As it is transformer-derived, the exposed voltage during an earth fault is depressed below the ELV level.

Stand-alone power systems

Cabling for ELV systems, such as in remote-area power systems (RAPS), is designed to minimise energy losses while maximising safety. Lower voltages require a higher current for the same power. The higher current results in greater resistive losses in the cabling. Cable sizing must therefore consider maximum demand, voltage drop over the cable, and current-carrying capacity. Voltage drop is usually the main factor considered, but current-carrying capacity is as important when considering short, high-current runs such as between a battery bank and inverter.

Arcing is a risk in DC ELV systems, and some fuse types which can cause undesired arcing include semi-enclosed, rewireable and automotive fuse types. Instead, high rupturing capacity fuses and appropriately rated circuit breakers are the recommended type for RAPS. Cable termination and connections must be done properly to avoid arcing also, and soldering is not recommended.

Regulations

Precise definitions of "extra low voltage" are given in applicable wiring regulations in a region.

European Union

According to DIN EN 61140:2016 chapter 4.2 Table 1 (German version of EU standard EN 61140), Extra Low Voltage (≤ 50 V a.c. or ≤ 120 V d.c.) is defined as a sub-category of Low voltage (≤ 1000 V a.c. or ≤ 1500 V d.c.). This is similar to the definition provided in IEC 61140:2016. [7]

The European Union directives on the other hand do not define extra-low voltage. The nearest they get to this concept is in the Low Voltage Directive (2014/35/EU), [8] which applies to the range between 50 V AC / 75 V DC and 1,000 V AC / 1,500 V DC. The General Product Safety Directive (2001/95/EC) covers consumer goods with a voltage below 50 V for alternating current, or below 75 V for direct current. [8] The directive only covers electrical equipment and not voltages appearing inside equipment or voltages in electrical components.

IEC

IEC 61140:2016, Basic safety publication defines ELV as ≤ 50 VRMS AC and ≤ 120 V DC ripple-free.

IEC 60364-4-41:2017, Group safety publication defines ELV as ≤ 50 VRMS AC and ≤ 120 V DC ripple-free.

Australia and New Zealand

AS/NZS 3000 Wiring Rules define "extra low voltage" as "Not exceeding 50 V AC or 120 V ripple-free DC" However, AS/ACIF S009 Clause 3.1.78.1 Extra-Low Voltage (ELV)states: "a voltage not exceeding 42.4 V peak or 60 V DC [AS/NZS 60950.1:2003]" and adds a note: "This definition differs from the ELV definition contained in AS/NZS 3000:2000" which is more closely aligned to the Telecommunications Network Voltage (TNV) limits ... i.e. 120 V DC or 70.7 V AC peak (50 VRMS AC)" which accommodates telephone ringing voltage on the nominally 48 V DC battery supply which could be encountered on a telephone line and was not considered hazardous, whereas 120 V AC without current limiting at its source can inject 115mA into individuals leading to fibrillation of the heart.

Brazil

In Brazil, ELV (Extra-baixa tensão or EBT in Portuguese) is officially defined in Regulatory Standard no. 10 from the Brazilian Ministry of Labor and Employment as any voltage "not exceeding 50 volts a.c. or 120 volts d.c.". [9] Although that standard defines safety rules for electricity, the Regulatory Standard no. 12 requires an even lower voltage for start and stop devices on machines and equipment made from March 2012 and on, stating it shall not exceed 25 volts AC or 60 volts DC [10]

Related Research Articles

<span class="mw-page-title-main">Ground (electricity)</span> Reference point in an electrical circuit from which voltages are measured

In electrical engineering, ground or earth may be a reference point in an electrical circuit from which voltages are measured, a common return path for electric current, or a direct physical connection to the Earth.

<span class="mw-page-title-main">Electrical injury</span> Physiological reaction or injury caused by electric current

An electrical injury, or electrical shock is damage sustained to the skin or internal organs on direct contact with an electric current.

<span class="mw-page-title-main">Circuit breaker</span> Automatic circuit protection device

A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by current in excess of that which the equipment can safely carry (overcurrent). Its basic function is to interrupt current flow to protect equipment and to prevent fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.

<span class="mw-page-title-main">Surge protector</span> Protects electrical devices from voltage spikes

A surge protector (or spike suppressor, surge suppressor, surge diverter, surge protection device (SPD), transient voltage suppressor(TVS) or transient voltage surge suppressor (TVSS)) is an appliance or device intended to protect electrical devices in alternating current (AC) circuits from voltage spikes with very short duration measured in microseconds, which can arise from a variety of causes including lightning strikes in the vicinity.

Appliance classes specify measures to prevent dangerous contact voltages on unenergized parts, such as the metallic casing, of an electronic device. In the electrical appliance manufacturing industry, the following appliance classes are defined in IEC 61140 and used to differentiate between the protective-earth connection requirements of devices.

<span class="mw-page-title-main">Ground and neutral</span> In mains electricity, part of a circuit connected to ground or earth

In electrical engineering, ground and neutral are circuit conductors used in alternating current (AC) electrical systems. The neutral conductor receives and returns alternating current to the supply during normal operation of the circuit; to limit the effects of leakage current from higher-voltage systems, the neutral conductor is often connected to earth ground at the point of supply. By contrast, a ground conductor is not intended to carry current for normal operation, but instead connects exposed metallic components to earth ground. A ground conductor only carries significant current if there is a circuit fault that would otherwise energize exposed conductive parts and present a shock hazard. In that case, circuit protection devices may detect a fault to a grounded metal enclosure and automatically de-energize the circuit, or may provide a warning of a ground fault.

Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.

The prospective short-circuit current (PSCC), available fault current, or short-circuit making current is the highest electric current which can exist in a particular electrical system under short-circuit conditions. It is determined by the voltage and impedance of the supply system. It is of the order of a few thousand amperes for a standard domestic mains electrical installation, but may be as low as a few milliamperes in a separated extra-low voltage (SELV) system or as high as hundreds of thousands of amps in large industrial power systems. The term is used in electrical engineering rather than electronics.

<span class="mw-page-title-main">High voltage</span> Electrical potential that is large enough to cause damage or injury

High voltage electricity refers to electrical potential large enough to cause injury or damage. In certain industries, high voltage refers to voltage above a certain threshold. Equipment and conductors that carry high voltage warrant special safety requirements and procedures.

<span class="mw-page-title-main">Current transformer</span> Transformer used to scale alternating current, used as sensor for AC power

A current transformer (CT) is a type of transformer that reduces or multiplies alternating current (AC), producing a current in its secondary which is proportional to the current in its primary.

IEC 60364Electrical Installations for Buildings is the International Electrotechnical Commission (IEC)'s international standard on electrical installations of buildings. This standard is an attempt to harmonize national wiring standards in an IEC standard and is published in the European Union by CENELEC as "HD 60364". The latest versions of many European wiring regulations follow the section structure of IEC 60364 very closely, but contain additional language to cater for historic national practice and to simplify field use and determination of compliance by electricians and inspectors. National codes and site guides are meant to attain the common objectives of IEC 60364, and provide rules in a form that allows for guidance of persons installing and inspecting electrical systems.

<span class="mw-page-title-main">Capacitor types</span> Manufacturing styles of an electronic device

Capacitors are manufactured in many styles, forms, dimensions, and from a large variety of materials. They all contain at least two electrical conductors, called plates, separated by an insulating layer (dielectric). Capacitors are widely used as parts of electrical circuits in many common electrical devices.

An electrical code is a term for a set of regulations for the design and installation of electrical wiring in a building. The intention of such regulations is to provide standards to ensure electrical wiring systems are safe for people and property, protecting them from electrical shock and fire hazards. They are usually based on a model code produced by a national or international standards organisation.

An insulation monitoring device monitors the ungrounded system between an active phase conductor and earth. It is intended to give an alert or disconnect the power supply when the resistance between the two conductors drops below a set value, usually 50 kΩ. The main advantage is that the ungrounded or floating system allows a continuous operation of important consumers such as medical, chemical, military, etc.

In electrical engineering, low voltage is a relative term, the definition varying by context. Different definitions are used in electric power transmission and distribution, compared with electronics design. Electrical safety codes define "low voltage" circuits that are exempt from the protection required at higher voltages. These definitions vary by country and specific codes or regulations.

<span class="mw-page-title-main">Portable appliance testing</span> Procedure in which electrical appliances are routinely checked for safety

In electrical safety testing, portable appliance testing is a process by which electrical appliances are routinely checked for safety, commonly used in the United Kingdom, Ireland, New Zealand and Australia. The formal term for the process is "in-service inspection & testing of electrical equipment". Testing involves a visual inspection of the equipment and verification that power cables are in good condition. Additionally, other tests may be done when required, such as a verification of earthing (grounding) continuity, a test of the soundness of insulation between the current-carrying parts, and a check for any exposed metal that could be touched. The formal limits for a pass/fail of these electrical tests vary somewhat depending on the category of equipment being tested.

In electrical engineering, electrical safety testing is essential to make sure electrical products and installations are safe. To meet this goal, governments and various technical bodies have developed electrical safety standards. All countries have their own electrical safety standards that must be complied with. To meet to these standards, electrical products and installations must pass electrical safety tests.

<span class="mw-page-title-main">Film capacitor</span> Electrical capacitor with an insulating plastic film as the dielectric

Film capacitors, plastic film capacitors, film dielectric capacitors, or polymer film capacitors, generically called film caps as well as power film capacitors, are electrical capacitors with an insulating plastic film as the dielectric, sometimes combined with paper as carrier of the electrodes.

CEAR namely Central Electricity Authority Regulations, 2010 are regulations framed by Central Electricity Authority of India under the Indian Electricity Act, 2003, to regulate measures relating to safety and electric supply in India.

References

  1. IEC 61140:2016 Chapter 4.2
  2. BS 7671
  3. DIN/VDE 0100-410
  4. IEC 60364-4-41: Low-voltage electrical installations – Part 4-41: Protection for safety – Protection against electric shock.
  5. IEC 61140: Protection against electric shock – Common aspects for installation and equipment.
  6. "IEC 60050 - International Electrotechnical Vocabulary - Details for IEV number 195-06-28: "SELV system"". www.electropedia.org. Retrieved 2024-10-02.
  7. DIN EN 61140:2016 chapter 4.2 Table 1
  8. 1 2 "Low Voltage Directive (LVD) - European Commission". single-market-economy.ec.europa.eu.
  9. "NR-10 atualizada - Glossário" [updated NR-10 - Glossary](PDF). Brazilian Ministry of Labor and Employment Website (in Portuguese). December 7, 2004. Retrieved September 9, 2015.
  10. "NR-12 atualizada - item 12.36" [updated NR-12 - Item 12.36](PDF). Brazilian Ministry of Labor and Employment Website (in Portuguese). June 25, 2015. Retrieved September 9, 2015.