Sound attenuator

Last updated

A sound attenuator, or duct silencer, sound trap, or muffler, is a noise control acoustical treatment of Heating Ventilating and Air-Conditioning (HVAC) ductwork designed to reduce transmission of noise through the ductwork, either from equipment into occupied spaces in a building, or between occupied spaces. [1] [2]

Contents

In its simplest form, a sound attenuator consists of a baffle within the ductwork. These baffles often contain sound-absorbing materials. The physical dimensions and baffle configuration of sound attenuators are selected to attenuate a specific range of frequencies. Unlike conventional internally-lined ductwork, which is only effective at attenuating mid- and high-frequency noise, [3] sound attenuators can achieve broader band attenuation in relatively short lengths. [2] Certain types of sound attenuators are essentially a Helmholtz resonator used as a passive noise-control device.

Configuration

Circular sound attenuator (left of the grille) A Circular Attenuator.jpg
Circular sound attenuator (left of the grille)

Generally, sound attenuators consist of the following elements:

Sound attenuators are available in circular and rectangular form factors. Prefabricated rectangular sound attenuators typically come in 3, 5, 7, or 9-ft lengths. The width and height of the sound attenuators are often determined by the surrounding ductwork, though extended media options are available for improved attenuation. The baffles of rectangular sound attenuators are commonly referred to as splitters, whereas circular sound attenuators contain a bullet-shaped baffle. [7]

Sound attenuators are typically classified as "Low," "Medium," or "High" based on performance characteristics and/or duct velocity. An example classification scheme is listed below.

Sound Attenuator Classification at 1000 ft/min [8]
ShapePressure DropAttenuator Classification
Rectangular<0.10 in. w.g."Low"
Rectangular0.10-0.30 in. w.g."Medium"
Rectangular> 0.30 in. w.g."High"
Cylindrical< 0.03 in w.g."Low"
Cylindrical> 0.03 in w.g."High"

Properties

The acoustical properties of commercially available sound attenuators are tested in accordance with ASTM E477: Standard Test Method for Laboratory Measurements of Acoustical and Airflow Performance of Duct Liner Materials and Prefabricated Silencers. [9] These tests are conducted at NVLAP-accredited facilities and then reported by the manufacturer in marketing or engineering bulletins. Outside of the US, sound attenuators are tested in accordance with British Standard 4718 (legacy) or ISO 7235.

Dynamic insertion loss

The dynamic insertion loss of a sound attenuator is the amount of attenuation, in decibels, provided by the silencer under flow conditions. While flow conditions in typical low velocity duct systems rarely exceed 2000–3000 ft/min, sound attenuators for steam vents must withstand airflow velocities in the 15,000-20,000 ft/min. range. [10] The acoustic performance of a sound attenuator is tested over a range of airflow velocities, and for forward and reverse flow conditions. Forward flow is when the air and sound waves propagate in the same direction. The insertion loss of a silencer is defined as [11]

where:

= Radiated sound power from the duct with the attenuator

= Radiated sound power from the duct without the attenuator

Some manufacturers report the static insertion loss of the silencer, which is typically measured with a loudspeaker in lieu of a fan to represent a zero flow condition. [7] These values can be useful in the design of smoke evacuation systems, where sound attenuators are used to attenuate exterior noise that breaks into the exhaust ductwork.

The insertion loss of a sound attenuator is sometimes referred to as transmission loss.

Regenerated noise

The internal baffles of a sound attenuator constrict airflow, which in turn generates turbulent noise. Noise generated by a sound attenuator is directly related to the airflow velocity at the constriction, and changes proportionally with the face area of the sound attenuator.

The change in generated noise can be expressed as

where:

= The new face area of the sound attenuator

= Reference face area of the sound attenuator

For example, if the attenuator doubles in width, while maintaining a constant airflow velocity, the generated noise will increase by 3 dB. Conversely, if the attenuator shrinks by a factor of 10, while keeping the airflow velocity constant, the generated noise will decrease by 10 dB. Since turbulence generated noise caused by duct fittings changes at a rate of , [12] airflow velocities are a critical component of attenuator sizing.

Regenerated noise should always be reviewed, but it is usually only a concern in very quiet rooms (e.g. concert halls, recording studios, music rehearsal rooms) or when the ductwork velocity is greater than 1500 ft/m. [4]

There is a prediction formula that can be used to estimate duct silencer regenerated noise if no data exists [13] [14]

where:

= sound power level generated by the sound attenuator (dB)

= velocity at the constricted cross-area (ft/min)

= reference velocity (196.8 ft/min)

= number of air passages (number of splitters)

= height or circumference of the sound attenuator (in)

= reference dimension (0.0394 in)

Pressure drop

Similar to other duct fittings, sound attenuators cause pressure drop. Catalog pressure drop values obtained through ASTM E477 assume ideal, laminar airflow, which is not allow always found in field installations. The ASHRAE Handbook provides pressure drop correction factors for different inlet and outlet conditions. [15] These correction factors are used whenever there's a turbulent wake within 3 to 5 duct diameters upstream or downstream of the attenuator. [16]

Where sound attenuator dimensions differ from surrounding duct dimensions, transitions to and from the sound attenuator should be smooth and gradual. Abrupt transitions cause the pressure drop and regenerated noise to significantly increase. [17]

The pressure drop through a sound attenuator is typically higher than the pressure drop for an equivalent length of lined duct. However, significantly longer lengths of lined duct are required to achieve equal attenuation, at which point the pressure drop of large extents of lined duct is significantly greater than incurred through a single sound attenuator. [18]

Friction losses due to dissipative sound attenuators can be expressed as [11]

where:

= ratio of the sound attenuator perimeter and area

= length of the duct

= The friction loss coefficient

= density of air

= passage velocity

The perimeter, area, and length of the sound attenuator are also parameters which affect its pressure drop. [16] Friction loss at the sound attenuator is directly proportional to its noise attenuation performance, whereby greater attenuation usually equates to greater pressure drop.

Design variations

Prefabricated sound attenuators rose to prominence in the late 1950s-early 1960s. [2] Several manufacturers were among the first to produce and test prefabricated sound attenuators: Koppers, [19] [20] Industrial Acoustics Company, [21] Industrial Sound Control, [22] and Elof Hansson. [19]

Though rectangular dissipative attenuators are the most common variant of attenuators used today in architectural acoustics noise control, other design options exist.

Reactive silencers

Reactive silencers are very common in muffler design of automobiles and trucks. [10] Attenuation is primarily achieved through sound reflection, area change, and tuned chambers. [11] The design of reactive silencers from scratch is mathematically intensive, so manufacturers often have a number of prefabricated designs.

Dissipative silencers

Dissipative silencers attenuate sound by transferring sound energy to heat. [10] Dissipative silencers are used when broadband attenuation with low pressure drop is desired. [11] In typical ductwork, high frequencies propagate down the duct as a beam, and minimally interact with the outer, lined edges. Sound attenuators with baffles that break the line of sight or elbow attenuators with a bend provide better high frequency attenuation than conventional lined ductwork. [19] Generally, longer attenuators with thicker baffles will have a greater insertion loss over a wider frequency range. [4]

These types of attenuators are commonly used on air handling units, ducted fan coil units, and at the air intake of compressors, gas turbines, and other ventilated equipment enclosures. [4] [10] On certain air handling unit or fan applications, it is common to use a co-planar silencer—a dissipative silencer that is sized for the fan and mounted directly to the fan outlet. [23] This is a common feature in fan array design.

Crosstalk silencers

Purpose-built sound attenuators to prevent crosstalk between two closed, private spaces. Their design typically incorporates one or more bends to form a "Z" or "U" shape. This bend increases the efficacy of the sound attenuator without significantly increasing its overall length. Crosstalk attenuators are passive devices and should be sized for extremely low pressure drops — typically less than 0.05 inches w.g.

Exhaust registers

In the early 1970s, American SF Products, Inc. created the KGE Exhaust Register, which was an air distribution device with an integral sound attenuator. [24]

Noise control implementation

First, the project noise control engineer (or acoustician), mechanical engineer, and equipment representative select the quietest possible equipment which meets the mechanical requirements and budget constraints of the project. Then, the noise control engineers will typically calculate out the path, without the attenuator first. The required sound attenuator insertion loss is the difference between the calculated path and the target background noise level. [16] If no attenuator selection is feasible, the noise control engineer and mechanical must re-evaluate the path between the equipment and the sound attenuator. When space constraints do not allow for a straight attenuator, an elbow or transitional attenuator can be used. [16]

Duct silencers are prominently featured in systems where fiberglass internal duct liner is prohibited. While fiberglass's contribution to air quality is insignificant, [25] many higher education projects have adopted a limit on internal fiberglass liner. In these situations, the project acoustician must rely on duct silencers as the primary means of fan noise and duct-borne noise attenuation.

Sound attenuators are typically located near ducted mechanical equipment, to attenuate noise which propagates down the duct. This creates a trade-off: the sound attenuator should be located near the fan and yet the air is typically more turbulent closer to fans and dampers. [16] Ideally, sound attenuators should straddle the wall of the mechanical equipment room provided there are no fire dampers. [26] If a sound attenuator is located over occupied space, the noise control engineer should confirm that duct breakout noise is not an issue prior to the attenuator. [23] If there is significant distance between the attenuator and the mechanical room penetration, additional duct cladding (such as external fiberglass blanket or gypsum lagging) may be required to prevent noise from breaking into the duct and bypassing the attenuator. [23]

Sound attenuators can also be used outdoors to quiet cooling towers, air intake of emergency generators, and exhaust fans. [4] Larger equipment will require an array of sound attenuators, otherwise known as an attenuator bank.

See also

Related Research Articles

<span class="mw-page-title-main">Heating, ventilation, and air conditioning</span> Technology of indoor and vehicular environmental comfort

Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.

<span class="mw-page-title-main">Furnace (central heating)</span> Device used for heating buildings

A furnace, referred to as a heater or boiler in British English, is an appliance used to generate heat for all or part of a building. Furnaces are mostly used as a major component of a central heating system. Furnaces are permanently installed to provide heat to an interior space through intermediary fluid movement, which may be air, steam, or hot water. Heating appliances that use steam or hot water as the fluid are normally referred to as a residential steam boilers or residential hot water boilers. The most common fuel source for modern furnaces in North America and much of Europe is natural gas; other common fuel sources include LPG, fuel oil, wood and in rare cases coal. In some areas electrical resistance heating is used, especially where the cost of electricity is low or the primary purpose is for air conditioning. Modern high-efficiency furnaces can be up to 98% efficient and operate without a chimney, with a typical gas furnace being about 80% efficient. Waste gas and heat are mechanically ventilated through either metal flue pipes or polyvinyl chloride (PVC) pipes that can be vented through the side or roof of the structure. Fuel efficiency in a gas furnace is measured in AFUE.

<span class="mw-page-title-main">Blower door</span>

A blower door is a machine used to perform a building air leakage test. It can also be used to measure airflow between building zones, to test ductwork airtightness and to help physically locate air leakage sites in the building envelope.

<span class="mw-page-title-main">Architectural acoustics</span> Science and engineering of achieving a good sound within a building

Architectural acoustics is the science and engineering of achieving a good sound within a building and is a branch of acoustical engineering. The first application of modern scientific methods to architectural acoustics was carried out by the American physicist Wallace Sabine in the Fogg Museum lecture room. He applied his newfound knowledge to the design of Symphony Hall, Boston.

Sound Transmission Class is an integer rating of how well a building partition attenuates airborne sound. In the US, it is widely used to rate interior partitions, ceilings, floors, doors, windows and exterior wall configurations. Outside the US, the ISO Sound Reduction Index (SRI) is used. The STC rating very roughly reflects the decibel reduction of noise that a partition can provide. The STC is useful for evaluating annoyance due to speech sounds, but not music or machinery noise as these sources contain more low frequency energy than speech.

<span class="mw-page-title-main">Air handler</span> Device used to regulate and circulate air as part of an HVAC system

An air handler, or air handling unit, is a device used to regulate and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. An air handler is usually a large metal box containing a blower, furnace or A/C elements, filter racks or chambers, sound attenuators, and dampers. Air handlers usually connect to a ductwork ventilation system that distributes the conditioned air through the building and returns it to the AHU, sometimes exhausting air to the atmosphere and bringing in fresh air. Sometimes AHUs discharge (supply) and admit (return) air directly to and from the space served without ductwork

A diffuser is "a device for reducing the velocity and increasing the static pressure of a fluid passing through a system”. The fluid's static pressure rise as it passes through a duct is commonly referred to as pressure recovery. In contrast, a nozzle is used to increase the discharge velocity and lower the pressure of a fluid passing through it.

<span class="mw-page-title-main">Variable air volume</span> Heating or air-conditioning system

Variable air volume (VAV) is a type of heating, ventilating, and/or air-conditioning (HVAC) system. Unlike constant air volume (CAV) systems, which supply a constant airflow at a variable temperature, VAV systems vary the airflow at a constant or varying temperature. The advantages of VAV systems over constant-volume systems include more precise temperature control, reduced compressor wear, lower energy consumption by system fans, less fan noise, and additional passive dehumidification.

<span class="mw-page-title-main">Duct (flow)</span> Conduit used in heating, ventilation, and air conditioning

Ducts are conduits or passages used in heating, ventilation, and air conditioning (HVAC) to deliver and remove air. The needed airflows include, for example, supply air, return air, and exhaust air. Ducts commonly also deliver ventilation air as part of the supply air. As such, air ducts are one method of ensuring acceptable indoor air quality as well as thermal comfort.

<span class="mw-page-title-main">Acoustic transmission line</span> Acoustic waveguide used to transmit sound

An acoustic transmission line is the use of a long duct, which acts as an acoustic waveguide and is used to produce or transmit sound in an undistorted manner. Technically it is the acoustic analog of the electrical transmission line, typically conceived as a rigid-walled duct or tube, that is long and thin relative to the wavelength of sound present in it.

<span class="mw-page-title-main">Passive ventilation</span> Ventilation without use of mechanical systems

Passive ventilation is the process of supplying air to and removing air from an indoor space without using mechanical systems. It refers to the flow of external air to an indoor space as a result of pressure differences arising from natural forces.

The Air Movement and Control Association International, Inc. (AMCA) is an American trade body that sets standards for Heating, Ventilation and Air Conditioning (HVAC) equipment. It rates fan balance and vibration, aerodynamic performance, air density, speed and efficiency.

<span class="mw-page-title-main">Centrifugal fan</span> Mechanical fan that forces fluid to move radially outward

A centrifugal fan is a mechanical device for moving air or other gases in a direction at an angle to the incoming fluid. Centrifugal fans often contain a ducted housing to direct outgoing air in a specific direction or across a heat sink; such a fan is also called a blower, blower fan, or squirrel-cage fan. Tiny ones used in computers are sometimes called biscuit blowers. These fans move air from the rotating inlet of the fan to an outlet. They are typically used in ducted applications to either draw air through ductwork/heat exchanger, or push air through similar impellers. Compared to standard axial fans, they can provide similar air movement from a smaller fan package, and overcome higher resistance in air streams.

Process duct work conveys large volumes of hot, dusty air from processing equipment to mills, baghouses to other process equipment. Process duct work may be round or rectangular. Although round duct work costs more to fabricate than rectangular duct work, it requires fewer stiffeners and is favored in many applications over rectangular ductwork.

HVAC is a major sub discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary.

<span class="mw-page-title-main">Underfloor air distribution</span>

Underfloor air distribution (UFAD) is an air distribution strategy for providing ventilation and space conditioning in buildings as part of the design of a HVAC system. UFAD systems use an underfloor supply plenum located between the structural concrete slab and a raised floor system to supply conditioned air to supply outlets, located at or near floor level within the occupied space. Air returns from the room at ceiling level or the maximum allowable height above the occupied zone.

<span class="mw-page-title-main">Dedicated outdoor air system</span>

A dedicated outdoor air system (DOAS) is a type of heating, ventilation and air-conditioning (HVAC) system that consists of two parallel systems: a dedicated system for delivering outdoor air ventilation that handles both the latent and sensible loads of conditioning the ventilation air, and a parallel system to handle the loads generated by indoor/process sources and those that pass through the building enclosure.

Airflow, or air flow, is the movement of air. The primary cause of airflow is the existence of air. Air behaves in a fluid manner, meaning particles naturally flow from areas of higher pressure to those where the pressure is lower. Atmospheric air pressure is directly related to altitude, temperature, and composition.

Transmission loss (TL) in duct acoustics describes the acoustic performances of a muffler-like system. It is frequently used in the industry areas such as muffler manufacturers and NVH department of automobile manufacturers, and in academic studies. Generally the higher transmission loss of a system it has, the better it will perform in terms of noise cancellation.

Ductwork airtightness can be defined as the resistance to inward or outward air leakage through the ductwork envelope. This air leakage is driven by differential pressures across the ductwork envelope due to the combined effects of stack and fan operation.

References

  1. ASHRAE Guide and Data Book. 1961. pp. 217–218.
  2. 1 2 3 Doelling, Norman (1961). "Noise Reduction Characteristics of Package Attenuators for Air-Conditioning". ASHRAE Journal. 3 (12).
  3. Albright, Jacob (2015-12-01). Sound Attenuation of Fiberglass Lined Ventilation Ducts. Digital Scholarship@UNLV. OCLC   946287869.
  4. 1 2 3 4 5 Charles M. Salter Associates. (1998). Acoustics : architecture, engineering, the environment. William Stout. ISBN   0-9651144-6-5. OCLC   925548399.
  5. Schaffer, Mark E., 1949- (2011). A practical guide to noise and vibration control for HVAC systems. American Society of Heating, Refrigerating, and Air-Conditioning Engineers. ISBN   978-1-936504-02-2. OCLC   702357408.{{cite book}}: CS1 maint: multiple names: authors list (link)
  6. CUMMINGS, A. (January 2001). "Sound Transmission Through Duct Walls". Journal of Sound and Vibration. 239 (4): 731–765. Bibcode:2001JSV...239..731C. doi:10.1006/jsvi.2000.3226. ISSN   0022-460X. S2CID   17710118.
  7. 1 2 CIBSE. (2016). Noise and Vibration Control for Building Services Systems - CIBSE Guide B4-2016. CIBSE. ISBN   978-1-906846-79-4. OCLC   987013225.
  8. Blazier, Warren; Miller, Nicholas; Towers, David (1981). Development of a mechanical equipment noise-control permit scheme for model building code. Environmental Protection Agency, Office of Noise Abatement and Control.
  9. "ASTM E477 - 13e1 Standard Test Method for Laboratory Measurements of Acoustical and Airflow Performance of Duct Liner Materials and Prefabricated Silencers". www.astm.org. Retrieved 2020-01-11.
  10. 1 2 3 4 Thumann, Albert. (1990). Fundamentals of noise control engineering. Fairmont Press. ISBN   0-88173-091-2. OCLC   301407261.
  11. 1 2 3 4 Vér, I. L. Beranek, Leo L. 1914-2016 (2010). Noise and vibration control engineering : principles and applications. Wiley. ISBN   978-0-471-44942-3. OCLC   1026960754.{{cite book}}: CS1 maint: multiple names: authors list (link)
  12. Reynolds, Douglas D. (1991). Algorithms for HVAC acoustics. American Society of Heating, Regrigerating and Air-conditioning Engineers. ISBN   0-910110-75-1. OCLC   300308745.
  13. Long, Marshall. (2006). Architectural acoustics. Elsevier Academic Press. ISBN   978-0-12-455551-8. OCLC   906254282.
  14. Fry, Alan. (1988). Noise control in building services. Pergamon Press. ISBN   0-08-034067-9. OCLC   924971315.
  15. American Society of Heating, Refrigerating and Air Conditioning Engineers. (2006). ASHRAE handbook. ASHRAE. OCLC   315340946.
  16. 1 2 3 4 5 American Society of Heating, Refrigerating and Air Conditioning Engineers. (2015). ASHRAE handbook. ASHRAE.
  17. Cerami, Vito; Bishop, Edwin (1966). "Control of Duct Generated Noise". Air Conditioning, Heating and Ventilating. September (September): 55–64.
  18. Beranek, Leo L. (Leo Leroy), 1914-2016. (1991) [1988]. Noise reduction. Peninsula Pub. ISBN   0-932146-58-9. OCLC   30656509.{{cite book}}: CS1 maint: multiple names: authors list (link)
  19. 1 2 3 Doelling, Norman (1960). "Noise Reduction Characteristics of Package Attenuators for Air-Conditioning Systems". ASHRAE Journal. 66: 114–128.
  20. Advertisement (1961). "We don't know what noise annoys an oyster...". ASHRAE Journal. March: 23.
  21. Advertisement (1961). "Fan Noise Controlled in Air Handling Systems Quickly & Accurately in less than 5 minutes!". ASHRAE Journal. February: 141.
  22. Farris, R. W.; Young, W. S. Jr. (1955). "All Quiet on the Residential Front?". ASHRAE Journal. March: 36–37.
  23. 1 2 3 Woods, R. I. (1972). Noise control in mechanical services. Sound Attenuators. OCLC   807408333.
  24. American SF Products, Inc. (1972). "Meet the KGE: the first exhaust register designed as a sound trap". ASHRAE Journal. September.
  25. North American Insulation Manufacturers Association. (2002). Fibrous glass duct liner standard : design, fabrication and installation guidelines. NAIMA. OCLC   123444561.
  26. Jones, Robert (2003). "Controlling Noise from HVAC Systems". ASHRAE. September: 28–33.