Electrical contact

Last updated
An electromagnetic relay with a pair of contacts Relay principle vertical.jpg
An electromagnetic relay with a pair of contacts

An electrical contact is an electrical circuit component found in electrical switches, relays, connectors and circuit breakers. [1] Each contact is a piece of electrically conductive material, typically metal. When a pair of contacts touch, they can pass an electrical current with a certain contact resistance, dependent on surface structure, surface chemistry and contact time; [2] when the pair is separated by an insulating gap, then the pair does not pass a current. When the contacts touch, the switch is closed; when the contacts are separated, the switch is open. The gap must be an insulating medium, such as air, vacuum, oil, SF6. Contacts may be operated by humans in push-buttons and switches, by mechanical pressure in sensors or machine cams, and electromechanically in relays. The surfaces where contacts touch are usually composed of metals such as silver or gold alloys [3] [4] that have high electrical conductivity, wear resistance, oxidation resistance and other properties. [5]

Contents

Materials

Contacts can be produced from a wide variety of materials. Typical materials include: [5]


Electrical ratings

Contacts are rated for the current carrying capacity while closed, breaking capacity when opening (due to arcing) and voltage rating. Opening voltage rating may be an AC voltage rating, DC voltage rating or both.[ citation needed ]

Arc suppression

Contacts of a high-voltage switch employing open air as an insulating medium Hochleistungs-Freischalter Typ II.jpg
Contacts of a high-voltage switch employing open air as an insulating medium

When relay contacts open to interrupt a high current with an inductive load, a voltage spike will result, striking an arc across the contacts. If the voltage is high enough, an arc may be struck even without an inductive load. Regardless of how the arc forms, it will persist until the current through the arc falls to the point too low to sustain it. Arcing damages the electrical contacts, and a sustained arc may prevent the open contacts from removing power from the system being controlled. [7]

In AC systems, where the current passes through zero twice for each cycle, all but the most energetic arcs are extinguished at the zero crossing. The problem is more severe with DC where such zero crossings do not occur. This is why contacts rated for one voltage for switching AC frequently have a lower voltage rating for DC. [8]

Electrical contact theory

Ragnar Holm contributed greatly to electrical contact theory and application. [9]

Macroscopically smooth and clean surfaces are microscopically rough and, in air, contaminated with oxides, adsorbed water vapor, and atmospheric contaminants. When two metal electrical contacts touch, the actual metal-to-metal contact area is small compared to the total contact-to-contact area physically touching. In electrical contact theory, the relatively small area where electrical current flows between two contacts is called the a-spot where "a" stands for asperity. If the small a-spot is treated as a circular area and the resistivity of the metal is homogeneous, then the current and voltage in the metal conductor has spherical symmetry and a simple calculation can relate the size of the a-spot to the resistance of the electrical contact interface. If there is metal-to-metal contact between electrical contacts, then the electrical contact resistance, or ECR (as opposed to the bulk resistance of the contact metal) is mostly due to constriction of the current through a very small area, the a-spot. For contact spots of radii smaller than the mean free path of electrons , ballistic conduction of electrons occurs, resulting in a phenomenon known also as Sharvin resistance. [10] Contact force or pressure increases the size of the a-spot which decreases the constriction resistance and the electrical contact resistance. [11] When the size of contacting asperities becomes larger than the mean free path of electrons, Holm-type contacts become the dominant transport mechanism, resulting in a relatively low contact resistance. [2]

Relay contacts

Schematic for an electromechanical relay showing a coil, four pair of normally open and one pair of normally closed contacts Kontakt.svg
Schematic for an electromechanical relay showing a coil, four pair of normally open and one pair of normally closed contacts

The National Association of Relay Manufacturers and its successor, the Relay and Switch Industry Association define 23 distinct forms of electrical contact found in relays and switches. [12]

A normally closed (NC) contact pair is closed (in a conductive state) when it, or the device operating it, is in a deenergized state or relaxed state.

A normally open (NO) contact pair is open (in a non-conductive state) when it, or the device operating it, is in a deenergized state or relaxed state.[ citation needed ]

Contact form

The National Association of Relay Manufacturers and its successor, the Relay and Switch Industry Association define 23 distinct electrical contact forms found in relays and switches. [13] The following contact forms are particularly common:

Form A contacts

Form A contacts ("make contacts") are normally open contacts. The contacts are open when the energizing force (magnet or relay solenoid) is not present. When the energizing force is present, the contact will close. An alternate notation for Form A is SPST-NO. [12]

Form B contacts

Form B contacts ("break contacts") are normally closed contacts. Its operation is logically inverted from Form A. An alternate notation for Form B is SPST-NC. [12]

Form C contacts

A small relay using a Form C contacts Relay2.jpg
A small relay using a Form C contacts

Form C contacts ("change over" or "transfer" contacts) are composed of a normally closed contact pair and a normally open contact pair that are operated by the same device; there is a common electrical connection between a contact of each pair that results in only three connection terminals. These terminals are usually labelled as normally open, common, and normally closed (NO-C-NC). An alternate notation for Form C is SPDT. [12]

These contacts are quite frequently found in electrical switches and relays as the common contact element provides a mechanically economical method of providing a higher contact count. [12]

Form D contacts

Form D contacts ("continuity transfer" contacts) differ from Form C in only one regard, the make-break order during transition. Where Form C guarantees that, briefly, both connections are open, Form D guarantees that, briefly, all three terminals will be connected. This is a relatively uncommon configuration. [12]

Form E contacts

Form E is a combination of form D and B.

Form K contacts

Form K contacts (center-off) differ from Form C in that there is a center-off or normally-open position where neither connection is made. SPDT toggle switches with a center off position are common, but relays with this configuration are relatively rare. [12]

Form X contacts

Toggle switch with one Form X contact. When actuated, the moving contact swings left to bridge the gap between the two fixed contacts. Togglesw2.jpg
Toggle switch with one Form X contact. When actuated, the moving contact swings left to bridge the gap between the two fixed contacts.

Form X or double-make contacts are equivalent to two Form A contacts in series, mechanically linked and operated by a single actuator, and can also be described as SPST-NO contacts. These are commonly found in contactors and in toggle switches designed to handle high power inductive loads. [12]

Form Y contacts

Form Y or double-break contacts are equivalent to two Form B contacts in series, mechanically linked and operated by a single actuator, and can also be described as SPST-NC contacts. [12]

Form Z contacts

Form Z or double-make double-break contacts are comparable to Form C contacts, but they almost always have four external connections, two for the normally open path and two for the normally closed path. As with forms X and Y, both current paths involve two contacts in series, mechanically linked and operated by a single actuator. Again, this is also described as an SPDT contact. [12]

Make-break order

Types of make and break Ueberlappende kontakte en.svg
Types of make and break

Where a switch contains both normally open (NO) and normally closed (NC) contacts, the order in which they make and break may be significant. In most cases, the rule is break-before-make or B-B-M; that is, the NO and NC contacts are never simultaneously closed during the transition between states. This is not always the case, Form C contacts follow this rule, while the otherwise equivalent Form D contacts follow the opposite rule, make before break. The less common configuration, when the NO and NC contacts are simultaneously closed during the transition, is make-before-break or M-B-B.[ citation needed ]

See also

Related Research Articles

<span class="mw-page-title-main">Relay</span> Electrically-operated switch

A relay is an electrically operated switch. It consists of a set of input terminals for a single or multiple control signals, and a set of operating contact terminals. The switch may have any number of contacts in multiple contact forms, such as make contacts, break contacts, or combinations thereof.

In electrical engineering, a switch is an electrical component that can disconnect or connect the conducting path in an electrical circuit, interrupting the electric current or diverting it from one conductor to another. The most common type of switch is an electromechanical device consisting of one or more sets of movable electrical contacts connected to external circuits. When a pair of contacts is touching current can pass between them, while when the contacts are separated no current can flow.

<span class="mw-page-title-main">Mercury switch</span> Type of electrical switch

A mercury switch is an electrical switch that opens and closes a circuit when a small amount of the liquid metal mercury connects metal electrodes to close the circuit. There are several different basic designs but they all share the common design strength of non-eroding switch contacts.

<span class="mw-page-title-main">Reed switch</span> Electrical switch operated by an applied magnetic field

The reed switch is an electromechanical switch operated by an applied magnetic field. It was invented in 1922 by professor Valentin Kovalenkov at the Petrograd Electrotechnical University, and later evolved at Bell Telephone Laboratories in 1936 by Walter B. Ellwood into the reed relay. In its simplest and most common form, it consists of a pair of ferromagnetic flexible metal contacts in a hermetically sealed glass envelope. The contacts are usually normally open, closing when a magnetic field is present, or they may be normally closed and open when a magnetic field is applied. The switch may be actuated by an electromagnetic coil, making a reed relay, or by bringing a permanent magnet near it. When the magnetic field is removed, the contacts in the reed switch return to their original position. The "reed" is the metal part inside the reed switch envelope that is relatively thin and wide to make it flexible, resembling the reed of a musical instrument. The term "reed" may also include the external wire lead as well as the internal part.

A snubber is a device used to suppress a phenomenon such as voltage transients in electrical systems, pressure transients in fluid systems or excess force or rapid movement in mechanical systems.

<span class="mw-page-title-main">Electric arc</span> Electrical breakdown of a gas that results in an ongoing electrical discharge

An electric arc is an electrical breakdown of a gas that produces a prolonged electrical discharge. The current through a normally nonconductive medium such as air produces a plasma, which may produce visible light. An arc discharge is initiated either by thermionic emission or by field emission. After initiation, the arc relies on thermionic emission of electrons from the electrodes supporting the arc. An arc discharge is characterized by a lower voltage than a glow discharge. An archaic term is voltaic arc, as used in the phrase "voltaic arc lamp".

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

<span class="mw-page-title-main">Electronic component</span> Discrete device in an electronic system

An electronic component is any basic discrete electronic device or physical entity part of an electronic system used to affect electrons or their associated fields. Electronic components are mostly industrial products, available in a singular form and are not to be confused with electrical elements, which are conceptual abstractions representing idealized electronic components and elements. A datasheet for an electronic component is a technical document that provides detailed information about the component's specifications, characteristics, and performance.

<span class="mw-page-title-main">Contactor</span> Electronic circuit element serving as a switch

A contactor is an electrically controlled switch used for switching an electrical power circuit. A contactor is typically controlled by a circuit which has a much lower power level than the switched circuit, such as a 24-volt coil electromagnet controlling a 230-volt motor switch.

<span class="mw-page-title-main">Electronic symbol</span> Pictogram used to represent various electrical and electronic devices or functions

An electronic symbol is a pictogram used to represent various electrical and electronic devices or functions, such as wires, batteries, resistors, and transistors, in a schematic diagram of an electrical or electronic circuit. These symbols are largely standardized internationally today, but may vary from country to country, or engineering discipline, based on traditional conventions.

A zone valve is a specific type of valve used to control the flow of water or steam in a hydronic heating or cooling system.

<span class="mw-page-title-main">Arc flash</span> Heat and light produced during an electrical arc fault

An arc flash is the light and heat produced as part of an arc fault, a type of electrical explosion or discharge that results from a connection through air to ground or another voltage phase in an electrical system.

Electrical contact resistance is resistance to the flow of electric current caused by incomplete contact of the surfaces through which the current is flowing, and by films or oxide layers on the contacting surfaces. It occurs at electrical connections such as switches, connectors, breakers, contacts, and measurement probes. Contact resistance values are typically small.

<span class="mw-page-title-main">Flyback diode</span> Voltage-spike stopping diode across an inductor

A flyback diode is any diode connected across an inductor used to eliminate flyback, which is the sudden voltage spike seen across an inductive load when its supply current is suddenly reduced or interrupted. It is used in circuits in which inductive loads are controlled by switches, and in switching power supplies and inverters.

In building wiring, multiway switching is the interconnection of two or more electrical switches to control an electrical load from more than one location. A common application is in lighting, where it allows the control of lamps from multiple locations, for example in a hallway, stairwell, or large room.

<span class="mw-page-title-main">Failure of electronic components</span> Ways electronic components fail and prevention measures

Electronic components have a wide range of failure modes. These can be classified in various ways, such as by time or cause. Failures can be caused by excess temperature, excess current or voltage, ionizing radiation, mechanical shock, stress or impact, and many other causes. In semiconductor devices, problems in the device package may cause failures due to contamination, mechanical stress of the device, or open or short circuits.

Automatic test system switching test equipment allows for high-speed testing of a device or devices in a test situation, where strict sequences and combinations of switching must be observed. By automating the process in this way, the possibility of test errors and inaccuracies is minimized, and only systematic errors would generally be encountered due to such as an incorrect programmed test condition. This eliminates error due to human factors and allows application of a standard test sequence repetitively. The design of a test system’s switching configuration is governed by the test specification, which is derived from the functional tests to be performed.

Arc suppression is the reduction of the electric arc energy that occurs when current-carrying contacts are opened and closed. An electric arc is a man-made, continuous arc-discharge consisting of highly energized electrons and ions supported by an electric current of at least 100mA; not to be confused with an electric spark.

Contact protection methods are designed to mitigate the wear and degradation occurring during the normal use of contacts within an electromechanical switch, relay or contactor and thus avoid an excessive increase in contact resistance or switch failure.

In electrical and electronics engineering, wetting current is the minimum electric current needing to flow through a contact to break through the surface film resistance at a contact. It is typically far below the contact's nominal maximum current rating.

References

  1. Relay Basics; Omron.
  2. 1 2 Zhai, C.; Hanaor, D.; Proust, G.; Gan, Y. (2015). "Stress-Dependent Electrical Contact Resistance at Fractal Rough Surfaces" (PDF). Journal of Engineering Mechanics. 143 (3): B4015001. doi:10.1061/(ASCE)EM.1943-7889.0000967.
  3. Matsushita Electronics, "Relay Techninal Information: Definition of Relay Terminology", § Contact, http://media.digikey.com/pdf/other%20related%20documents/panasonic%20other%20doc/small%20signal%20relay%20techincal%20info.pdf
  4. "Mech Eng Term" (PDF). Panasonic.biz.
  5. 1 2 "Electrical Contact Materials". PEP Brainin. 2013-12-13. Retrieved 2017-03-04.
  6. Beurskens, Jack. "Contacts - Shin-Etsu Polymer Europe B.V." www.shinetsu.info. Retrieved 2017-03-04.
  7. "Contact Arc Phenomenon" (PDF). PickerComponents.com. Picker Components.
  8. Chapter 4, Volume IV, Lessons in Electric Circuits, EETech Media, retrieved June 2017.
  9. "IEEE Holm Conferences on Electrical Contacts". ieee-holm.org. Retrieved 2017-03-04.
  10. Zhai, C; et al. (2016). "Interfacial electro-mechanical behaviour at rough surfaces" (PDF). Extreme Mechanics Letters. 9: 422–429. doi:10.1016/j.eml.2016.03.021.
  11. Holm, Ragnar (1999). Electric Contacts: Theory and Applications (4th ed.). Springer. ISBN   978-3540038757.
  12. 1 2 3 4 5 6 7 8 9 10 Section 1.6, Engineers' Relay Handbook, 5th ed, Relay and Switch Industry Association, Arlington, VA; 3rd ed, National Association of Relay Manufacturers, Elkhart Ind., 1980; 2nd Ed. Hayden, New York, 1966; large parts of the 5th edition are on line here Archived 2017-07-05 at the Wayback Machine .
  13. Section 1.6, Engineers' Relay Handbook, 5th ed, Relay and Switch Industry Association, Arlington, VA; 3rd ed, National Association of Relay Manufacturers, Elkhart Ind., 1980; 2nd Ed. Hayden, New York, 1966; large parts of the 5th edition are on line here Archived 2017-07-05 at the Wayback Machine .

Further reading