Wet oxidation

Last updated

Wet oxidation is a form of hydrothermal treatment. It is the oxidation of dissolved or suspended components in water using oxygen as the oxidizer. It is referred to as "Wet Air Oxidation" (WAO) when air is used. The oxidation reactions occur in superheated water at a temperature above the normal boiling point of water (100 °C), but below the critical point (374 °C).

Contents

The system must be maintained under pressure to avoid excessive evaporation of water. This is done to control energy consumption due to the latent heat of vaporization. It is also done because liquid water is necessary for most of the oxidation reactions to occur. Compounds oxidize under wet oxidation conditions that would not oxidize under dry conditions at the same temperature and pressure.

Wet oxidation has been used commercially for around 60 years. It is used predominantly for treating wastewater. It is often referred to as Zimpro (from ZIMmerman PROcess), after Fred J. Zimmermann who commercialized it in the mid 20th century. [1]

System Description

Commercial systems typically use a bubble column reactor, where air is bubbled through a vertical column that is liquid full of the hot and pressurized wastewater. Fresh wastewater enters the bottom of the column and oxidized wastewater exits the top. The heat released during the oxidation is used to maintain the operating temperature.

WAO is a liquid phase reaction using dissolved oxygen in water to oxidize wastewater contaminants. The dissolved oxygen is typically supplied using pressurized air, but pure oxygen can also be used. The oxidation reaction generally occurs at moderate temperatures of 150°-320 °C and at pressures from 10 to 220 bar. The process converts organic contaminants to carbon dioxide, water, and biodegradable short chain organic acids. Inorganic constituents such as sulfides and cyanides are converted to non-reactive inorganic compounds.

In the WAO reaction, complex organic molecules, including biological refractory compounds, are broken into simpler organic compounds or to a complete mineralized state (CO2, NH3, Cl, SO4−2, PO4−3). Simple organic compounds such as low molecular weight carboxylic acids and mineralized reaction products may be present in the WAO effluents. Because of this, the WAO effluent generally requires post treatment prior to discharge. WAO effluents are typically readily biodegradable and exhibit high values for BOD:COD ratios. Standard treatment techniques such as activated sludge biotreatment are typically used with WAO for complete treatment. [2]

Catalyst can be used in the WAO system to enhance treatment and achieve a higher COD destruction. Heterogeneous and homogenous catalysts have been used. Heterogeneous catalysts are based on precious metals deposited on a stable substrate. Homogenous catalysts are dissolved transition metals. Several processes, such as Ciba-Geigy, LOPROX, and ATHOS utilize a homogenous catalyst. [3] [4] Mixed metal catalysts, such a Ce/Mn, Co/Ce, Ag/Ce, have also been effective in improving the treatment achieved in a WAO system. [5]

A special type of wet oxidation process was the so-called "VerTech process" system. A system of this type operated in Apeldoorn, Netherlands between 1994 and 2004. The system was installed in a below-ground pressure vessel (also called a gravity pressure vessel or GPV). The pressure was supplied by feeding the material to a reactor with a depth of 1,200 metres (3,900 ft). The deep shaft reactor also served as a heat exchanger, so no pre-heating was required. The operating temperature was about 270 °C with a pressure of about 100 bars (1,500 psi). The installation was eventually shut down due to operational problems. [6] [7]

Commercial Applications

Spent Caustic Treatment

The majority of commercial wet oxidation systems are used to treat industrial wastewater, such as sulfide laden spent caustic streams from ethylene and LPG production as well as naphthenic and cresylic spent caustics from refinery applications.

ClassificationTemperature

(Pressure)

Treatment of Compounds
Low110-150 °C

(2-10 bar)

Reactive Sulfides
Mid200-220 °C

(20-45 bar)

Sulfides, Mercaptans
High240-260 °C

(45-100 bar)

Naphthenic and Cresylic Acids, Sulfides, Mercaptans

Typical classification of WAO treatment systems. [8]

Low temperature WAO systems oxidize sulfides to thiosulfate and sulfate but high concentrations of thiosulfate are present in the treated effluent. The mid temperature systems fully oxidize sulfides to sulfate and mercaptans are oxidized to sulfonic acids. For sulfidic spent caustics, this results in a high chemical oxygen demand (COD) destruction (>90%). High temperature systems are used to oxidize organic compounds that are present in naphthenic and cresylic spent caustics.

Sewage Sludge Treatment

Almost as many systems are also used for treating biosolids, in order to pasteurize and to decrease volume of material for disposal. The thermal conditioning occurs at temperatures of 210 – 240 °C. A 4% dry solid slurry can be processed in a WAO system where it is disinfected and the treated effluent can be dewatered to 55% dry solids using a filter press. [4]

Other Applications

Wet air oxidation has also been used to treat a variety of other industrial process waters and wastewaters which include:

· Hazardous Waste [9]

· Kinetic Hydrate Inhibitors (KHI) from produced water [10]

· Polyol ether/styrene monomer (POSM) wastewater [11]

· Ammonium sulfate crystallizer mother liquor [11]

· Pharmaceutical wastewater [11]

· Cyanide Wastewater [11]

· Powdered Activated Carbon regeneration [11]

See also

Related Research Articles

<span class="mw-page-title-main">Supercritical water oxidation</span>

Supercritical water oxidation (SCWO) is a process that occurs in water at temperatures and pressures above a mixture's thermodynamic critical point. Under these conditions water becomes a fluid with unique properties that can be used to advantage in the destruction of recalcitrant and hazardous wastes such as polychlorinated biphenyls (PCB) or Per- and polyfluoroalkyl substances (PFASs). Supercritical water has a density between that of water vapor and liquid at standard conditions, and exhibits high gas-like diffusion rates along with high liquid-like collision rates. In addition, the behavior of water as a solvent is altered - it behaves much less like a polar solvent. As a result, the solubility behavior is "reversed" so that oxygen, and organics such as chlorinated hydrocarbons become soluble in the water, allowing single-phase reaction of aqueous waste with a dissolved oxidizer. The reversed solubility also causes salts to precipitate out of solution, meaning they can be treated using conventional methods for solid-waste residuals. Efficient oxidation reactions occur at low temperature with reduced NOx production.

<span class="mw-page-title-main">Wastewater treatment</span> Converting wastewater into an effluent for return to the water cycle

Wastewater treatment is a process used to remove contaminants from wastewater and convert it into an effluent that can be returned to the water cycle. Once returned to the water cycle, the effluent creates an acceptable impact on the environment or is reused for various purposes. The treatment process takes place in a wastewater treatment plant. There are several kinds of wastewater which are treated at the appropriate type of wastewater treatment plant. For domestic wastewater, the treatment plant is called a sewage treatment plant. For industrial wastewater, treatment either takes place in a separate industrial wastewater treatment plant, or in a sewage treatment plant. Further types of wastewater treatment plants include agricultural wastewater treatment plants and leachate treatment plants.

<span class="mw-page-title-main">Waste stabilization pond</span> Ponds designed and built for wastewater treatment

Waste stabilization ponds are ponds designed and built for wastewater treatment to reduce the organic content and remove pathogens from wastewater. They are man-made depressions confined by earthen structures. Wastewater or "influent" enters on one side of the waste stabilization pond and exits on the other side as "effluent", after spending several days in the pond, during which treatment processes take place.

<span class="mw-page-title-main">Activated sludge</span> Wastewater treatment process using aeration and a biological floc

The activated sludgeprocess is a type of biological wastewater treatment process for treating sewage or industrial wastewaters using aeration and a biological floc composed of bacteria and protozoa. It uses air and microorganisms to biologically oxidize organic pollutants, producing a waste sludge containing the oxidized material.

<span class="mw-page-title-main">Industrial wastewater treatment</span> Processes used for treating wastewater that is produced by industries as an undesirable by-product

Industrial wastewater treatment describes the processes used for treating wastewater that is produced by industries as an undesirable by-product. After treatment, the treated industrial wastewater may be reused or released to a sanitary sewer or to a surface water in the environment. Some industrial facilities generate wastewater that can be treated in sewage treatment plants. Most industrial processes, such as petroleum refineries, chemical and petrochemical plants have their own specialized facilities to treat their wastewaters so that the pollutant concentrations in the treated wastewater comply with the regulations regarding disposal of wastewaters into sewers or into rivers, lakes or oceans. This applies to industries that generate wastewater with high concentrations of organic matter, toxic pollutants or nutrients such as ammonia. Some industries install a pre-treatment system to remove some pollutants, and then discharge the partially treated wastewater to the municipal sewer system.

An aerated lagoon is a simple wastewater treatment system consisting of a pond with artificial aeration to promote the biological oxidation of wastewaters.

Fenton's reagent is a solution of hydrogen peroxide (H2O2) with ferrous iron (typically iron(II) sulfate, FeSO4) as a catalyst that is used to oxidize contaminants or waste waters as part of an advanced oxidation process. Fenton's reagent can be used to destroy organic compounds such as trichloroethylene (TCE) and tetrachloroethylene (perchloroethylene, PCE). It was developed in the 1890s by Henry John Horstman Fenton as an analytical reagent.

<span class="mw-page-title-main">Total organic carbon</span>

Total organic carbon (TOC) is the amount of carbon found in an organic compound and is often used as a non-specific indicator of water quality or cleanliness of pharmaceutical manufacturing equipment. TOC may also refer to the amount of organic carbon in soil, or in a geological formation, particularly the source rock for a petroleum play; 2% is a rough minimum. For marine surface sediments average TOC content is 0.5% in the deep ocean, and 2% along the eastern margins.

Electrocoagulation (EC) is a technique used for wastewater treatment, wash water treatment, industrially processed water, and medical treatment. Electrocoagulation has become a rapidly growing area of wastewater treatment due to its ability to remove contaminants that are generally more difficult to remove by filtration or chemical treatment systems, such as emulsified oil, total petroleum hydrocarbons, refractory organics, suspended solids, and heavy metals. There are many brands of electrocoagulation devices available and they can range in complexity from a simple anode and cathode to much more complex devices with control over electrode potentials, passivation, anode consumption, cell REDOX potentials as well as the introduction of ultrasonic sound, ultraviolet light and a range of gases and reactants to achieve so-called Advanced Oxidation Processes for refractory or recalcitrant organic substances.

<span class="mw-page-title-main">Wastewater quality indicators</span> Ways to test the suitability of wastewater

Wastewater quality indicators are laboratory test methodologies to assess suitability of wastewater for disposal, treatment or reuse. The main parameters in sewage that are measured to assess the sewage strength or quality as well as treatment options include: solids, indicators of organic matter, nitrogen, phosphorus, indicators of fecal contamination. Tests selected vary with the intended use or discharge location. Tests can measure physical, chemical, and biological characteristics of the wastewater. Physical characteristics include temperature and solids. Chemical characteristics include pH value, dissolved oxygen concentrations, biochemical oxygen demand (BOD) and chemical oxygen demand (COD), nitrogen, phosphorus, chlorine. Biological characteristics are determined with bioassays and aquatic toxicology tests.

<span class="mw-page-title-main">Secondary treatment</span> Biological treatment process for wastewater or sewage

Secondary treatment is the removal of biodegradable organic matter from sewage or similar kinds of wastewater. The aim is to achieve a certain degree of effluent quality in a sewage treatment plant suitable for the intended disposal or reuse option. A "primary treatment" step often precedes secondary treatment, whereby physical phase separation is used to remove settleable solids. During secondary treatment, biological processes are used to remove dissolved and suspended organic matter measured as biochemical oxygen demand (BOD). These processes are performed by microorganisms in a managed aerobic or anaerobic process depending on the treatment technology. Bacteria and protozoa consume biodegradable soluble organic contaminants while reproducing to form cells of biological solids. Secondary treatment is widely used in sewage treatment and is also applicable to many agricultural and industrial wastewaters.

<span class="mw-page-title-main">Sequencing batch reactor</span> Type of activated sludge process for the treatment of wastewater

Sequencing batch reactors (SBR) or sequential batch reactors are a type of activated sludge process for the treatment of wastewater. SBR reactors treat wastewater such as sewage or output from anaerobic digesters or mechanical biological treatment facilities in batches. Oxygen is bubbled through the mixture of wastewater and activated sludge to reduce the organic matter. The treated effluent may be suitable for discharge to surface waters or possibly for use on land.

Merox is an acronym for mercaptan oxidation. It is a proprietary catalytic chemical process developed by UOP used in oil refineries and natural gas processing plants to remove mercaptans from LPG, propane, butanes, light naphthas, kerosene and jet fuel by converting them to liquid hydrocarbon disulfides.

Spent caustic is a waste industrial caustic solution that has become exhausted and is no longer useful (or spent). Spent caustics are made of sodium hydroxide or potassium hydroxide, water, and contaminants. The contaminants have consumed the majority of the sodium (or potassium) hydroxide and thus the caustic liquor is spent, for example, in one common application H2S (gas) is scrubbed by the NaOH (aqueous) to form NaHS (aq) and H2O (l), thus consuming the caustic.

Huntsman Chemical Company of Australia Pty Ltd (HCCA) operated a complex chemical manufacturing plant in Somerville Rd Brooklyn in Melbourne. The site is 35 hectares in size and is located in the City of Brimbank. HCCA was partially owned by the Huntsman Corporation.

<span class="mw-page-title-main">Trickling filter</span> Type of wastewater treatment system with a fixed bed of rocks or similar

A trickling filter is a type of wastewater treatment system. It consists of a fixed bed of rocks, coke, gravel, slag, polyurethane foam, sphagnum peat moss, ceramic, or plastic media over which sewage or other wastewater flows downward and causes a layer of microbial slime (biofilm) to grow, covering the bed of media. Aerobic conditions are maintained by splashing, diffusion, and either by forced-air flowing through the bed or natural convection of air if the filter medium is porous. The treatment of sewage or other wastewater with trickling filters is among the oldest and most well characterized treatment technologies.

Humid oxidation with peroxide (OHP) is a technology for wastewater treatment which uses hydrogen peroxide to generate highly oxidative hydroxyl radicals. OHP can be used to treat all types of organic wastewaters to achieve chemical oxygen demand (COD) and total organic carbon (TOC) reduction, or increase biodegradability. It can be applied as the standalone treatment or combined with a more economical biological treatment, depending on the oxidant's dose.

As an extension of the fluidized bed family of separation processes, the flash reactor (FR) employs turbulent fluid introduced at high velocities to encourage chemical reactions with feeds and subsequently achieve separation through the chemical conversion of desired substances to different phases and streams. A flash reactor consists of a main reaction chamber and an outlet for separated products to enter downstream processes.

<span class="mw-page-title-main">Vermifilter</span> Aerobic treatment system, consisting of a biological reactor containing media

A vermifilter is an aerobic treatment system, consisting of a biological reactor containing media that filters organic material from wastewater. The media also provides a habitat for aerobic bacteria and composting earthworms that purify the wastewater by removing pathogens and oxygen demand. The "trickling action" of the wastewater through the media dissolves oxygen into the wastewater, ensuring the treatment environment is aerobic for rapid decomposition of organic substances.

Electro-oxidation(EO), also known as anodic oxidation or electrochemical oxidation, is a technique used for wastewater treatment, mainly for industrial effluents, and is a type of advanced oxidation process (AOP). The most general layout comprises two electrodes, operating as anode and cathode, connected to a power source. When an energy input and sufficient supporting electrolyte are provided to the system, strong oxidizing species are formed, which interact with the contaminants and degrade them. The refractory compounds are thus converted into reaction intermediates and, ultimately, into water and CO2 by complete mineralization.

References

  1. "Zimpro History" . Retrieved February 4, 2010.
  2. Kumfer, B.; Lehmann, D. Wet Air Oxidation of Difficult to Treat Pharmaceutical Waste Streams. Water Practice2007,2, 1-11.
  3. Levec,J.; Albin,P. Catalytic wet-air oxidation processes: A review. Catalysis Today. 2007, 124, 172-184.
  4. 1 2 Luck, F. Wet air oxidation: past, present and future. Catalysis Today1999, 53, 81-91.
  5. Silva, A.; Marques, R.; Quinta-Ferreira, R. Catalyst based in cerium oxide for wet oxidation of acrylic acid in the prevention of environmental risks. Applied Catalysis2004, 47, 269-279.
  6. Bhargava, S.K.; Tardio, J.; Prasad, J.; Folger, K.; Akolekar, D.B.; Grocott, S.C. Wet Oxidation and Catalytic Wet Oxidation. Ind. Eng. Chem. Res.2006, 45, 1221-1258.
  7. Kolaczkowski, S.T.; Plucinski, P.; Beltran, F.J.; Rivas, F.J.; McLurgh, D.B. Wet air oxidation: a review of process technologies and aspects in reactor design. Chemical Engineering Journal199973, 143-160.
  8. Kumfer, B.; Clark, M. “Wet Air Oxidation of Spent Caustic in Petroleum Refineries”, International Water Conference (IWC), San Antonio, TX, November 4–8, 2012.
  9. Heimbuch, J.; Wilhelmi, A. Wet Air Oxidation – A treatment Means for Aqueous Hazardous Waste Streams. Journal of Hazardous Material. 1985, 12, 187-200.
  10. Kumfer, B.; Clark, M.; Cook, S.; Garza, T.; Jackson, S. “Treatment of Produced Water Containing KHI by Wet Air Oxidation”, International Conference on Gas Hydrates (ICGH), Beijing, China, 28 July- 1 August 2014.
  11. 1 2 3 4 5 Patria, L.; Maugans, C.; Ellis, C.; Belkhodja, M.; Cretenot, D. Luck, F., Copa, B; Wet air oxidation processes. In Advanced Oxidation Processes for Water and Wastewater Treatment, Parsons, S.; IWA Publishing: London, 2004, 247-274.