In AC electrical power systems, a synchroscope is a device that indicates the degree to which two systems (generators or power networks) are synchronized with each other. [1]
For two electrical systems to be synchronized, both systems must operate at the same frequency, and the phase angle between the systems must be zero (and two polyphase systems must have the same phase sequence). Synchroscopes measure and display the frequency difference and phase angle between two power systems. Only when these two quantities are zero is it safe to connect the two systems together. Connecting two unsynchronized AC power systems together is likely to cause high currents to flow, which will severely damage any equipment not protected by fuses or circuit breakers.
The simplest aid to synchronizing a generator to another system uses lamps wired between similar phases of the two systems; when the lamps stay dark, the voltage and frequency of the two systems are the same and the generator may be connected. However, the accuracy of this approach is low since it is difficult to discern slight phase differences, and the lamps do not show the relative speeds of the two systems. Synchroscopes are instruments that show the relative frequency (speed) difference and the phase angle between the machine to be synchronized and the system voltage.
Since most synchroscopes are connected only to a single phase of the two systems, they cannot assure that the phase sequence is correct. When generators are newly connected to a power system, or temporary connections are used, other means are required to assure both systems have the same phase sequence. Some generators use both a synchroscope and a set of two lamps. If the lamps flash out of sequence, then the phase sequence is incorrect.
Synchroscopes are electrodynamic instruments, which rely on the interaction of magnetic fields to rotate a pointer. In most types, unlike voltmeters and wattmeters, there is no restoring spring torque for the magnetically produced torques to overcome; the pointer system is free to rotate continually. Synchroscopes have a damping vane to smooth out vibration of the moving system.
A polarized-vane synchroscope has a field winding with a phase-shifting network arranged to produce a rotating magnetic field. The field windings are connected to the "incoming" machine. A single-phase polarizing winding is connected to the "running" system. It is mounted perpendicular to the field winding and produces a magnetic flux that passes through the moving vanes. The moving vanes turn a shaft that carries a pointer moving over a scale. If the frequency of the source connected to the polarizing winding is different from the source connected to the field winding, the pointer rotates continually at a speed proportional to the difference in system frequencies (the beat frequency). The scale is marked to show the direction of rotation corresponding to the "incoming" machine running faster than the "running" system. When the frequencies match, the moving vanes will rotate to a position corresponding to the phase difference between the two sources. The incoming machine can then be adjusted in speed so that the two systems are in phase agreement.
In the moving iron instrument, an iron vane is mounted on a shaft along with the pointer. The field winding is a three-phase winding, with the phases connected to both the running and incoming sources through a phase-shifting "impedor" network containing resistors, capacitors, and inductors. In this instrument, conceptually the field winding produces two rotating magnetic fields due to the running and incoming sources. The iron vane moves in response to the resultant sum of the two fields.
The cross-coil synchroscope somewhat resembles a wound-field induction motor. A two-phase rotor winding is connected to the incoming machine source by a phase-shifting network through brushes and slip rings. The stationary field winding is connected to the incoming source. [2]
In a Weston pattern synchroscope, the moving element is not free to rotate continuously and oscillates back and forth slowly as the two sources are brought into synchronism. The moving pointer is illuminated by a pilot lamp connected to a three-winding transformer fed by both sources. The pointer is only illuminated at the in-phase condition, thereby distinguishing between in-phase and 180-degree out of phase conditions.
All these instruments use single-phase connections to the running and incoming systems to simplify the wiring. For most systems, synchroscopes are connected through voltage transformers to reduce the machine voltage to around 120 volts to operate the instruments. Synchroscopes operate only over a limited range of frequencies, a few per cent above and below the system nominal frequency. Cross-coil type instruments draw a relatively large amount of power from the systems and are intended for only brief operation. The moving-iron and polarized-vane instruments put less burden on the system and can operate for a longer time without overheating. [2]
Electronic digital systems can measure and display the phase angle difference directly. The display may be a ring of discrete LEDs arranged to simulate the effect of a pointer moving over a scale, with a different color of LED to indicate the "in phase" condition. These instruments may also have a relay contact for use by external control circuits, to indicate synchronism.
Synchroscopes are used in any power plant that connects to an outside electrical grid and also in isolated plants containing more than one generator. Each generator must be synchronized with the others before being connected to the plant bus. If line voltages are unequal when they are connected, a heavy current will flow as each line will attempt to equalize the other, causing damage in the process.
When operators of an electric generator wish to connect it to the grid, they first start the generator spinning at a rate approximately equal to the line frequency of the grid with which they plan to connect. The voltage of the generator is then matched with the grid by adjusting the field/armature current. The synchroscope is connected to the power grid and to the generator being started.
If the generator is turning at a lower frequency than the grid, the synchroscope pointer rotates continually in the direction (usually counterclockwise) marked "slow" or "lag" on the dial to indicate that the generator is running slower than, or lagging behind, the grid. If the generator is running faster than the grid, the pointer rotates continually in the opposite direction, marked "fast" or "lead". Next, the plant operator adjusts the speed of the generator until it is running at precisely the same speed (frequency) as the grid. As the frequency of the generator nears that of the grid, the synchroscope pointer slows down and when the frequencies match, the pointer stops rotating.
There is then one more task to perform before the generator can be connected to the grid. Although the generator and the grid are now operating at the same frequency, they are not necessarily at the same position in the rotational cycle as each other. If two electrical networks operating at two different phase angles were to be connected to each other, a fault similar to a short circuit would occur, presenting a hazard of damage to the generator or other equipment.
The position (as opposed to rotation) of the pointer on a synchroscope indicates the phase angle between the two systems. The angle between the systems is zero when the synchroscope pointer is directly on the line in between the "slow" and "fast" markings on the dial. (In the picture example in this article, the zero-phase-angle position is straight upwards, at the "12 o'clock" position.)
Speed of the prime mover is adjusted slightly according to the "slow" or "fast" indication of the pointer. Slightly before the pointer reaches the zero mark, the plant operator returns the generator to the grid frequency in order to stop the needle when it reaches the zero mark. When the pointer is at zero and is not moving, the two systems are synchronized.
Once the two systems are synchronized, they can be safely connected. Depending on the application and the circuit design, the operator closes the breaker when the synchroscope pointer is passing through approximately "11 o'clock", while traveling slowly in the fast direction. The idea is that when the breaker makes contact, the phase difference would be close to zero (12 o'clock). The slightly faster frequency is intended to prevent the generator paralleling onto the grid as a motor load, potentially damaging the prime mover (steam turbine or reciprocating internal combustion engine). The machine may be protected from this occurrence by a "reverse power" trip.
In some power plants, a set of lamps may be connected between the generator and system busses (or between the instrument transformers connected to those busses) as a backup to the synchroscope instrument. The lamps flicker at the difference between system and generator frequency. The lamps can be connected to go dark when the phase voltages are identical and in-phase. [1]
In addition to synchronizing generators to power systems, similar frequency-difference indicating instruments are used on multiengine ships and aircraft to allow the operators to exactly synchronize the speed of engines. This helps reduce the noise and vibration due to slight differences, for example, in the speeds of two propellers on an aircraft. In this application a synchroscope responds to slight speed differences that would not be visible on an engine tachometer.
Three-phase electric power is a common type of alternating current (AC) used in electricity generation, transmission, and distribution. It is a type of polyphase system employing three wires and is the most common method used by electrical grids worldwide to transfer power.
In electrical engineering, the power factor of an AC power system is defined as the ratio of the real power absorbed by the load to the apparent power flowing in the circuit. Real power is the average of the instantaneous product of voltage and current and represents the capacity of the electricity for performing work. Apparent power is the product of root mean square (RMS) current and voltage. Due to energy stored in the load and returned to the source, or due to a non-linear load that distorts the wave shape of the current drawn from the source, the apparent power may be greater than the real power, so more current flows in the circuit than would be required to transfer real power alone. A power factor magnitude of less than one indicates the voltage and current are not in phase, reducing the average product of the two. A negative power factor occurs when the device generates real power, which then flows back towards the source.
Alternating current (AC) is an electric current that periodically reverses direction and changes its magnitude continuously with time, in contrast to direct current (DC), which flows only in one direction. Alternating current is the form in which electric power is delivered to businesses and residences, and it is the form of electrical energy that consumers typically use when they plug kitchen appliances, televisions, fans and electric lamps into a wall socket. The abbreviations AC and DC are often used to mean simply alternating and direct, respectively, as when they modify current or voltage.
In electricity generation, a generator is a device that converts motion-based power or fuel-based power into electric power for use in an external circuit. Sources of mechanical energy include steam turbines, gas turbines, water turbines, internal combustion engines, wind turbines and even hand cranks. The first electromagnetic generator, the Faraday disk, was invented in 1831 by British scientist Michael Faraday. Generators provide nearly all the power for electrical grids.
An alternator is an electrical generator that converts mechanical energy to electrical energy in the form of alternating current. For reasons of cost and simplicity, most alternators use a rotating magnetic field with a stationary armature. Occasionally, a linear alternator or a rotating armature with a stationary magnetic field is used. In principle, any AC electrical generator can be called an alternator, but usually, the term refers to small rotating machines driven by automotive and other internal combustion engines.
A polyphase system is a means of distributing alternating-current (AC) electrical power that utilizes more than one AC phase, which refers to the phase offset value between AC in multiple conducting wires; phases may also refer to the corresponding terminals and conductors, as in color codes. Polyphase systems have two or more energized electrical conductors carrying alternating currents with a defined phase between the voltage waves in each conductor. Early systems used 4 wire two-phase with a 90° phase angle, but modern systems almost universally use three-phase voltage, with a phase angle of 120°.
A synchronous electric motor is an AC electric motor in which, at steady state, the rotation of the shaft is synchronized with the frequency of the supply current; the rotation period is exactly equal to an integer number of AC cycles. Synchronous motors use electromagnets as the stator of the motor which create a magnetic field that rotates in time with the oscillations of the current. The rotor with permanent magnets or electromagnets turns in step with the stator field at the same rate and as a result, provides the second synchronized rotating magnet field. Doubly fed synchronous motors use independently-excited multiphase AC electromagnets for both rotor and stator.
A synchro is, in effect, a transformer whose primary-to-secondary coupling may be varied by physically changing the relative orientation of the two windings. Synchros are often used for measuring the angle of a rotating machine such as an antenna platform or transmitting rotation. In its general physical construction, it is much like an electric motor. The primary winding of the transformer, fixed to the rotor, is excited by an alternating current, which by electromagnetic induction causes voltages to appear between the Y-connected secondary windings fixed at 120 degrees to each other on the stator. The voltages are measured and used to determine the angle of the rotor relative to the stator.
An AC motor is an electric motor driven by an alternating current (AC). The AC motor commonly consists of two basic parts, an outside stator having coils supplied with alternating current to produce a rotating magnetic field, and an inside rotor attached to the output shaft producing a second rotating magnetic field. The rotor magnetic field may be produced by permanent magnets, reluctance saliency, or DC or AC electrical windings.
Doubly fed electric machines, also slip-ring generators, are electric motors or electric generators, where both the field magnet windings and armature windings are separately connected to equipment outside the machine.
An induction generator or asynchronous generator is a type of alternating current (AC) electrical generator that uses the principles of induction motors to produce electric power. Induction generators operate by mechanically turning their rotors faster than synchronous speed. A regular AC induction motor usually can be used as a generator, without any internal modifications. Because they can recover energy with relatively simple controls, induction generators are useful in applications such as mini hydro power plants, wind turbines, or in reducing high-pressure gas streams to lower pressure.
The rotor is a moving component of an electromagnetic system in the electric motor, electric generator, or alternator. Its rotation is due to the interaction between the windings and magnetic fields which produces a torque around the rotor's axis.
Various types of electrical transformer are made for different purposes. Despite their design differences, the various types employ the same basic principle as discovered in 1831 by Michael Faraday, and share several key functional parts.
In an alternating current (AC) electric power system, synchronization is the process of matching the frequency, phase and voltage of a generator or other source to an electrical grid in order to transfer power. If two unconnected segments of a grid are to be connected to each other, they cannot safely exchange AC power until they are synchronized.
In electrical engineering, electric machine is a general term for machines using electromagnetic forces, such as electric motors, electric generators, and others. They are electromechanical energy converters: an electric motor converts electricity to mechanical power while an electric generator converts mechanical power to electricity. The moving parts in a machine can be rotating or linear. While transformers are occasionally called "static electric machines", since they do not have moving parts, generally they are not considered "machines", but as electrical devices "closely related" to the electrical machines.
A permanent magnet synchronous generator is a generator where the excitation field is provided by a permanent magnet instead of a coil. The term synchronous refers here to the fact that the rotor and magnetic field rotate with the same speed, because the magnetic field is generated through a shaft-mounted permanent magnet mechanism, and current is induced into the stationary armature.
A magneto is an electrical generator that uses permanent magnets to produce periodic pulses of alternating current. Unlike a dynamo, a magneto does not contain a commutator to produce direct current. It is categorized as a form of alternator, although it is usually considered distinct from most other alternators, which use field coils rather than permanent magnets.
Single-phase generator is an alternating current electrical generator that produces a single, continuously alternating voltage. Single-phase generators can be used to generate power in single-phase electric power systems. However, polyphase generators are generally used to deliver power in three-phase distribution system and the current is converted to single-phase near the single-phase loads instead. Therefore, single-phase generators are found in applications that are most often used when the loads being driven are relatively light, and not connected to a three-phase distribution, for instance, portable engine-generators. Larger single-phase generators are also used in special applications such as single-phase traction power for railway electrification systems.
This glossary of electrical and electronics engineering is a list of definitions of terms and concepts related specifically to electrical engineering and electronics engineering. For terms related to engineering in general, see Glossary of engineering.