OPC Data Access

Last updated
OPC Data Access (OPC DA)
International standardOPC DA specification
Developed by OPC Foundation
IntroducedAugust 1996;27 years ago (1996-08)
Industry Operational technology and Information technology
Compatible hardware Windows
Superseded by OPC Unified Architecture
Website https://opcfoundation.org/about/opc-technologies/opc-classic/

The OPC Data Access Specification is the first of a group of specifications known as the OPC Classic Specifications. [1]

Contents

OPC Data Access is a group of client–server standards that provides specifications for communicating real-time data from data acquisition devices such as PLCs to display and interface devices like Human–Machine Interfaces (HMI), SCADA systems [2] and also ERP/MES systems. [3] The specifications focus on the continuous communication of data.

The OPC Data Access specification is also known as OPC DA. OPC DA deals only with real-time data and not historical data (for historical data you need to use OPC Historical Data Access, or OPC HDA) or events (for Alarms and Events you need to use OPC Alarms and Events, or OPC AE). There are three attributes associated with OPC DA data. These are

  1. a value,
  2. the quality of the value, and
  3. a timestamp.

The OPC DA specification states that these three attributes have to be returned to an OPC client making a request. Therefore, if the data source is not capable of providing a timestamp, for example, the OPC DA server must create a timestamp.

The OPC Classic specifications are based on the Microsoft COM technology [4] and define a C/C++ interface. A standard Automation wrapper interface is also defined for access from Visual Basic, Delphi and other automation-enabled languages. [5] Several vendors offer .NET toolkits to make the OPC interface accessible in .NET applications.

The newer OPC .NET (OPC Xi) specification is based on WCF (Windows Communication Foundation) and defines a .NET interface with the functionality of the OPC Classic specifications OPC DA, OPC HDA and OPC AE (Alarms&Events). [6]

The more recent OPC Unified Architecture allows the same functionality but offers platform independence and optionally complex information modelling capabilities. [7]

See also

Related Research Articles

Supervisory control and data acquisition (SCADA) is a control system architecture comprising computers, networked data communications and graphical user interfaces for high-level supervision of machines and processes. It also covers sensors and other devices, such as programmable logic controllers, which interface with process plant or machinery.

<span class="mw-page-title-main">Preboot Execution Environment</span> Standard for booting from a server

In computing, the Preboot eXecution Environment, PXE specification describes a standardized client–server environment that boots a software assembly, retrieved from a network, on PXE-enabled clients. On the client side it requires only a PXE-capable network interface controller (NIC), and uses a small set of industry-standard network protocols such as DHCP and TFTP.

Open Platform Communications (OPC) is a series of standards and specifications for industrial telecommunication. They are based on Object Linking and Embedding (OLE) for process control. An industrial automation task force developed the original standard in 1996 under the name OLE for Process Control. OPC specifies the communication of real-time plant data between control devices from different manufacturers.

The OPC Foundation is an industry consortium that creates and maintains standards for open connectivity of industrial automation devices and systems, such as industrial control systems and process control generally. The OPC standards specify the communication of industrial process data, alarms and events, historical data and batch process data between sensors, instruments, controllers, software systems, and notification devices.

In computing, Web-Based Enterprise Management (WBEM) comprises a set of systems-management technologies developed to unify the management of distributed computing environments. The WBEM initiative, initially sponsored in 1996 by BMC Software, Cisco Systems, Compaq Computer, Intel, and Microsoft, is now widely adopted. WBEM is based on Internet standards and Distributed Management Task Force (DMTF) open standards:

A fieldbus is a member of a family of industrial digital communication networks used for real-time distributed control. Fieldbus profiles are standardized by the International Electrotechnical Commission (IEC) as IEC 61784/61158.

Microsoft Active Accessibility (MSAA) is an application programming interface (API) for user interface accessibility. MSAA was introduced as a platform add-on to Microsoft Windows 95 in 1997. MSAA is designed to help Assistive Technology (AT) products interact with standard and custom user interface (UI) elements of an application, as well as to access, identify, and manipulate an application's UI elements. AT products work with MSAA enabled applications in order to provide better access for individuals who have physical or cognitive difficulties, impairments, or disabilities. Some examples of AT products are screen readers for users with limited sight, on screen keyboards for users with limited physical access, or narrators for users with limited hearing. MSAA can also be used for automated testing tools, and computer-based training applications.

The Windows Communication Foundation (WCF), previously known as Indigo, is a free and open-source runtime and a set of APIs in the .NET Framework for building connected, service-oriented applications.

This group of standards, created by the OPC Foundation, provides COM specifications for communicating data from devices and applications that provide historical data, such as databases. The specifications provides for access to raw, interpolated and aggregate data.

<span class="mw-page-title-main">Profinet</span> Computer network protocol

Profinet is an industry technical standard for data communication over Industrial Ethernet, designed for collecting data from, and controlling equipment in industrial systems, with a particular strength in delivering data under tight time constraints. The standard is maintained and supported by Profibus and Profinet International, an umbrella organization headquartered in Karlsruhe, Germany.

The international standard IEC 61499, addressing the topic of function blocks for industrial process measurement and control systems, was initially published by the International Electrotechnical Commission (IEC) in 2005. The specification of IEC 61499 defines a generic model for distributed control systems and is based on the IEC 61131 standard. The concepts of IEC 61499 are also explained by Lewis and Zoitl as well as Vyatkin.

OPC Unified Architecture is a cross-platform, open-source, IEC62541 standard for data exchange from sensors to cloud applications developed by the OPC Foundation. Distinguishing characteristics are:

Microsoft UI Automation (UIA) is an application programming interface (API) that allows one to access, identify, and manipulate the user interface (UI) elements of another application.

WCF Data Services is a platform for what Microsoft calls Data Services. It is actually a combination of the runtime and a web service through which the services are exposed. It also includes the Data Services Toolkit which lets Astoria Data Services be created from within ASP.NET itself. The Astoria project was announced at MIX 2007, and the first developer preview was made available on April 30, 2007. The first CTP was made available as a part of the ASP.NET 3.5 Extensions Preview. The final version was released as part of Service Pack 1 of the .NET Framework 3.5 on August 11, 2008. The name change from ADO.NET Data Services to WCF data Services was announced at the 2009 PDC.

IEC 60870 part 6 in electrical engineering and power system automation, is one of the IEC 60870 set of standards which define systems used for telecontrol in electrical engineering and power system automation applications. The IEC Technical Committee 57 have developed part 6 to provide a communication profile for sending basic telecontrol messages between two systems which is compatible with ISO standards and ITU-T recommendations.

Inductive Automation is a supplier of web-based industrial automation software based in Folsom, California, US. The Ignition SCADA platform is the company's main product line.

Sercos III is the third generation of the Sercos interface, a standardized open digital interface for the communication between industrial controls, motion devices, input/output devices (I/O), and Ethernet nodes, such as PCs. Sercos III applies the hard real-time features of the Sercos interface to Ethernet. It is based upon and conforms to the Ethernet standard. Work began on Sercos III in 2003, with vendors releasing first products supporting it in 2005.

Manufacturing execution systems (MES) are computerized systems used in manufacturing to track and document the transformation of raw materials to finished goods. MES provides information that helps manufacturing decision-makers understand how current conditions on the plant floor can be optimized to improve production output. MES works as real-time monitoring system to enable the control of multiple elements of the production process.

PLCopen is an independent organisation providing efficiency in industrial automation based on the needs of users. PLCopen members have concentrated on technical specifications around IEC 61131-3, creating specifications and implementations in order to reduce cost in industrial engineering. The outcome for example is standardized libraries for different application fields, harmonized language conformity levels and engineering interfaces for exchange. Experts of the PLCopen members are organized in technical committees and together with end users define such open standards.

Ignition is an Integrated Software Platform for SCADA systems released by Inductive Automation in January 2010. It is based on a SQL Database-centric architecture. Ignition features cross platform web based deployment through Java Web Start technology. The Ignition platform has three main components: the Ignition Gateway, the Designer, and the runtime clients. Independent modules provide separate functionality in any or all of the platform components. Ignition SCADA modules provide features such as: Real-Time Status Control, Alarming, Reporting, Data Acquisition, Scripting, Scheduling, MES, and Mobile support.

References

  1. "Members".
  2. "What is OPC?".
  3. Mahalik, Nitaigour P. (2013-03-09). Fieldbus Technology: Industrial Network Standards for Real-Time Distributed Control. Springer. ISBN   9783662072196.
  4. "Classic".
  5. "Members".
  6. ".NET 4.0 (WCF) | OPC Foundation". opcfoundation.org. Archived from the original on 2014-07-03.
  7. "Unified Architecture".