Flexible AC transmission system

Last updated

A Flexible Alternating Current Transmission System (FACTS) is a family of Power-Electronic based devices designed for use on an Alternating Current (AC) Transmission System to improve and control Power Flow and support Voltage. FACTs devices are alternatives to traditional electric grid solutions and improvements, where building additional Transmission Lines or Substation is not economically or logistically viable.

Contents

In general, FACTs devices improve power and voltage in three different ways: Shunt Compensation of Voltage (replacing the function of capacitors or inductors), Series Compensation of Impedance (replacing series capacitors) or Phase-Angle Compensation (replacing Generator Droop-Control or Phase-Shifting Transformers). While other traditional equipment can accomplish all of this, FACTs devices utilize Power Electronics that are fast enough to switch sub-cycle opposed to seconds or minutes. Most FACTs devices are also dynamic and can support voltage across a range rather than just on and off, and are multi-quadrant, i.e. they can both supply and consume Reactive Power, and even sometimes Real Power. All of this give them their "flexible" nature and make them well-suited for applications with unknown or changing requirements.

The FACTs family initially grew out of the development of High-Voltage Direct-Current (HVDC) conversion and transmission, which used Power Electronics to convert AC to DC to enable large, controllable power transfers. [1] While HVDC focused on conversion to DC, FACTs devices used the developed technology to control power and voltage on the AC system. The most common type of FACTs device is the Static VAR Compensator (SVC), which uses Thyristors to switch and control shunt capacitors and reactors, respectively.

History

When AC won the War of Currents in the late 19th century, and electric grids began expanding and connecting cities and states, the need for reactive compensation became apparent. [2] While AC offered benefits with transformation and reduced current, the alternating nature of voltage and current lead to additional challenges with the natural capacitance and inductance of transmission lines. Heavily loaded lines consumed reactive power due to the line's inductance, and as transmission voltage increased throughout the 20th century, the higher voltage supplied capacitive reactive power. As operating a transmission line only at it surge impedance loading (SIL) was not feasible, [2] other means to manage the reactive power was needed.

A mercury-arc Valve used for high-voltage power electronics. Mercury Arc Valve, Radisson Converter Station, Gillam MB.jpg
A mercury-arc Valve used for high-voltage power electronics.

Synchronous Machines were commonly used at the time for generators, and could provide some reactive power support, however were limited due to the increase in losses it caused. They also became less effective as higher voltage transmissions lines moved loads further from sources. Fixed, shunt capacitor and reactor banks filled this need by being deployed where needed. In particular, shunt capacitors switched by circuit breakers provided an effective means to managing varying reactive power requirements due to changing loads. [3] However, this was not without limitations.

Shunt capacitors and reactors are fixed devices, only able to be switched on and off. This required either a careful study of the exact size needed, [4] or accepting less than ideal effects on the voltage of a transmission line. The need for a more dynamic and flexible solution was realized with the mercury-arc valve in the early 20th century. Similar to a vacuum tube, the mercury-arc valve was a high-powered rectifier, capable of converting high AC voltages to DC. As the technology improved, inverting became possible as well and mercury valves found use in power systems and HVDC ties. When connected to a reactor, different switching pattern could be used to vary the effective inductance connected, [5] allow for more dynamic control. Arc valves continued to dominate power electronics until the rise of solid-state semiconductors in the mid 20th century. [6]

As semiconductors replaced vacuum tubes, the thyristor created the first modern FACTs devices in the Static VAR Compensator (SVC). [7] Effectively working as a circuit breaker that could switch on in milliseconds, it allowed for quickly switching capacitor banks. Connected to a reactor and switched sub-cycle allowed the effective inductance to be varied. The thyristor also greatly improved the control system, allowing an SVC to detect and react to faults to better support the system. [8] The thyristor dominated the FACTs and HVDC world until the late 20th century, when the IGBT began to match its power ratings. [9]

Theory

The basic theory for how FACTs devices affect the AC system is based on analyzing how power transfers between two points in an AC system. This is particularly relevant to how an AC electrical grid functions, as the grid has numerous nodes (substations) that lack sources (generators) or loads. Power flow must be calculated and controlled at each node (substation bus) to ensure the grid design and topology itself does not prevent generated electricity from reaching loads, [10] as when Transmission Lines reach dozens to hundreds of miles in length, they add significant impedance and voltage drop to the system.

Given two buses, each with their own voltage magnitude and phase angle, and connected by a Transmission Line with an impedance, the current flowing between them is given by [11]

A simple Circuit Diagram showing two buses connected through an impedance, with a Vector Diagram representing the phase-angle between them FACTS theory1.PNG
A simple Circuit Diagram showing two buses connected through an impedance, with a Vector Diagram representing the phase-angle between them

Apparent Power flow, and thus real and reactive power, is then given by

Combining these two equations gives the real and reactive power flow as a function of voltages and impedance. This can be done relatively easily, and is done in load-flow and power analysis programs, but results in equations that are not intuitive to understand. Two approximations can be made to simplify things: assume a lossless Transmission Line (a decent assumption as very low resistance conductor is typically used) and neglecting any capacitance on the line (a fair assumption for 200kV lines and lower). This reduces the Line impedance to just a reactance, and results in the real and reactive power being

where

is the magnitude of the Sending-End Voltage, at the first bus

is the magnitude of the Receiving-End Voltage, at the second bus

is the reactance of the Transmission Line between the buses

is the phase angle difference between the sending-end and receiving end voltages

From the above equations, it can be seen that there are three variables that affect real and reactive power flow on a Transmission Line: [12] the voltage magnitudes at either bus, the line reactance between the buses, and the voltage phase-angle difference between the buses. All FACTs devices operation on the fundamental principal that changing one or more of these variables will change the real and reactive power flow on the transmission line. Some FACTs devices will just change a single variable, while others will control all three.

It should be noted, and will be made more explicit below, that FACTs devices do not create or add real power to the system, they simply affect the circuit parameters between two points to affect how and when power flows.

Types of FACTs devices

Given that FACTs device can change up to three parameters to affect power flow (voltage, impedance, and/or phase-angle), they are often categorized by what parameter they are controlling. As the conventional devices for controlling voltage (shunt capacitors and shunt inductors) and impedance (series capacitors and load-flow reactors) are so common, FACTs devices targeting voltage and impedance parameters are categorized as shunt and series devices, respectively.

Shunt Compensation Devices

The goal shunt compensation is to connect a device in parallel with the system that will improve voltage and enable larger power flow. This is traditionally done using shunt capacitors and inductors (reactors), [13] much like Power Factor Correction.

The most common shunt compensation device is the Static VAR Compensator (SVC). [14] SVCs use power electronics, generally Thyristors, to switch fixed capacitors and reactors. These are referred to as Thyristor Switched Capacitor (TSC) and Thyristor Switched Reactor (TSR), respectively. Thyristors are fast enough that they can be switched sub-cycle, and can switch a reactor at different points each cycle to control the vars the reactor produces. When arranged to do this, the TSR is referred to as a Thyristor Controlled Reactor (TCR). TCRs produce large amounts of harmonics and require Filter Banks to prevent adverse effects to the system.

Another type of shunt compensation is the Static Synchronous Compensator or STATCOM. Power electronics are combined in series with a reactor to form a Voltage-Sourced Converter (VSC), which when connected to an AC system forms a STATCOM. [15] A VSC use the same principal of power flow on a transmission line; measuring the system voltage its connected to and varying the voltage of the power electronics to cause reactive power flow in or out of the VSC. Early STATCOMs used thyristors as their power electronics and Pulse-Width Modulation (PWM) to control reactive power, but with advances in semiconductor technologies, Insulated-Gate Bipolar Transistors (IGBT) have replaced them.

Series Compensation Devices

Series Compensation devices change the impedance of the Transmission Line to increase or decrease power flow. Power flow is increased by adding a series capacitor to offset line inductance or decreased by adding a series load-flow reactor to add to the line inductance.

One type of series compensation is the Thyristor-Controlled Series Capacitor (TCSC), which combines the TCR from an SVC in parallel with a traditional fixed series capacitor. As using power electronics to switch capacitors sub-cycle is not feasible due to concerns of stored charge, a TCR is used to create a variable inductance to offset the capacitor. A TCSC can be used to dynamically vary the power flow on a transmission line. [16]

A VSC can also be used as a series compensation device if it's connected across the secondary winding of a series-connected transformer. This arrangement is referred to as a Static Synchronous Series Compensator (SSSC), [12] and offers the benefits of a smaller reactor than in a TCSC, and the lower harmonic production of a VSC (or Voltage-Source Inverter - VSI when used in a SSSC) compared to a TCR.

Phase Angle Compensation

Power will only flow between two points on an AC system if there is a phase angle difference between the buses. Traditionally this is controlled by generators, however in large grids this becomes ineffective for managing power flow between distant buses. Phase-Shifting Transformers (PST) are generally used for these applications and can just be a Phase-Angle Regulator (PAR) or control both phase-angle and voltage.

The most straightforward phase angle compensation device would be to replace the tap changer on PAR with thyristors to switch portions of the winding in and out, forming a Thyristor-Controlled Phase-Shifting Transformer (TCPST). [17] However, this is generally not done as a TCPST would be considerably more expensive than a PAR. Instead, this idea is expanded to replace a Quadrature Booster with a device referred to as a Thyristor-Controlled Phase-Angle Regulator (TCPAR), also known as a Static Phase-Shifter (SPS). [18] From the schematic, it can be seen that a TCPAR is just a Quadrature Booster with the mechanical portions of the excitor and booster transformers replaced with Power Electronics, typically Thyristors.

Another way to form a TCPAR is to separate the Excitor and Booster transformer and control their secondaries with separate sets of Power Electronics. By linking the two sets of Power Electronics through a DC bus, typically by using GTO Thyristors or IGBTs, a TCPAR can be formed. While doing this may initially seem unnecessary, by looking at the shunt and series transformers and their electronics separately, it is apparent that the shunt portion is a STATCOM, and the series portion is a SSSC. With the DC bus providing power from the shunt portion to the series portion, the device functions as a Phase-Angle regulator, however with the DC bus isolating the two side, the STATCOM can control the shunt voltage or the SSSC can control line impedance. This gives the device its name, the Unified Power Flow Controller (UPFC), [19] as it can control all three parameters that affect Power Control.

See also

Related Research Articles

<span class="mw-page-title-main">High-voltage direct current</span> Electric power transmission system

A high-voltage direct current (HVDC) electric power transmission system uses direct current (DC) for electric power transmission, in contrast with the more common alternating current (AC) transmission systems.

<span class="mw-page-title-main">Rectifier</span> Electrical device that converts AC to DC

A rectifier is an electrical device that converts alternating current (AC), which periodically reverses direction, to direct current (DC), which flows in only one direction. The reverse operation is performed by an inverter.

<span class="mw-page-title-main">Thyristor</span> Type of solid state switch

A thyristor is a solid-state semiconductor device which can be thought of as being a highly robust and switchable diode, allowing the passage of current in one direction but not the other, often under control of a gate electrode, that is used in high power applications like inverters and radar generators. It usually consists of four layers of alternating P- and N-type materials. It acts as a bistable switch. There are two designs, differing in what triggers the conducting state. In a three-lead thyristor, a small current on its gate lead controls the larger current of the anode-to-cathode path. In a two-lead thyristor, conduction begins when the potential difference between the anode and cathode themselves is sufficiently large. The thyristor continues conducting until the voltage across the device is reverse-biased or the voltage is removed, or through the control gate signal on newer types.

A static VAR compensator (SVC) is a set of electrical devices for providing fast-acting reactive power on high-voltage electricity transmission networks. SVCs are part of the flexible AC transmission system device family, regulating voltage, power factor, harmonics and stabilizing the system. A static VAR compensator has no significant moving parts. Prior to the invention of the SVC, power factor compensation was the preserve of large rotating machines such as synchronous condensers or switched capacitor banks.

In electrical engineering, particularly power engineering, voltage regulation is a measure of change in the voltage magnitude between the sending and receiving end of a component, such as a transmission or distribution line. Voltage regulation describes the ability of a system to provide near constant voltage over a wide range of load conditions. The term may refer to a passive property that results in more or less voltage drop under various load conditions, or to the active intervention with devices for the specific purpose of adjusting voltage.

<span class="mw-page-title-main">Power electronics</span> Technology of power electronics

Power electronics is the application of electronics to the control and conversion of electric power.

<span class="mw-page-title-main">HVDC converter station</span> Type of substation

An HVDC converter station is a specialised type of substation which forms the terminal equipment for a high-voltage direct current (HVDC) transmission line. It converts direct current to alternating current or the reverse. In addition to the converter, the station usually contains:

<span class="mw-page-title-main">AC power</span> Power in alternating current systems

In an electric circuit, instantaneous power is the time rate of flow of energy past a given point of the circuit. In alternating current circuits, energy storage elements such as inductors and capacitors may result in periodic reversals of the direction of energy flow. Its SI unit is the watt.

<span class="mw-page-title-main">Static synchronous compensator</span>

A static synchronous compensator (STATCOM), is a shunt-connected, reactive compensation device used on transmission networks. It uses power electronics to form a voltage-source converter that can act as either a source or sink of reactive AC power to an electricity network. It is a member of the FACTS family of devices.

<span class="mw-page-title-main">Electric power system</span> Network of electrical component deployed to generate, transmit & distribute electricity

An electric power system is a network of electrical components deployed to supply, transfer, and use electric power. An example of a power system is the electrical grid that provides power to homes and industries within an extended area. The electrical grid can be broadly divided into the generators that supply the power, the transmission system that carries the power from the generating centers to the load centers, and the distribution system that feeds the power to nearby homes and industries.

<span class="mw-page-title-main">GK Dürnrohr</span>

The GK Dürnrohr was a high-voltage direct current back-to-back scheme west of Dürnrohr substation, which was used for the energy exchange between Austria and Czechoslovakia between 1983 and 1996. The installation is no longer in use.

Dynamic voltage restoration (DVR) is a method of overcoming voltage sags and swells that occur in electrical power distribution. These are a problem because spikes consume power and sags reduce efficiency of some devices. DVR saves energy through voltage injections that can affect the phase and wave-shape of the power being supplied.

<span class="mw-page-title-main">Unified power flow controller</span> Electrical device for reactive power compensation on high-voltage electricity transmission networks

A unified power flow controller (UPFC) is an electrical device for providing fast-acting reactive power compensation on high-voltage electricity transmission networks. It uses a pair of three-phase controllable bridges to produce current that is injected into a transmission line using a series transformer. The controller can control active and reactive power flows in a transmission line.

In an electric power transmission system, a thyristor-controlled reactor (TCR) is a reactance connected in series with a bidirectional thyristor valve. The thyristor valve is phase-controlled, which allows the value of delivered reactive power to be adjusted to meet varying system conditions. Thyristor-controlled reactors can be used for limiting voltage rises on lightly loaded transmission lines. Another device which used to be used for this purpose is a magnetically controlled reactor (MCR), a type of magnetic amplifier otherwise known as a transductor.

A thyristor-switched capacitor (TSC) is a type of equipment used for compensating reactive power in electrical power systems. It consists of a power capacitor connected in series with a bidirectional thyristor valve and, usually, a current limiting reactor (inductor). The thyristor switched capacitor is an important component of a Static VAR Compensator (SVC), where it is often used in conjunction with a thyristor controlled reactor (TCR). Static VAR compensators are a member of the Flexible AC transmission system (FACTS) family.

An HVDC converter converts electric power from high voltage alternating current (AC) to high-voltage direct current (HVDC), or vice versa. HVDC is used as an alternative to AC for transmitting electrical energy over long distances or between AC power systems of different frequencies. HVDC converters capable of converting up to two gigawatts (GW) and with voltage ratings of up to 900 kilovolts (kV) have been built, and even higher ratings are technically feasible. A complete converter station may contain several such converters in series and/or parallel to achieve total system DC voltage ratings of up to 1,100 kV.

A magnetically-controlled shunt reactor represents electrotechnical equipment purposed for compensation of reactive power and stabilization of voltage level in high voltage (HV) electric networks rated for voltage classes 36 – 750 kV. MCSR is shunt-type static device with smooth regulation by means of inductive reactance.

<span class="mw-page-title-main">Static synchronous series compensator</span>

A static synchronous series compensator (SSSC) is a type of flexible AC transmission system which consists of a solid-state voltage source inverter coupled with a transformer that is connected in series with a transmission line. This device can inject an almost sinusoidal voltage in series with the line. This injected voltage could be considered as an inductive or capacitive reactance, which is connected in series with the transmission line. This feature can provide controllable voltage compensation. In addition, SSSC is able to reverse the power flow by injecting a sufficiently large series reactive compensating voltage.

This glossary of power electronics is a list of definitions of terms and concepts related to power electronics in general and power electronic capacitors in particular. For more definitions in electric engineering, see Glossary of electrical and electronics engineering. For terms related to engineering in general, see Glossary of engineering.

Voltage control and reactive power management are two facets of an ancillary service that enables reliability of the transmission networks and facilitates the electricity market on these networks. Both aspects of this activity are intertwined, so within this article the term voltage control will be primarily used to designate this essentially single activity, as suggested by Kirby & Hirst (1997). Voltage control does not include reactive power injections within one AC cycle; these are a part of a separate ancillary service, so-called system stability service. The transmission of reactive power is limited by its nature, so the voltage control is provided through pieces of equipment distributed throughout the power grid, unlike the frequency control that is based on maintaining the overall active power balance in the system.

References

  1. EPRI High Voltage Direct Current (HVDC) Transmission Reference Book EPRI, Palo Alto, CA: 2017. 1020401.
  2. 1 2 EPRI Increased Power Flow Guidebook—2017: Increasing Power Flow in Lines, Cables, and Substations. EPRI, Palo Alto, CA: 2017. 3002010150
  3. Gujar, Abhilash (2020-11-06). "Reactive Power Compensation using Shunt Capacitors for Transmission Line Loaded Above Surge Impedance". 2020 IEEE International Conference for Innovation in Technology (INOCON). IEEE. pp. 1–4. doi:10.1109/INOCON50539.2020.9298284. ISBN   978-1-7281-9744-9. S2CID   230512769.
  4. Kamel, Salah; Mohamed, Marwa; Selim, Ali; Nasrat, Loai S.; Jurado, Francisco (March 2019). "Power System Voltage Stability Based on Optimal Size and Location of Shunt Capacitor Using Analytical Technique". 2019 10th International Renewable Energy Congress (IREC). IEEE. pp. 1–5. doi:10.1109/IREC.2019.8754516. ISBN   978-1-7281-0140-8. S2CID   195831344.
  5. Rissik, H., Mercury-Arc Current Converters, Pitman. 1941.
  6. "1954: Morris Tanenbaum fabricates the first silicon transistor at Bell Labs". The Silicon Engine. Computer History Museum. Retrieved 23 August 2019.
  7. Owen, Edward L. (August 2007). "Fiftieth anniversary of modern power electronics: The Silicon Controlled Rectifier". 2007 IEEE Conference on the History of Electric Power. pp. 201–211. doi:10.1109/HEP.2007.4510267. ISBN   978-1-4244-1343-0. S2CID   12720980.
  8. Choudhary, Sunita; Mahela, Om Prakash; Ola, Sheesh Ram (November 2016). "Detection of transmission line faults in the presence of thyristor controlled reactor using discrete wavelet transform". 2016 IEEE 7th Power India International Conference (PIICON). IEEE. pp. 1–5. doi:10.1109/POWERI.2016.8077268. ISBN   978-1-4673-8962-4. S2CID   23488189.
  9. Iwamuro, Noriyuki; Laska, Thomas (March 2017). "IGBT History, State-of-the-Art, and Future Prospects". IEEE Transactions on Electron Devices. 64 (3): 741–752. Bibcode:2017ITED...64..741I. doi:10.1109/TED.2017.2654599. ISSN   0018-9383. S2CID   36435533.
  10. Kumar, Yogesh; Devabhaktuni, Vijay K.; Vemuru, Srinivasa (May 2015). "Comparison of power system simulation tools with load flow study cases". 2015 IEEE International Conference on Electro/Information Technology (EIT). IEEE. pp. 290–294. doi:10.1109/EIT.2015.7293355. ISBN   978-1-4799-8802-0.
  11. Mohan, Ned (2007). First course on power systems (Year 2006 Edition; revised July 2007 ed.). Minneapolis: MNPERE. ISBN   978-0-9715292-7-4.
  12. 1 2 Hingorani, Narain G.; Gyugyi, Laszlo (2000). Understanding FACTS: concepts and technology of flexible AC transmission systems. New York: IEEE Press. ISBN   978-0-7803-3455-7.
  13. EPRI Increased Power Flow Guidebook—2017: Increasing Power Flow in Lines, Cables, and Substations. EPRI, Palo Alto, CA: 2017. 3002010150.
  14. EPRI Power Electronics-Based Transmission Controllers Reference Book ("The Gold Book") EPRI, Palo Alto, CA: 2017. 1020401.
  15. Sood, Vijay K. (2004). HVDC and FACTS controllers: applications of static converters in power systems. Power electronics and power systems. Boston: Kluwer Academic Publishers. ISBN   978-1-4020-7890-3.
  16. Cao, Foqing; Hu, Lei; Zhang, Jingtao; Almenweer, Reem A.; Alnasseir, Jamal; Almaghout, Fadi (2023-12-15). "Study on Power Flow Improvement Using Static Compensators and Thyristor Controlled Series Capacitor in Transmission Network". IEEE: 354–359. doi:10.1109/CEECT59667.2023.10420634. ISBN   979-8-3503-4225-3.{{cite journal}}: Cite journal requires |journal= (help)
  17. Rezvanfar, R.; Mosayebian, M. E.; Monsef, H.; Ghasemi, H. (May 2011). "Impact of optimally located thyristor controlled phase angle regulator on system security and reliability". 2011 10th International Conference on Environment and Electrical Engineering. IEEE. doi:10.1109/eeeic.2011.5874829.
  18. Song, Yong-hua; Johns, Allan T., eds. (1999). Flexible ac transmission systems (FACTS). IEE power and energy series. London: Institution of Electrical Engineers. ISBN   978-0-85296-771-3.
  19. 2745.1-2019 - IEEE Guide for Technology of Unified Power Flow Controller Using Modular Multilevel Converter - Part 1: Functions, IEEE Standard