Reflections of signals on conducting lines

Last updated

A time-domain reflectometer; an instrument used to locate the position of faults on lines from the time taken for a reflected wave to return from the discontinuity. Megger Time-Domain Reflectometer MTDR1.jpg
A time-domain reflectometer; an instrument used to locate the position of faults on lines from the time taken for a reflected wave to return from the discontinuity.

A signal travelling along an electrical transmission line will be partly, or wholly, reflected back in the opposite direction when the travelling signal encounters a discontinuity in the characteristic impedance of the line, or if the far end of the line is not terminated in its characteristic impedance. This can happen, for instance, if two lengths of dissimilar transmission lines are joined.

Contents

This article is about signal reflections on electrically conducting lines. Such lines are loosely referred to as copper lines, and indeed, in telecommunications are generally made from copper, but other metals are used, notably aluminium in power lines. Although this article is limited to describing reflections on conducting lines, this is essentially the same phenomenon as optical reflections in fibre-optic lines and microwave reflections in waveguides.

Reflections cause several undesirable effects, including modifying frequency responses, causing overload power in transmitters and overvoltages on power lines. However, the reflection phenomenon can also be made use of in such devices as stubs and impedance transformers. The special cases of open circuit and short circuit lines are of particular relevance to stubs.

Reflections cause standing waves to be set up on the line. Conversely, standing waves are an indication that reflections are present. There is a relationship between the measures of reflection coefficient and standing wave ratio.

Specific cases

There are several approaches to understanding reflections, but the relationship of reflections to the conservation laws is particularly enlightening. A simple example is a step voltage, (where is the height of the step and is the unit step function with time ), applied to one end of a lossless line, and consider what happens when the line is terminated in various ways. The step will be propagated down the line according to the telegrapher's equation at some velocity and the incident voltage, , at some point on the line is given by [1]

The incident current, , can be found by dividing by the characteristic impedance,

Open circuit line

Fig. 1. Step voltage disturbance V u(t) is injected into the input of the line, vi travels down the line and is reflected back at the far end as vr. Step disturbance on transmission line.svg
Fig. 1. Step voltage disturbance Vu(t) is injected into the input of the line, vi travels down the line and is reflected back at the far end as vr.

The incident wave travelling down the line is not affected in any way by the open circuit at the end of the line. It cannot have any effect until the step actually reaches that point. The signal cannot have any foreknowledge of what is at the end of the line and is only affected by the local characteristics of the line. However, if the line is of length the step will arrive at the open circuit at time , at which point the current in the line is zero (by the definition of an open circuit). Since charge continues to arrive at the end of the line through the incident current, but no current is leaving the line, then conservation of electric charge requires that there must be an equal and opposite current into the end of the line. Essentially, this is Kirchhoff's current law in operation. This equal and opposite current is the reflected current, , and since

there must also be a reflected voltage, , to drive the reflected current down the line. This reflected voltage must exist by reason of conservation of energy. The source is supplying energy to the line at a rate of . None of this energy is dissipated in the line or its termination and it must go somewhere. The only available direction is back up the line. Since the reflected current is equal in magnitude to the incident current, it must also be so that

These two voltages will add to each other so that after the step has been reflected, twice the incident voltage appears across the output terminals of the line. As the reflection proceeds back up the line the reflected voltage continues to add to the incident voltage and the reflected current continues to subtract from the incident current. After a further interval of the reflected step arrives at the generator end and the condition of double voltage and zero current will pertain there also as well as all along the length of the line. If the generator is matched to the line with an impedance of the step transient will be absorbed in the generator internal impedance and there will be no further reflections. [2]

Fig. 2. Equivalent circuit of generator feeding a line. Equivalent generator and line.svg
Fig. 2. Equivalent circuit of generator feeding a line.

This counter-intuitive doubling of voltage may become clearer if the circuit voltages are considered when the line is so short that it can be ignored for the purposes of analysis. The equivalent circuit of a generator matched to a load to which it is delivering a voltage can be represented as in figure 2. That is, the generator can be represented as an ideal voltage generator of twice the voltage it is to deliver and an internal impedance of . [2]

Fig. 3. Open circuit generator Equivalent generator open circuit.svg
Fig. 3. Open circuit generator

However, if the generator is left open circuit, a voltage of appears at the generator output terminals as in figure 3. The same situation pertains if a very short transmission line is inserted between the generator and the open circuit. If, however, a longer line with a characteristic impedance of and noticeable end-to-end delay is inserted, the generator – being initially matched to the impedance of the line – will have at the output. But after an interval, a reflected transient will return from the end of the line with the "information" that the line is actually unterminated, and the voltage will become as before. [2]

Short circuit line

The reflection from a short-circuited line can be described in similar terms to that from an open-circuited line. Just as in the open circuit case where the current must be zero at the end of the line, in the short circuit case the voltage must be zero since there can be no volts across a short circuit. Again, all of the energy must be reflected back up the line and the reflected voltage must be equal and opposite to the incident voltage by Kirchhoff's voltage law:

and

As the reflection travels back up the line, the two voltages subtract and cancel, while the currents will add (the reflection is double negative - a negative current traveling in the reverse direction), the dual situation to the open circuit case. [2]

Arbitrary impedance

Fig. 4. Equivalent circuit of an incident wave on a transmission line arriving at an arbitrary load impedance. Equivalent incident wave and load.svg
Fig. 4. Equivalent circuit of an incident wave on a transmission line arriving at an arbitrary load impedance.

For the general case of a line terminated in some arbitrary impedance it is usual to describe the signal as a wave traveling down the line and analyse it in the frequency domain. The impedance is consequently represented as a frequency dependant complex function.

For a line terminated in its own characteristic impedance there is no reflection. By definition, terminating in the characteristic impedance has the same effect as an infinitely long line. Any other impedance will result in a reflection. The magnitude of the reflection will be smaller than the magnitude of the incident wave if the terminating impedance is wholly or partly resistive since some of the energy of the incident wave will be absorbed in the resistance. The voltage () across the terminating impedance (), may be calculated by replacing the output of the line with an equivalent generator (figure 4) and is given by [3]

The reflection, must be the exact amount required to make ,

The reflection coefficient, , is defined as

and substituting in the expression for ,

In general is a complex function but the above expression shows that the magnitude is limited to

when

The physical interpretation of this is that the reflection cannot be greater than the incident wave when only passive elements are involved (but see negative resistance amplifier for an example where this condition does not hold). [4] For the special cases described above,

Termination relation
Open circuit
Short circuit


When both and are purely resistive then must be purely real. In the general case when is complex, this is to be interpreted as a shift in phase of the reflected wave relative to the incident wave. [5]

Reactive termination

Another special case occurs when is purely real () and is purely imaginary (), that is, it is a reactance. In this case,

Since

then

showing that all the incident wave is reflected, and none of it is absorbed in the termination, as is to be expected from a pure reactance. There is, however, a change of phase, , in the reflection given by

Discontinuity along line

Fig. 5. Mismatch of transmission line characteristic impedances causes a discontinuity (marked with a star) in the line parameters and results in a reflected wave. Mismatched transmission line.svg
Fig. 5. Mismatch of transmission line characteristic impedances causes a discontinuity (marked with a star) in the line parameters and results in a reflected wave.

A discontinuity, or mismatch, somewhere along the length of the line results in part of the incident wave being reflected and part being transmitted onward in the second section of line as shown in figure 5. The reflection coefficient in this case is given by

In a similar manner, a transmission coefficient, , can be defined to describe the portion of the wave, , that it is transmitted in the forward direction:

Fig. 6. Lumped components or networks connected to the line also cause a discontinuity (marked with a star). Discontinuity on transmission line.svg
Fig. 6. Lumped components or networks connected to the line also cause a discontinuity (marked with a star).

Another kind of discontinuity is caused when both sections of line have an identical characteristic impedance but there is a lumped element, , at the discontinuity. For the example shown (figure 6) of a shunt lumped element,

 
 

Similar expressions can be developed for a series element, or any electrical network for that matter. [6]

Networks

Reflections in more complex scenarios, such as found on a network of cables, can result in very complicated and long lasting waveforms on the cable. Even a simple overvoltage pulse entering a cable system as uncomplicated as the power wiring found in a typical private home can result in an oscillatory disturbance as the pulse is reflected to and from multiple circuit ends. These ring waves as they are known [7] persist for far longer than the original pulse and their waveforms bears little obvious resemblance to the original disturbance, containing high frequency components in the tens of MHz range. [8]

Standing waves

Standing waves on a transmission line with an open-circuit load (top), and a short-circuit load (bottom). Black dots represent electrons, and the arrows show the electric field. Transmission line animation open short2.gif
Standing waves on a transmission line with an open-circuit load (top), and a short-circuit load (bottom). Black dots represent electrons, and the arrows show the electric field.

For a transmission line carrying sinusoidal waves, the phase of the reflected wave is continually changing with distance, with respect to the incident wave, as it proceeds back down the line. Because of this continuous change there are certain points on the line that the reflection will be in phase with the incident wave and the amplitude of the two waves will add. There will be other points where the two waves are in anti-phase and will consequently subtract. At these latter points the amplitude is at a minimum and they are known as nodes. If the incident wave has been totally reflected and the line is lossless, there will be complete cancellation at the nodes with zero signal present there despite the ongoing transmission of waves in both directions. The points where the waves are in phase are anti-nodes and represent a peak in amplitude. Nodes and anti-nodes alternate along the line and the combined wave amplitude varies continuously between them. The combined (incident plus reflected) wave appears to be standing still on the line and is called a standing wave. [9]

The incident wave can be characterised in terms of the line's propagation constant , source voltage , and distance from the source , by

However, it is often more convenient to work in terms of distance from the load () and the incident voltage that has arrived there ().

The negative sign is absent because is measured in the reverse direction back up the line and the voltage is increasing closer to the source. Likewise the reflected voltage is given by

The total voltage on the line is given by

It is often convenient to express this in terms of hyperbolic functions

Similarly, the total current on the line is

The voltage nodes (current nodes are not at the same locations) and anti-nodes occur when

Because of the absolute value bars, the general case analytical solution is tiresomely complicated, but in the case of lossless lines (or lines that are short enough that the losses can be neglected) can be replaced by where is the phase change constant. The voltage equation then reduces to trigonometric functions

and the partial differential of the magnitude of this yields the condition,

Expressing in terms of wavelength, , allows to be solved in terms of :

is purely real when the termination is short circuit or open circuit, or when both and are purely resistive. In those cases the nodes and anti-nodes are given by

which solves for at

For the first point is a node, for the first point is an anti-node and thereafter they will alternate. For terminations that are not purely resistive the spacing and alternation remain the same but the whole pattern is shifted along the line by a constant amount related to the phase of . [10]

Voltage standing wave ratio

The ratio of at anti-nodes and nodes is called the voltage standing wave ratio (VSWR) and is related to the reflection coefficient by

for a lossless line; the expression for the current standing wave ratio (ISWR) is identical in this case. For a lossy line the expression is only valid adjacent to the termination; VSWR asymptotically approaches unity with distance from the termination or discontinuity.

VSWR and the positions of the nodes are parameters that can be directly measured with an instrument called a slotted line. This instrument makes use of the reflection phenomenon to make many different measurements at microwave frequencies. One use is that VSWR and node position can be used to calculate the impedance of a test component terminating the slotted line. This is a useful method because measuring impedances by directly measuring voltages and currents is difficult at these frequencies. [11] [12]

VSWR is the conventional means of expressing the match of a radio transmitter to its antenna. It is an important parameter because power reflected back into a high power transmitter can damage its output circuitry. [13]

Input impedance

The input impedance looking into a transmission line which is not terminated with its characteristic impedance at the far end will be something other than and will be a function of the length of the line. The value of this impedance can be found by dividing the expression for total voltage by the expression for total current given above: [14]

Substituting , the length of the line and dividing through by reduces this to

As before, when considering just short pieces of transmission line, can be replaced by and the expression reduces to trigonometric functions

Applications

There are two structures that are of particular importance which use reflected waves to modify impedance. One is the stub which is a short length of line terminated in a short circuit (or it can be an open circuit). This produces a purely imaginary impedance at its input, that is, a reactance

By suitable choice of length, the stub can be used in place of a capacitor, an inductor or a resonant circuit. [15]

The other structure is the quarter wave impedance transformer. As its name suggests, this is a line exactly in length. Since this will produce the inverse of its terminating impedance [16]

Both of these structures are widely used in distributed element filters and impedance matching networks.

See also

Citations

  1. Carr, pages 70–71
  2. 1 2 3 4 Pai & Zhang, pages 89–96
  3. Matthaei et al., pages 34
  4. Matthaei et al., pages 8–10
  5. Connor, pages 30–31
  6. Matthaei et al., pages 34–35
  7. Term originally defined in IEEE Standard 587 Applicability to Adjustable Frequency Control (Surge Voltages)
  8. Standler, pages 74–76
  9. Connor, pages 28–31
  10. Connor, page 29
  11. Connor, pages 31–32
  12. Engen, pages 73–76
  13. Bowick et al., page 182
  14. Connor, pages 13–14
  15. Connor, pp. 32–35, Matthaei et al., pages 595–605
  16. Matthaei et al., pages 434–435

Related Research Articles

<span class="mw-page-title-main">Characteristic impedance</span> Property of an electrical circuit

The characteristic impedance or surge impedance (usually written Z0) of a uniform transmission line is the ratio of the amplitudes of voltage and current of a single wave propagating along the line; that is, a wave travelling in one direction in the absence of reflections in the other direction. Alternatively, and equivalently, it can be defined as the input impedance of a transmission line when its length is infinite. Characteristic impedance is determined by the geometry and materials of the transmission line and, for a uniform line, is not dependent on its length. The SI unit of characteristic impedance is the ohm.

The propagation constant of a sinusoidal electromagnetic wave is a measure of the change undergone by the amplitude and phase of the wave as it propagates in a given direction. The quantity being measured can be the voltage, the current in a circuit, or a field vector such as electric field strength or flux density. The propagation constant itself measures the change per unit length, but it is otherwise dimensionless. In the context of two-port networks and their cascades, propagation constant measures the change undergone by the source quantity as it propagates from one port to the next.

<span class="mw-page-title-main">Reflection coefficient</span> Measure of wave reflectivity

In physics and electrical engineering the reflection coefficient is a parameter that describes how much of a wave is reflected by an impedance discontinuity in the transmission medium. It is equal to the ratio of the amplitude of the reflected wave to the incident wave, with each expressed as phasors. For example, it is used in optics to calculate the amount of light that is reflected from a surface with a different index of refraction, such as a glass surface, or in an electrical transmission line to calculate how much of the electromagnetic wave is reflected by an impedance discontinuity. The reflection coefficient is closely related to the transmission coefficient. The reflectance of a system is also sometimes called a "reflection coefficient".

In telecommunications, return loss is a measure in relative terms of the power of the signal reflected by a discontinuity in a transmission line or optical fiber. This discontinuity can be caused by a mismatch between the termination or load connected to the line and the characteristic impedance of the line. It is usually expressed as a ratio in decibels (dB);

In radio engineering and telecommunications, standing wave ratio (SWR) is a measure of impedance matching of loads to the characteristic impedance of a transmission line or waveguide. Impedance mismatches result in standing waves along the transmission line, and SWR is defined as the ratio of the partial standing wave's amplitude at an antinode (maximum) to the amplitude at a node (minimum) along the line.

<span class="mw-page-title-main">Transmission line</span> Cable or other structure for carrying radio waves

In electrical engineering, a transmission line is a specialized cable or other structure designed to conduct electromagnetic waves in a contained manner. The term applies when the conductors are long enough that the wave nature of the transmission must be taken into account. This applies especially to radio-frequency engineering because the short wavelengths mean that wave phenomena arise over very short distances. However, the theory of transmission lines was historically developed to explain phenomena on very long telegraph lines, especially submarine telegraph cables.

<span class="mw-page-title-main">Waveguide</span> Structure that guides waves efficiently

A waveguide is a structure that guides waves, such as electromagnetic waves or sound, with minimal loss of energy by restricting the transmission of energy to one direction. Without the physical constraint of a waveguide, wave intensities decrease according to the inverse square law as they expand into three-dimensional space.

<span class="mw-page-title-main">Impedance matching</span> Matching loads to power sources in engineering

In electronics, impedance matching is the practice of designing or adjusting the input impedance or output impedance of an electrical device for a desired value. Often, the desired value is selected to maximize power transfer or minimize signal reflection. For example, impedance matching typically is used to improve power transfer from a radio transmitter via the interconnecting transmission line to the antenna. Signals on a transmission line will be transmitted without reflections if the transmission line is terminated with a matching impedance.

Radiation resistance is that part of an antenna's feedpoint electrical resistance that is caused by the emission of radio waves from the antenna. In radio transmission, a radio transmitter is connected to an antenna. The transmitter generates a radio frequency alternating current which is applied to the antenna, and the antenna radiates the energy in the alternating current as radio waves. Because the antenna is absorbing the energy it is radiating from the transmitter, the antenna's input terminals present a resistance to the current from the transmitter.

<span class="mw-page-title-main">Dipole antenna</span> Antenna consisting of two rod shaped conductors

In radio and telecommunications a dipole antenna or doublet is the simplest and most widely used class of antenna. The dipole is any one of a class of antennas producing a radiation pattern approximating that of an elementary electric dipole with a radiating structure supporting a line current so energized that the current has only one node at each end. A dipole antenna commonly consists of two identical conductive elements such as metal wires or rods. The driving current from the transmitter is applied, or for receiving antennas the output signal to the receiver is taken, between the two halves of the antenna. Each side of the feedline to the transmitter or receiver is connected to one of the conductors. This contrasts with a monopole antenna, which consists of a single rod or conductor with one side of the feedline connected to it, and the other side connected to some type of ground. A common example of a dipole is the "rabbit ears" television antenna found on broadcast television sets.

<span class="mw-page-title-main">Smith chart</span> Electrical engineers graphical calculator

The Smith chart, invented by Phillip H. Smith (1905–1987) and independently by Mizuhashi Tosaku, is a graphical calculator or nomogram designed for electrical and electronics engineers specializing in radio frequency (RF) engineering to assist in solving problems with transmission lines and matching circuits. The Smith chart can be used to simultaneously display multiple parameters including impedances, admittances, reflection coefficients, scattering parameters, noise figure circles, constant gain contours and regions for unconditional stability, including mechanical vibrations analysis. The Smith chart is most frequently used at or within the unity radius region. However, the remainder is still mathematically relevant, being used, for example, in oscillator design and stability analysis. While the use of paper Smith charts for solving the complex mathematics involved in matching problems has been largely replaced by software based methods, the Smith chart is still a very useful method of showing how RF parameters behave at one or more frequencies, an alternative to using tabular information. Thus most RF circuit analysis software includes a Smith chart option for the display of results and all but the simplest impedance measuring instruments can plot measured results on a Smith chart display.

Scattering parameters or S-parameters describe the electrical behavior of linear electrical networks when undergoing various steady state stimuli by electrical signals.

Ripple in electronics is the residual periodic variation of the DC voltage within a power supply which has been derived from an alternating current (AC) source. This ripple is due to incomplete suppression of the alternating waveform after rectification. Ripple voltage originates as the output of a rectifier or from generation and commutation of DC power.

The telegrapher's equations are a pair of coupled, linear partial differential equations that describe the voltage and current on an electrical transmission line with distance and time. The equations come from Oliver Heaviside who developed the transmission line model starting with an August 1876 paper, On the Extra Current. The model demonstrates that the electromagnetic waves can be reflected on the wire, and that wave patterns can form along the line.

<span class="mw-page-title-main">Transmission coefficient</span>

The transmission coefficient is used in physics and electrical engineering when wave propagation in a medium containing discontinuities is considered. A transmission coefficient describes the amplitude, intensity, or total power of a transmitted wave relative to an incident wave.

<span class="mw-page-title-main">Π pad</span> An attenuator whose circuit components are in the shape of the Greek letter pi

The Π pad is a specific type of attenuator circuit in electronics whereby the topology of the circuit is formed in the shape of the Greek capital letter pi (Π).

Image impedance is a concept used in electronic network design and analysis and most especially in filter design. The term image impedance applies to the impedance seen looking into a port of a network. Usually a two-port network is implied but the concept can be extended to networks with more than two ports. The definition of image impedance for a two-port network is the impedance, Zi 1, seen looking into port 1 when port 2 is terminated with the image impedance, Zi 2, for port 2. In general, the image impedances of ports 1 and 2 will not be equal unless the network is symmetrical with respect to the ports.

A quarter-wave impedance transformer, often written as λ/4 impedance transformer, is a transmission line or waveguide used in electrical engineering of length one-quarter wavelength (λ), terminated with some known impedance. It presents at its input the dual of the impedance with which it is terminated.

<span class="mw-page-title-main">Primary line constants</span> Parameters of transmission lines

The primary line constants are parameters that describe the characteristics of conductive transmission lines, such as pairs of copper wires, in terms of the physical electrical properties of the line. The primary line constants are only relevant to transmission lines and are to be contrasted with the secondary line constants, which can be derived from them, and are more generally applicable. The secondary line constants can be used, for instance, to compare the characteristics of a waveguide to a copper line, whereas the primary constants have no meaning for a waveguide.

<span class="mw-page-title-main">Performance and modelling of AC transmission</span>

Performance modelling is the abstraction of a real system into a simplified representation to enable the prediction of performance. The creation of a model can provide insight into how a proposed or actual system will or does work. This can, however, point towards different things to people belonging to different fields of work.

References