IEC 60269

Last updated

In electrical engineering, IEC 60269 is a set of technical standards for low-voltage power fuses. [1] The standard is in four volumes, which describe general requirements, fuses for industrial and commercial applications, fuses for residential applications, and fuses to protect semiconductor devices. The IEC standard unifies several national standards, thereby improving the interchangeability of fuses in international trade. All fuses of different technologies tested to meet IEC standards will have similar time-current characteristics, which simplifies design and maintenance.

Contents


In IEC standards, the replaceable element is called a fuse link and the assembly of fuse link and fuse holder is called a fuse. North American standards call the replaceable element only the fuse.

Application categories and time-current characteristics

IEC 60269 unifies the electrical characteristics of fuses that are dimensionally interchangeable with fuses built to earlier British, German, French or Italian standards. [2] The standard identifies application categories which classify the time-current characteristic of each type of fuse. The application category is a two-digit code.

The second letter indicates the type of equipment or system to be protected:

Any fuses built to the IEC 60269 standard and carrying the same application category (for example, gG or aM) will have similar electrical characteristics, time-current characteristics, and power dissipation as any other, even if the fuses are made in the packages standardized to the earlier national standards. Fuses of the same application category can be substituted for each other provided the voltage rating of the circuit does not exceed the fuse rating.

The tests recommended on Fuses by IEC 60269 are:

  1. Temperature rise & power dissipation test
  2. Non-fusing & Fusing test
  3. Verification of rated current test
  4. Overload test
  5. Verification of Time Current Characteristics and Gates

D type fuses

Diagram of an installed DIAZED fuse Cartridge Fuse.svg
Diagram of an installed DIAZED fuse
DIAZED fuse element D II (right) and screw cap Smeltveiligheid.jpg
DIAZED fuse element D II (right) and screw cap

D-type (Diazed, from German "Diametral abgestuftes zweiteiliges Edisongewinde" for "diametrically graded two-part Edison thread") fuse cartridges have a bottle-shaped ceramic body with metal end caps and are used with screw-in fuse holders. Introduced in 1909 by Siemens, they are available today in five different body sizes, with ratings from 2 A up to 200 A (see table), though only D II and D III fuses are commonly used. The designation of a size consists of the letter D and a Roman numeral. Higher-voltage types rated up to 750 V have increased clearance distances and are longer than lower-voltage-rated fuses. They are available with interrupting ratings up to 50kA RMS, and are intended for use as incoming main protection from an electrical supply utility.

D0-type (Neozed) fuses were introduced in 1967 and use the same concept, but have a smaller, cylindrical body. They are available in three different sizes with ratings from 2 A up to 100 A (see table).

Fuse holders may be secured by screws to a panel, attached to bus bars, or mounted on DIN rails. For the Neozed fuses, there are also fuse bases with integrated disconnecting switches. Changing fuses with the circuit off increases the safety of the user. With new versions of these load disconnecting switches, the fuse cartridges are no longer screwed, but are held by spring clips.

Traditional Diazed fuse holders are made as a conducting metal envelope covered with non-conducting porcelain cover. Under mechanical stress it is possible for the cover to crack partially or fully, uncovering the conducting element. It may happen if a fuse holder was accidentally dropped or someone was using too much force to screw it in. Uncovered metal envelopes present a serious risk of shock and should be replaced immediately under extreme precautions by trained personnel.

The smaller end cap (the "top" of the bottle) has a diameter that varies with the fuse rating: higher ratings have wider end caps. The fixed part of the fuse holder contains a (usually colour-coded) gauge ring, which will accept end caps up to a certain diameter. It is therefore not possible to fit a fuse of a higher rating than allowed for by the gauge ring. The size of the gauge ring is determined by the current rating of the circuit to be protected. Gauge rings are intended to be changed only by authorized personnel.

The larger end cap (the "bottom" of the bottle) has at its centre a small spring-loaded button retained by a thin wire, which serves as a "fuse blown" indicator. When the fuse blows, the wire breaks and the indicator button is ejected by the spring. A missing or displaced indicator thus pinpoints a blown fuse. The removable part of the fuse holder has a small window to allow inspection of the indicator without removal of the fuse. The indicator button usually has a coloured dot indicating the fuse rating (see table).

D- and D0-type fuses are used for protection of circuits up to 500 V AC in residential and commercial installations, and occasionally for the protection of electric motors. The most common operating class is gG (general purpose, formerly gL), but other classes are available. A gG class fuse will typically blow within 2–5 seconds at five times the rated current, and within 0.1–0.2 seconds at ten times the rated current.

Gauge rings and fuse indicators are colour coded for the nominal current:

2 A4 A6 A10 A13 A16 A20 A25 A
  Pink
  Brown
  Green
  Red
  Black
  Grey
  Blue
  Yellow
32 A35 A40 A50 A63 A80 A100 A
  Black
  Black
  Black
  White
  Copper
  Silver
  Red
125 A160 A200 A
  Yellow
  Copper
  Blue

D-system (DIAZED)

D III fuses 50 A, 35 A
D II fuses 25 A, 20 A, 16 A DIAZED fuses.jpg
D III fuses 50 A, 35 A
D II fuses 25 A, 20 A, 16 A
SizeDesignated currentThread
D I (Swiss)2 A, 4 A, 6 A, 10 A, 16 ASE21
D I (NDz)2 A, 4 A, 6 A, 10 A, 16 A, 20 A, 25 AE16
D II2 A, 4 A, 6 A, 10 A, 13 A, 16 A, 20 A, 25 AE27
D III35 A, 40 A, 50 A, 63 AE33
D IV80 A, 100 AG 1¼″
D V125 A, 160 A, 200 AG 2″
D01 fuse cartridge 16A (Neozed) D01-Neozed-16A.png
D01 fuse cartridge 16A (Neozed)
Neozed Fuse block for 3-phase AC 3-poliges Sicherungselement, Einzelteile-2.jpg
Neozed Fuse block for 3-phase AC

D0-System (NEOZED)

Fuses of the D0 system (read as D zero) or NEOZED are smaller than the DIAZED fuses. NEOZED fuses are divided into three sizes.

SizeRated currentThread
D012 A, 4 A, 6 A, 10 A, 13 A, 16 AE14
D0220 A, 25 A, 32 A, 35 A, 40 A, 50 A, 63 AE18
D0380 A, 100 AM 30 × 2

The D03 size is used very rarely, because with these high currents NH fuses have proven to be more reliable. In circuits with a very high prospective short-circuit current level (more than 50kA), D-fuses cannot be used and type NH fuses are used instead.

D01 is nowadays uncommon because miniature circuit breakers are usually used instead for these currents.

NH fuses

NH fuses of sizes 000 and 00, rated 63A and 125A NH 000 00.jpg
NH fuses of sizes 000 and 00, rated 63A and 125A
NH fuses of sizes 1, 2 and 3, rated 250A, 400A and 630A NH 1 2 3.jpg
NH fuses of sizes 1, 2 and 3, rated 250A, 400A and 630A

NH fuses [3] have a square or oblong body and blade-style terminals. These fuses are larger and have higher ratings than the screw type fuses, exceeding 100 kA. NH fuses are widespread in industrial plants as well as in public mains electricity applications, e.g., in electrical substations and electrical distribution boards, or in house junction boxes in buildings.

NH fuses can be changed with power on the circuit, but this requires special training, special tools, and personal protective equipment. An isolation protection mat and isolating gloves may be necessary. Pulling any fuse cartridge under load can cause an electric arc, which may cause serious and fatal injuries without protection equipment. NH disconnecting switches facilitate the safety of cartridge replacement.

NH fuses are manufactured in several current rating ranges.

SizeCurrent range (A)Approx. blade length (mm)
00/0006–16078
06–160125
180–250135
2125–400150
3315–630150
4500–1,000200
4a500–1,250200

British domestic fuses

In British residential installations, cylindrical fuses with a diameter of 14 inch and a length of 1 inch (Ø 6.3 × 25.4 mm) in compliance with British Standard BS 1362 are found inside a standard UK 13 A plug. The specification calls for sand-filled fuses with a ceramic body and metallic contacts at the ends with a 5.5 mm length.

Related Research Articles

<span class="mw-page-title-main">Varistor</span> Electronic component

A varistor is a surge protecting electronic component with an electrical resistance that varies with the applied voltage. It has a nonlinear, non-ohmic current–voltage characteristic that is similar to that of a diode. Unlike a diode however, it has the same characteristic for both directions of traversing current. Traditionally, varistors were indeed constructed by connecting two rectifiers, such as the copper-oxide or germanium-oxide rectifier in antiparallel configuration. At low voltage the varistor has a high electrical resistance which decreases as the voltage is raised. Modern varistors are primarily based on sintered ceramic metal-oxide materials which exhibit directional behavior only on a microscopic scale. This type is commonly known as the metal-oxide varistor (MOV).

<span class="mw-page-title-main">Circuit breaker</span> Automatic circuit protection device

A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by overcurrent. Its basic function is to interrupt current flow to protect equipment and to prevent the risk of fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.

<span class="mw-page-title-main">IEC 60320</span> Set of standards for AC power connectors used on domestic appliances on the appliance side

IEC 60320 Appliance couplers for household and similar general purposes is a set of standards from the International Electrotechnical Commission (IEC) specifying non-locking connectors for connecting power supply cords to electrical appliances of voltage not exceeding 250 V (a.c.) and rated current not exceeding 16 A. Different types of connector are specified for different combinations of current, temperature and earthing requirements. Unlike IEC 60309 connectors, they are not coded for voltage; users must ensure that the voltage rating of the equipment is compatible with the mains supply. The standard uses the term coupler to encompass connectors on power cords and power inlets and outlets built into appliances.

<span class="mw-page-title-main">Surge protector</span> Protects electrical devices from voltage spikes

A surge protector (or spike suppressor, surge suppressor, surge diverter, surge protection device or transient voltage surge suppressor is an appliance or device intended to protect electrical devices from voltage spikes in alternating current circuits. A voltage spike is a transient event, typically lasting 1 to 30 microseconds, that may reach over 1,000 volts. Lightning that hits a power line can give a spike of over 100,000 volts and can burn through wiring insulation and cause fires, but even modest spikes can destroy a wide variety of electronic devices, computers, battery chargers, modems and TVs etc, that happen to be plugged in at the time. Typically the surge device will trigger at a set voltage, around 3 to 4 times the mains voltage, and divert the current to earth. Some devices may absorb the spike and release it as heat. They are generally rated according to the amount of energy in joules they can absorb.

<span class="mw-page-title-main">Fuse (electrical)</span> Electrical safety device that provides overcurrent protection

In electronics and electrical engineering, a fuse is an electrical safety device that operates to provide overcurrent protection of an electrical circuit. Its essential component is a metal wire or strip that melts when too much current flows through it, thereby stopping or interrupting the current. It is a sacrificial device; once a fuse has operated it is an open circuit, and must be replaced or rewired, depending on its type.

AC power plugs and sockets connect electric equipment to the alternating current (AC) mains electricity power supply in buildings and at other sites. Electrical plugs and sockets differ from one another in voltage and current rating, shape, size, and connector type. Different standard systems of plugs and sockets are used around the world.

Appliance classes specify measures to prevent dangerous contact voltages on unenergized parts, such as the metallic casing, of an electronic device. In the electrical appliance manufacturing industry, the following appliance classes are defined in IEC 61140 and used to differentiate between the protective-earth connection requirements of devices.

<span class="mw-page-title-main">Electrical wiring</span> Electrical installation of cabling

Electrical wiring is an electrical installation of cabling and associated devices such as switches, distribution boards, sockets, and light fittings in a structure.

Electrical wiring in the United Kingdom is commonly understood to be an electrical installation for operation by end users within domestic, commercial, industrial, and other buildings, and also in special installations and locations, such as marinas or caravan parks. It does not normally cover the transmission or distribution of electricity to them.

<span class="mw-page-title-main">Current transformer</span> Transformer used to scale alternating current, used as sensor for AC power

A current transformer (CT) is a type of transformer that is used to reduce or multiply an alternating current (AC). It produces a current in its secondary which is proportional to the current in its primary.

<span class="mw-page-title-main">Switchgear</span> Control gear of an electric power system

In an electric power system, a switchgear is composed of electrical disconnect switches, fuses or circuit breakers used to control, protect and isolate electrical equipment. Switchgear is used both to de-energize equipment to allow work to be done and to clear faults downstream. This type of equipment is directly linked to the reliability of the electricity supply.

<span class="mw-page-title-main">Extra-low voltage</span> Electrical standard designed to protect against electric shock

Extra-low voltage (ELV) is an electricity supply voltage and is a part of the Low voltage band in a range which carries a low risk of dangerous electrical shock. There are various standards that define extra-low voltage. The International Electrotechnical Commission (IEC) and the UK IET define an ELV device or circuit as one in which the electrical potential between two conductors or between an electrical conductor and earth (ground) does not exceed 50 V AC or 120 V DC.

Breaking capacity or interrupting rating is the current that a fuse, circuit breaker, or other electrical apparatus is able to interrupt without being destroyed or causing an electric arc with unacceptable duration. The prospective short-circuit current that can occur under short circuit conditions should not exceed the rated breaking capacity of the apparatus, otherwise breaking of the current cannot be guaranteed. The current breaking capacity corresponds to a certain voltage, so an electrical apparatus may have more than one breaking capacity current, according to the actual operating voltage. Breaking current may be stated in terms of the total current or just in terms of the alternating-current (symmetrical) component. Since the time of opening of a fuse or switch is not coordinated with the reversal of the alternating current, in some circuits the total current may be offset and can be larger than the alternating current component by itself. A device may have different interrupting ratings for alternating and direct current.

<span class="mw-page-title-main">Edison screw</span> Lightbulb socket standard (E5-E40)

Edison screw (ES) is a standard lightbulb socket for electric light bulbs. It was developed by Thomas Edison (1847–1931), patented in 1881, and was licensed in 1909 under General Electric's Mazda trademark. The bulbs have right-hand threaded metal bases (caps) which screw into matching threaded sockets. For bulbs powered by AC current, the thread is generally connected to neutral and the contact on the bottom tip of the base is connected to the "live" phase.

<span class="mw-page-title-main">Fuse (automotive)</span> Class of fuses used to protect the wiring and electrical equipment for vehicles

Automotive fuses are a class of fuses used to protect the wiring and electrical equipment for vehicles. They are generally rated for circuits no higher than 32 volts direct current, but some types are rated for 42-volt electrical systems. They are occasionally used in non-automotive electrical products. Automotive fuses are typically housed inside one or more fuse boxes within the vehicle, typically on one side of the engine compartment and/or under the dash near the steering wheel. Some fuses or circuit breakers may nonetheless be placed elsewhere, such as near the cabin fan or air bag controller. They also exist as circuit breakers that are resettable using a switch.

<span class="mw-page-title-main">Utilization categories</span>

In electrical engineering utilization categories are defined by IEC standards and indicate the type of electrical load and duty cycle of the loads to ease selection of contactors and relays.

<span class="mw-page-title-main">Film capacitor</span> Electrical capacitor with an insulating plastic film as the dielectric

Film capacitors, plastic film capacitors, film dielectric capacitors, or polymer film capacitors, generically called film caps as well as power film capacitors, are electrical capacitors with an insulating plastic film as the dielectric, sometimes combined with paper as carrier of the electrodes.

<span class="mw-page-title-main">AC power plugs and sockets: British and related types</span> AC power plug type

Plugs and sockets for electrical appliances not hardwired to mains electricity originated in the United Kingdom in the 1870s and were initially two-pin designs. These were usually sold as a mating pair, but gradually de facto and then official standards arose to enable the interchange of compatible devices. British standards have proliferated throughout large parts of the former British Empire.

References

  1. IEC Standard 60269-1 Ed. 3.0 1998
  2. Charles Mullert, GB 104 IEC 60269 gG & aM Standard Low Voltage Fuses, Ferraz-Shawmut, 2005
  3. (from the German "Niederspannungs Hochleistungs", meaning "low-voltage, high power")