A motor controller is a device or group of devices that can coordinate in a predetermined manner the performance of an electric motor. [1] A motor controller might include a manual or automatic means for starting and stopping the motor, selecting forward or reverse rotation, selecting and regulating the speed, regulating or limiting the torque, and protecting against overloads and electrical faults. Motor controllers may use electromechanical switching, or may use power electronics devices to regulate the speed and direction of a motor.
Motor controllers are used with both direct current and alternating current motors. A controller includes means to connect the motor to the electrical power supply, and may also include overload protection for the motor, and over-current protection for the motor and wiring. A motor controller may also supervise the motor's field circuit, or detect conditions such as low supply voltage, incorrect polarity or incorrect phase sequence, or high motor temperature. Some motor controllers limit the inrush starting current, allowing the motor to accelerate itself and connected mechanical load more slowly than a direct connection. Motor controllers may be manual, requiring an operator to sequence a starting switch through steps to accelerate the load, or may be fully automatic, using internal timers or current sensors to accelerate the motor.
Some types of motor controllers also allow adjustment of the speed of the electric motor. For direct-current motors, the controller may adjust the voltage applied to the motor, or adjust the current flowing in the motor's field winding. Alternating current motors may have little or no speed response to adjusting terminal voltage, so controllers for alternating current instead adjust rotor circuit resistance (for wound rotor motors) or change the frequency of the AC applied to the motor for speed control using power electronic devices or electromechanical frequency changers.
The physical design and packaging of motor controllers is about as varied as that of electric motors themselves. A wall-mounted toggle switch with suitable ratings may be all that is needed for a household ventilation fan. Power tools and household appliances may have a trigger switch that only turns the motor on and off. Industrial motors may be more complex controllers connected to automation systems; a factory may have a large number of motor controllers grouped in a motor control center. Controllers for electric travelling cranes or electric vehicles may be mounted on the mobile equipment. The largest motor controllers are used with the pumping motors of pumped storage hydroelectric plants, and may carry ratings of tens of thousands of horsepower (kilowatts). [2]
Motor controllers can be manually, remotely or automatically operated. They may include only the means for starting and stopping the motor or they may include other functions. [3] [4] [5]
An electric motor controller can be classified by the type of motor it is to drive, such as permanent magnet, servo, series, separately excited, and alternating current.
A motor controller is connected to a power source, such as a battery pack or power supply, and control circuitry in the form of analog or digital input signals.
A small motor can be started by simply connecting it to power. A larger motor requires a specialized switching unit called a motor starter or motor contactor. When energized, a direct on line (DOL) starter immediately connects the motor terminals directly to the power supply. In smaller sizes a motor starter is a manually operated switch; larger motors, or those requiring remote or automatic control, use magnetic contactors. Very large motors running on medium voltage power supplies (thousands of volts) may use power circuit breakers as switching elements.
A direct on line (DOL) or across the line starter applies the full line voltage to the motor terminals. This is the simplest type of motor starter. A DOL motor starter often contains protection devices (see below), and in some cases, condition monitoring. Smaller sizes of direct on-line starters are manually operated; larger sizes use an electromechanical contactor to switch the motor circuit. Solid-state direct on line starters also exist.
A direct on line starter can be used if the high inrush current of the motor does not cause excessive voltage drop in the supply circuit. The maximum size of a motor allowed on a direct on line starter may be limited by the supply utility for this reason. For example, a utility may require rural customers to use reduced-voltage starters for motors larger than 10 kW. [6]
DOL starting is sometimes used to start small water pumps, compressors, fans and conveyor belts. In the case of an asynchronous motor, such as the 3-phase squirrel-cage motor, the motor will draw a high starting current until it has run up to full speed. This starting current is typically 6-7 times greater than the full load current. To reduce the inrush current, larger motors will have reduced-voltage starters or adjustable-speed drives in order to minimise voltage dips to the power supply.
A reversing starter can connect the motor for rotation in either direction. Such a starter contains two DOL circuits — one for clockwise operation and the other for counter-clockwise operation, with mechanical and electrical interlocks to prevent simultaneous closure. [6] For three phase motors, this is achieved by swapping the wires connecting any two phases. Single phase AC motors and direct-current motors often can be reversed by swapping two wires but this is not always the case.
Motor starters other than 'DOL' connect the motor through a resistance to reduce the voltage the motor coils get on start up. The resistance for this needs to be sized to the motor - and a quick source for a good resistance to use is another coil in the motor - i.e. series/parallel. In series gives a gentler start then switched to parallel for full power running. When this is done with three phase motors, it is commonly called a star-delta (US: Y-delta) starter. Old star-delta starters were manually operated and often incorporated an ammeter so the person operating the starter could see when the motor was up to speed by the fact the current it was drawing had stopped decreasing. More modern starters have built-in timers to switch from star to delta and are set by the electrical installer of the machine. The machin's operator simply presses a green button once and the rest of the start procedure is automated.
A typical starter includes protection against overload, both electrical and mechanical, and protection against 'random' starting - if, for instance, the power has been off and has just come back on. An acronym for this type of protection is TONVR - Thermal Overload, No Volt Release. It insists that the green button is pressed to start the motor. The green button switches on a solenoid which closes a contactor (i.e. switch) to primarily power the motor. It also powers the solenoid to keep the power turned on when the green button is released. In a power failure, the contactor opens turning itself and the motor off. The only way the motor can then be started is by pressing the green button. The contactor can be quickly tripped by the starter passing a very high current due to an electrical fault downstream of it in either the wiring to the motor or within the motor. The thermal overload protection consists of a heating element on each power wire which heats a bimetallic strip. The hotter the strip, the more it deflects to the point it pushes a trip bar which disconnects power to the contactor solenoid, turning everything off. Thermal overloads come in different range ratings and this should be chosen to match the motor. Within the range, they are adjustable enabling the installer to set it correctly for the given motor.
Which type for specific applications? DOL gives a quick start so is used more commonly with generally smaller motors. It is also used on machines with an uneven load such as piston type compressors where the full power of the motor is needed to get the piston past the compression stage - the actual working stage. Star-delta is generally used with larger motors or where either the motor is under no load at starting, very little load or a consistent load. It is particularly suited to motors driving machinery with heavy flywheels - to get the flywheels up to speed before the machine is engaged and driven by the flywheel.
Reduced-voltage or soft starters connect the motor to the power supply through a voltage reduction device and increases the applied voltage gradually or in steps. [3] [4] [5] Two or more contactors may be used to provide reduced voltage starting of a motor. By using an autotransformer or a series inductance, a lower voltage is present at the motor terminals, reducing starting torque and inrush current. Once the motor has come up to some fraction of its full-load speed, the starter switches to full voltage at the motor terminals. Since the autotransformer or series reactor only carries the heavy motor starting current for a few seconds, the devices can be much smaller compared to continuously rated equipment. The transition between reduced and full voltage may be based on elapsed time, or triggered when a current sensor shows the motor current has begun to reduce. An autotransformer starter was patented in 1908.
Larger 3 phase induction motors can have their power reduced within the motor ! The motor is started 'DOL' with full voltage supplied to the field coils of the motor outer part ('stator'). The inner part ('rotor') has a current induced into it to once again react with the magnetic field generated by the stator. By breaking the rotor into parts and electrically connecting these parts to external resistances via slip rings and brushes as well as control contactors, the magnetic power of the rotor can be varied - i.e. reduced, for starting or low power running. Although a much more complex process, it means the currents (electrical loads) being switched are significantly lower than if reducing the power to the main feed of the motor.
A third way to achieve a very smooth progressive start is to dip resistance rods into a conductive liquid (e.g. mercury) which has a layer of insulative oil on the top. As the rods are lowered the resistance is gradually reduced.
A star delta starter is another type of Reduced-voltage starter in induction motor. A star delta starter will start a motor with a star connected stator winding. When motor reaches about 80% of its full load speed, it will begin to run in a delta connected stator winding. Star Delta Starter are two types. (1) Manual Operated Star Delta Starter, (2) Automatic Star Delta.
The manual operated star delta starter mainly consists of a TPDP switch which stands for Triple Pole Double Throw switch. This switch changes stator winding from star to delta. During starting condition stator winding is connected in the form of a star. Now we shall see how a star delta starter reduces the starting current of a three-phase induction motor. [7]
The above function achieved by using a power contactor and timer in automatic star delta starter. The automatic star delta starter is manufactured from three contactors, a timer and a thermal overload. The contactors are smaller than the single contactor used in a direct on line starter as they are controlling winding currents only. The currents through the winding are 1/root 3 (58%) of the current in the line. There are two contactors that are close during run, often referred to as the main contractor and the delta contactor. These are AC3 rated at 58% of the current rating of the motor. The third contactor is the star contactor and that only carries star current while the motor is connected in star. The current in star is one third of the current in delta, so this contactor can be AC3 rated at one third (33%) of the motor rating. [8]
The transition from star to delta can be an open transition or a closed transition. During open transition, the motor starter momentarily disconnects from the motor and reconnects in a delta configuration. In closed transition, the transition from the star to delta configuration is achieved without disconnecting the motor. In order to achieve that, an additional three-pole contactor and three resistors are required. [9]
An adjustable-speed drive (ASD) or variable-speed drive (VSD) is an interconnected combination of equipment that provides a means of driving and adjusting the operating speed of a mechanical load. An electrical adjustable-speed drive consists of an electric motor and a speed controller or power converter plus auxiliary devices and equipment. In common usage, the term "drive" is often applied to just the controller. [4] [5] Most modern ASDs and VSDs can also implement soft motor starting. [10]
An Intelligent Motor Controller (IMC) uses a microprocessor to control power electronic devices used for motor control. IMCs monitor the load on a motor and accordingly match motor torque to motor load. This is accomplished by reducing the voltage to the AC terminals and at the same time lowering current and kvar. This can provide a measure of energy efficiency improvement for motors that run under light load for a large part of the time, resulting in less heat, noise, and vibrations generated by the motor.
A starter will contain protective devices for the motor. At a minimum this would include a thermal overload relay. The thermal overload is designed to open the starting circuit and thus cut the power to the motor in the event of the motor drawing too much current from the supply for an extended time. The overload relay has a normally closed contact which opens due to heat generated by excessive current flowing through the circuit. Thermal overloads have a small heating device that increases in temperature as the motor running current increases.
There are two types of thermal overload relay. In one type, a bimetallic strip located close to a heater deflects as the heater temperature rises until it mechanically causes the device to trip and open the circuit, cutting power to the motor should it become overloaded. A thermal overload will accommodate the brief high starting current of a motor while accurately protecting it from a running current overload. The heater coil and the action of the bi-metallic strip introduce a time delay that affords the motor time to start and settle into normal running current without the thermal overload tripping. Thermal overloads can be manually or automatically resettable depending on their application and have an adjuster that allows them to be accurately set to the motor run current.
A second type of thermal overload relay uses a eutectic alloy, like a solder, to retain a spring-loaded contact. When too much current passes through the heating element for too long a time, the alloy melts and the spring releases the contact, opening the control circuit and shutting down the motor. Since eutectic alloy elements are not adjustable, they are resistant to casual tampering but require changing the heater coil element to match the motor rated current. [6]
Electronic digital overload relays containing a microprocessor may also be used, especially for high-value motors. These devices model the heating of the motor windings by monitoring the motor current. They can also include metering and communication functions.
Starters using magnetic contactors usually derive the power supply for the contactor coil from the same source as the motor supply. An auxiliary contact from the contactor is used to maintain the contactor coil energized after the start command for the motor has been released. If a momentary loss of supply voltage occurs, the contactor will open and not close again until a new start command is given. This prevents restarting of the motor after a power failure. This connection also provides a small degree of protection against low power supply voltage and loss of a phase. However, since contactor coils will hold the circuit closed with as little as 80% of normal voltage applied to the coil, this is not a primary means of protecting motors from low voltage operation. [6]
Some devices can be added so that during a voltage drop, the device maintains the current flow that is sufficient for the hold-in coil to keep the contacts closed. The circuit is designed allows current for the hold-in coil for voltage sags down to 15-25% voltage. [11]
After the electrical power has been restored (typically after a time delay of 30 to 60 seconds), then the time sequences of the automatic restarts of multiple motors are set to automatically begin. [12]
Without a time sequenced schedule, any attempt to restart many motors simultaneously could lead to partial or total site wide power failure. [13] [14]
Servo controllers are a wide category of motor control. Common features are:
Servo controllers use position feedback to close the control loop. This is commonly implemented with position encoders, resolvers, and Hall effect sensors to directly measure the rotor's position.
Other position feedback methods measure the back EMF in the undriven coils to infer the rotor position, or detect the Kick-Back voltage transient (spike) that is generated whenever the power to a coil is instantaneously switched off. These are therefore often called "sensorless" control methods.
A servo may be controlled using pulse-width modulation (PWM). How long the pulse remains high (typically between 1 and 2 milliseconds) determines where the motor will try to position itself. Another control method is pulse and direction.
A stepper, or stepping, motor is a synchronous, brushless, high pole count, polyphase motor. Control is usually, but not exclusively, done open loop, i.e., the rotor position is assumed to follow a controlled rotating field. Because of this, precise positioning with steppers is simpler and cheaper than closed loop controls.
Modern stepper controllers drive the motor with much higher voltages than the motor nameplate rated voltage, and limit current through chopping. The usual setup is to have a positioning controller, known as an indexer, sending step and direction pulses to a separate higher voltage drive circuit which is responsible for commutation and current limiting.
A relay is an electrically operated switch. It consists of a set of input terminals for a single or multiple control signals, and a set of operating contact terminals. The switch may have any number of contacts in multiple contact forms, such as make contacts, break contacts, or combinations thereof.
In electrical engineering, the power factor of an AC power system is defined as the ratio of the real power absorbed by the load to the apparent power flowing in the circuit. Real power is the average of the instantaneous product of voltage and current and represents the capacity of the electricity for performing work. Apparent power is the product of root mean square (RMS) current and voltage. Due to energy stored in the load and returned to the source, or due to a non-linear load that distorts the wave shape of the current drawn from the source, the apparent power may be greater than the real power, so more current flows in the circuit than would be required to transfer real power alone. A power factor magnitude of less than one indicates the voltage and current are not in phase, reducing the average product of the two. A negative power factor occurs when the device generates real power, which then flows back towards the source.
A power supply is an electrical device that supplies electric power to an electrical load. The main purpose of a power supply is to convert electric current from a source to the correct voltage, current, and frequency to power the load. As a result, power supplies are sometimes referred to as electric power converters. Some power supplies are separate standalone pieces of equipment, while others are built into the load appliances that they power. Examples of the latter include power supplies found in desktop computers and consumer electronics devices. Other functions that power supplies may perform include limiting the current drawn by the load to safe levels, shutting off the current in the event of an electrical fault, power conditioning to prevent electronic noise or voltage surges on the input from reaching the load, power-factor correction, and storing energy so it can continue to power the load in the event of a temporary interruption in the source power.
A circuit breaker is an electrical safety device designed to protect an electrical circuit from damage caused by overcurrent. Its basic function is to interrupt current flow to protect equipment and to prevent the risk of fire. Unlike a fuse, which operates once and then must be replaced, a circuit breaker can be reset to resume normal operation.
A voltage regulator is a system designed to automatically maintain a constant voltage. It may use a simple feed-forward design or may include negative feedback. It may use an electromechanical mechanism, or electronic components. Depending on the design, it may be used to regulate one or more AC or DC voltages.
A DC motor is an electrical motor that uses direct current (DC) to produce mechanical force. The most common types rely on magnetic forces produced by currents in the coils. Nearly all types of DC motors have some internal mechanism, either electromechanical or electronic, to periodically change the direction of current in part of the motor.
In electrical engineering, an autotransformer is an electrical transformer with only one winding. The "auto" prefix refers to the single coil acting alone. In an autotransformer, portions of the same winding act as both the primary winding and secondary winding sides of the transformer. In contrast, an ordinary transformer has separate primary and secondary windings that are not connected by an electrically conductive path. between them.
A motor–generator is a device for converting electrical power to another form. Motor–generator sets are used to convert frequency, voltage, or phase of power. They may also be used to isolate electrical loads from the electrical power supply line. Large motor–generators were widely used to convert industrial amounts of power while smaller motor–generators were used to convert battery power to higher DC voltages.
Inrush current, input surge current, or switch-on surge is the maximal instantaneous input current drawn by an electrical device when first turned on. Alternating-current electric motors and transformers may draw several times their normal full-load current when first energized, for a few cycles of the input waveform. Power converters also often have inrush currents much higher than their steady-state currents, due to the charging current of the input capacitance. The selection of over-current-protection devices such as fuses and circuit breakers is made more complicated when high inrush currents must be tolerated. The over-current protection must react quickly to overload or short-circuit faults but must not interrupt the circuit when the inrush current flows.
A contactor is an electrically controlled switch used for switching an electrical power circuit. A contactor is typically controlled by a circuit which has a much lower power level than the switched circuit, such as a 24-volt coil electromagnet controlling a 230-volt motor switch.
An electrical ballast is a device placed in series with a load to limit the amount of current in an electrical circuit.
An H-bridge is an electronic circuit that switches the polarity of a voltage applied to a load. These circuits are often used in robotics and other applications to allow DC motors to run forwards or backwards. The name is derived from its common schematic diagram representation, with four switching elements configured as the branches of a letter "H" and the load connected as the cross-bar.
An AC motor is an electric motor driven by an alternating current (AC). The AC motor commonly consists of two basic parts, an outside stator having coils supplied with alternating current to produce a rotating magnetic field, and an inside rotor attached to the output shaft producing a second rotating magnetic field. The rotor magnetic field may be produced by permanent magnets, reluctance saliency, or DC or AC electrical windings.
A motor soft starter is a device used with AC electrical motors to temporarily reduce the load and torque in the powertrain and electric current surge of the motor during start-up. This reduces the mechanical stress on the motor and shaft, as well as the electrodynamic stresses on the attached power cables and electrical distribution network, extending the lifespan of the system.
A brushed DC electric motor is an internally commutated electric motor designed to be run from a direct current power source and utilizing an electric brush for contact.
A magnetic starter is an electromagnetically operated switch which provides a safe method for starting an electric motor with a large load. Magnetic starters also provide under-voltage and overload protection and an automatic cutoff in the event of a power failure.
In electrical engineering, the Korndorfer starter is a technique used for reduced voltage soft starting of induction motors. The circuit uses a three-phase autotransformer and three three-phase switches. This motor starting method has been updated and improved by Hilton Raymond Bacon.
A motor control center (MCC) is an assembly to control some or all electric motors in a central location. It consists of multiple enclosed sections having a common power bus and with each section containing a combination starter, which in turn consists of motor starter, fuses or circuit breaker, and power disconnect. A motor control center can also include push buttons, indicator lights, variable-frequency drives, programmable logic controllers, and metering equipment. It may be combined with the electrical service entrance for the building.
A voltage controller, also called an AC voltage controller or AC regulator is an electronic module based on either thyristors, triodes for alternating current, silicon-controlled rectifiers or insulated-gate bipolar transistors, which converts a fixed voltage, fixed frequency alternating current (AC) electrical input supply to obtain variable voltage in output delivered to a resistive load. This varied voltage output is used for dimming street lights, varying heating temperatures in homes or industry, speed control of fans and winding machines and many other applications, in a similar fashion to an autotransformer. Voltage controller modules come under the purview of power electronics. Because they are low-maintenance and very efficient, voltage controllers have largely replaced such modules as magnetic amplifiers and saturable reactors in industrial use.