TV pickup

Last updated

TV pickup is a phenomenon in the United Kingdom that involves surges in demand on the electrical grid, occurring when a large number of people simultaneously watch the same television programme. TV pickup occurs when viewers take advantage of commercial breaks in programming to operate electrical appliances at the same time, causing large synchronised surges in national electricity consumption. Such sudden huge surges in demand tied to the TV schedule are unique to the United Kingdom. [1] [2]

Contents

Electricity networks devote considerable resources to predicting and providing supply for these events, which typically impose an extra demand of around 200–400 megawatts (MW) on the British National Grid. Short-term supply is often obtained from pumped storage reservoirs, which can be quickly brought online, and are backed up by the slower fossil fuel and nuclear power stations. The largest ever pickup occurred on 4 July 1990, when a 2800 megawatt demand was imposed by the ending of the penalty shootout in the England v West Germany FIFA World Cup semi-final. [3] [4] In addition to pickups, the Grid also prepares for synchronised switch-offs during remembrance and energy-awareness events.

Cause

TV pickups occur during breaks in popular television programmes and are a surge in demand caused by the switching on of millions of electric kettles to "brew up" cups of tea or coffee. Kettles in the UK are particularly high powered, typically consuming 2.5–3.0kW and create a very high peak demand on the electrical grid. The phenomenon is common in the UK, where individual programmes can often attract a significantly large audience share. [3] The introduction of a wider range of TV channels is mitigating the effect, but it remains a large concern for the National Grid operators. [3]

There are typically several large peaks in energy use caused by TV pickup during each day, dependent on TV schedules, the day of the week and weather. [5] The largest pickup of the day is usually at 21:00, when several popular TV programmes end or go to commercial breaks. [5] The most popular programmes, hence those giving the greatest pickup are soaps, sporting events, and reality TV. A typical TV pickup imposes an extra demand of 200–400  megawatts, with larger soap storylines bringing around 700–800 MW. [3]

Response

A sudden increase in demand, unmatched by an increase in supply, causes a drop in the mains frequency across the Grid (locally the voltage may also be affected due to changes in reactive power flows). [6]

The National Grid Energy Balancing Team is responsible for ensuring an adequate supply of electricity and try to ensure a frequency of between 49.5 and 50.5 Hz is maintained. [5] [7] [8] To prepare for pickups the team runs a computer program that compares the current day with corresponding periods over the past five years to predict the size of demand, [3] and studies TV schedules to anticipate demand from popular shows. Grid employees must also be familiar with popular soap-opera storylines as one might cause a sudden rise in demand. Owing to this, they are aware of what shows attract the largest audiences and of customers' television choices; one expressed his disapproval in 2013, "The TV pickup from Deal or No Deal is gobsmackingly high. How sad is that?" [8]

Sporting events like tennis matches are especially difficult because of the impossibility of predicting when one will end. [8] International football finals are a particular problem as research has shown that 71% of people in the UK will watch them at home instead of public venues such as pubs. [4] The Grid predicted a pickup of around 3000 MW, equivalent to 1.2 million kettles being turned on at once, if England made the later stages of the 2010 FIFA World Cup. [4] [9]

Diagram of a typical pumped storage power station Raccoon Mountain Pumped-Storage Plant.svg
Diagram of a typical pumped storage power station

It is important to predict demand as precisely as possible as electricity grids are not capable of storing electricity in large quantities and all power stations have a lead-in time before generation can begin. [10] Balancing teams attempt to meet short term fluctuations with "fast reserves" that are quick to come online, backed up with longer term fossil fuel-based "balance mechanism units". [5] The shortest lead-in times are on pumped storage reservoirs, such as the Dinorwig Power Station that has the fastest response time of any pumped storage station in the world at just 12 seconds to produce 1320 MW. [10] Once the longer term fossil fuel stations, which have response times around half an hour, and nuclear power stations, which can take even longer, come online then pumped storage stations can be turned off and the water returned to the reservoir. [10] If capacity further exceeds demand, additional power is accessible via the HVDC Cross-Channel undersea power cable that connects the UK and France. [11]

Records

The largest TV pickups recorded in the UK are:

Pickup demandDateProgramme
2800 MW4 July 1990 England v West Germany FIFA World Cup semi-final penalty shootout [3] [12]
2600 MW22 January 1984 The Thorn Birds [3] – Final episode [13]
2570 MW21 June 2002 England v Brazil FIFA World Cup quarter-final [3]
2340 MW12 June 2002 Nigeria v England FIFA World Cup group match [14]
2290 MW5 April 2001 EastEnders [3] – "Who Shot Phil?" [12]
2200 MW16 January 1984 The Thorn Birds [15] – Episode 4/5 [16]
2200 MW20 July 1989 The Thorn Birds [17]
2200 MW5 August 1985 Dallas [17]
2200 MW28 April 1991 The Darling Buds of May [15]
2200 MW12 May 1991 The Darling Buds of May [12]
2200 MW18 April 1994 EastEnders & Coronation Street (combined) [15]
2110 MW22 November 2003 England v Australia Rugby World Cup Final [12]
2100 MW30 June 1998 Argentina v England FIFA World Cup round of 16 half time [15]
2100 MW19 February 1986 The Colbys [17]
2010 MW7 April 2002 Coronation Street [17]
2000 MW1 April 1991 Coronation Street [15]
2000 MW3 July 1990 Italy v Argentina FIFA World Cup semi-final [14]
2000 MW2 April 1984 Coronation Street & Blue Thunder (combined) [17]
1960 MW1 July 2006 England v Portugal FIFA World Cup quarter-final [14]
1900 MW5 April 1994 EastEnders [15]
1830 MW20 June 2006 Sweden v England FIFA World Cup group match [14]
1820 MW21 April 1999 Juventus v Manchester United UEFA Champions League semi-final [14]
1820 MW21 June 2002 England v Brazil FIFA World Cup quarter-final [14]
1800 MW29 July 1981 Wedding of Prince Charles and Lady Diana Spencer [15]
1800 MW2 September 1992 Coronation Street [15]
1800 MW3 September 1992 EastEnders [15]
1800 MW7 September 1992 Coronation Street [15]
1800 MW11 July 2021 England v Italy UEFA European Football Championship final [18]
1700 MW25 June 2006 England v Ecuador FIFA World Cup round of 16 [14]
1600 MW29 April 2011 Wedding of Prince William and Catherine Middleton [12]
1400 MW11 July 2018 England v Croatia FIFA World Cup semi-final [19]
1400 MW7 July 2018 England v Sweden FIFA World Cup quarter-final [20]
1400 MW7 July 2021 England v Denmark UEFA European Football Championship semi-final [21]
1200 MW3 July 2018 England v Colombia FIFA World Cup round of 16 [22]
1000 MW20 November 1995"An Interview with HRH The Princess of Wales" [23]
950 MW16 April 2020 Clap for Our Carers [12]
700 MW29 June 1994 Charles: The Private Man, the Public Role [23]

Other events can cause even bigger pickups for the National Grid than television events. Immediately following the solar eclipse of 11 August 1999 there was a record demand of 3000 MW. [24] This was the largest rapid increase that the grid had ever experienced but it had been anticipated and sufficient generating plant were made ready to accommodate the additional demand. Around 1000 MW of the demand was due to traditional TV pick-up demand caused by kettles, with the remainder arising from the return of people to their workplaces. [25]

The Grid also plans for the opposite effect, a co-ordinated mass switch-off of appliances. Boxing Day is consistently, according to one employee, "the lowest of the low" power usage. [8] At midday on 5 January 2005 a three minutes silence in remembrance of the Boxing Day Tsunami resulted in a 1300 MW temporary drop in consumption followed by a sudden 1400 MW rise. [26] The 6 September 1997 funeral of Diana, Princess of Wales caused a 1000 MW drop. [15]

Similar, though smaller, switch-offs occur annually at 11 am on Remembrance Day. [3] These switch-offs occur during the day time, so they are smaller than pickups seen at night when more electrical appliances are likely to be in use. [3] National Grid argued against the mass switch-off originally planned for the Live Earth and Planet Aid events as these would have resulted in highly unpredictable demands for electricity and would have generated more carbon dioxide than would have been saved. These events were subsequently cancelled. [3]

The imposition of national lockdowns during the COVID-19 pandemic also affected the National Grid. Despite the trend towards streaming services reducing the magnitude of traditional pick-ups, televised pandemic statements such as by the Queen and Prime Minister Boris Johnson still attracted a large number of live viewers. For the Queen's 5 April 2020 address a pick-up of between 500 and 600 MW was recorded at the end of the event. The weekly Clap for Our Carers also saw a marginal dip in demand as people went outside followed by a peak in demand of around 1000 MW as people returned inside. During the lockdown periods demand for power overall was around 20% lower than usual owing to home working and furlough. [27]

See also

Related Research Articles

<span class="mw-page-title-main">Pumped-storage hydroelectricity</span> Electric energy storage system

Pumped-storage hydroelectricity (PSH), or pumped hydroelectric energy storage (PHES), is a type of hydroelectric energy storage used by electric power systems for load balancing. The method stores energy in the form of gravitational potential energy of water, pumped from a lower elevation reservoir to a higher elevation. Low-cost surplus off-peak electric power is typically used to run the pumps. During periods of high electrical demand, the stored water is released through turbines to produce electric power. Although the losses of the pumping process make the plant a net consumer of energy overall, the system increases revenue by selling more electricity during periods of peak demand, when electricity prices are highest. If the upper lake collects significant rainfall or is fed by a river then the plant may be a net energy producer in the manner of a traditional hydroelectric plant.

<span class="mw-page-title-main">Dinorwig Power Station</span> Dam in Dinorwig, Wales

The Dinorwig Power Station, known locally as Electric Mountain, or Mynydd Gwefru, is a pumped-storage hydroelectric scheme, near Dinorwig, Llanberis in Snowdonia national park in Gwynedd, north Wales. The scheme can supply a maximum power of 1,728 MW (2,317,000 hp) and has a storage capacity of around 9.1 GWh (33 TJ).

<span class="mw-page-title-main">HVDC Cross-Channel</span>

The HVDC Cross-Channel is the 73 km long high-voltage direct current (HVDC) interconnector that operates since 1986 under the English Channel between the continental European grid at Bonningues-lès-Calais and the British electricity grid at Sellindge. The cable is also known as IFA, and should not be confused with the new IFA-2, another interconnect with France that is three times as long but only half as powerful.

<span class="mw-page-title-main">National Grid (Great Britain)</span> High-voltage electric power transmission network in Great Britain

In the electricity sector in the United Kingdom, the National Grid is the high-voltage electric power transmission network serving Great Britain, connecting power stations and major substations and ensuring that electricity generated anywhere on it can be used to satisfy demand elsewhere. The network covers the great majority of Great Britain and several of the surrounding islands. It does not cover Northern Ireland, which is part of a single electricity market with the Republic of Ireland.

<span class="mw-page-title-main">Electricity sector in India</span> Power generation and distribution

India is the third largest producer of electricity in the world. During the fiscal year (FY) 2021–22, the total electricity generation in the country was 1,719 TWh, of which 1,484 TWh was generated by utilities.

<span class="mw-page-title-main">Grid energy storage</span> Large scale electricity supply management

Grid energy storage is a collection of methods used for energy storage on a large scale within an electrical power grid. Electrical energy is stored during times when electricity is plentiful and inexpensive or when demand is low, and later returned to the grid when demand is high, and electricity prices tend to be higher.

<span class="mw-page-title-main">Electric Reliability Council of Texas</span> Regional transmission organization in Texas

The Electric Reliability Council of Texas, Inc. (ERCOT) is an American organization that operates Texas's electrical grid, the Texas Interconnection, which supplies power to more than 25 million Texas customers and represents 90 percent of the state's electric load. ERCOT is the first independent system operator (ISO) in the United States. ERCOT works with the Texas Reliability Entity (TRE), one of eight regional entities within the North American Electric Reliability Corporation (NERC) that coordinate to improve reliability of the bulk power grid.

<span class="mw-page-title-main">Hybrid power</span> Combinations between different technologies to generate electric power

Hybrid power are combinations between different technologies to produce power.

<span class="mw-page-title-main">Solar power in India</span>

Solar power is a fast developing industry in India. The country's solar installed capacity was 63.303 GWAC as of 31 December 2022. Solar power generation in India ranks fourth globally in 2021.

<span class="mw-page-title-main">Load management</span> Process of balancing the supply of electricity on a network

Load management, also known as demand-side management (DSM), is the process of balancing the supply of electricity on the network with the electrical load by adjusting or controlling the load rather than the power station output. This can be achieved by direct intervention of the utility in real time, by the use of frequency sensitive relays triggering the circuit breakers, by time clocks, or by using special tariffs to influence consumer behavior. Load management allows utilities to reduce demand for electricity during peak usage times, which can, in turn, reduce costs by eliminating the need for peaking power plants. In addition, some peaking power plants can take more than an hour to bring on-line which makes load management even more critical should a plant go off-line unexpectedly for example. Load management can also help reduce harmful emissions, since peaking plants or backup generators are often dirtier and less efficient than base load power plants. New load-management technologies are constantly under development — both by private industry and public entities.

<span class="mw-page-title-main">Cruachan Power Station</span> Dam in Argyll and Bute

The Cruachan Power Station is a pumped-storage hydroelectric power station in Argyll and Bute, Scotland. The scheme can provide 440 MW of power and produced 705 GWh in 2009.

<span class="mw-page-title-main">Electricity sector in the United Kingdom</span> Overview of the electricity sector in the United Kingdom

The United Kingdom has a National Grid that covers most of mainland Great Britain and several of the surrounding islands, as well as some connectivity to other countries. The electrical sector supplies power at 50 Hz AC, and ~240 volts is supplied to consumers. In 2020 the electricity sector's grid supply came from 55% low-carbon power, 36.1% fossil fuelled power, and 8.4% imports. Renewable power is showing strong growth, while fossil fuel generator use in general and coal use in particular is shrinking, with historically dominant coal generators now mainly being run in winter due to pollution and costs, and contributed just 1.6% of the supply in 2020.

South Australia is a leader in utility-scale renewable energy generation, and also produces gas and uranium for electricity generation. Gas production is mostly concentrated in the Cooper Basin in the state's north-east. Gas is delivered from these fields by pipeline to users interstate and to Port Adelaide where it fuels three separate gas-fired power plants. Uranium is also mined in South Australia, though nuclear power generation is prohibited nationally. The Olympic Dam mine is the world's single largest known deposit of uranium and represents 30% of the world's total uranium resource. Many utility-scale wind farms and solar farms have been commissioned during the 21st century and geology with potential for geothermal energy has also been identified but is yet to be developed.

Lithuania is a net energy importer. Primary energy use in Lithuania was 98 TWh, or 29 TWh per million people in 2009.

<span class="mw-page-title-main">Hydroelectricity in the United Kingdom</span>

As of 2018, hydroelectric power stations in the United Kingdom accounted for 1.87 GW of installed electrical generating capacity, being 2.2% of the UK's total generating capacity and 4.2% of UK's renewable energy generating capacity. This includes four conventional hydroelectric power stations and run-of-river schemes for which annual electricity production is approximately 5,000 GWh, being about 1.3% of the UK's total electricity production. There are also pumped-storage hydroelectric power stations providing a further 2.8 GW of installed electrical generating capacity, and contributing up to 4,075 GWh of peak demand electricity annually.

<span class="mw-page-title-main">Solar power in Denmark</span>

Solar power in Denmark is at 2,339 MW (grid-connected) by mid-2022, and contributes to a goal to use 100% renewable energy by 2050. The goal of 200 MW of photovoltaics by 2020 was reached eight years early, in 2012, and 36 MW was being installed each month. Denmark had 790 MW in late 2015. A total of 3,400 MW is expected to be installed by 2030. Many solar-thermal district heating plants exist and are planned in Denmark.

<span class="mw-page-title-main">Energy in California</span> Overview of the use of energy in California, U.S.

Energy in California is a major area of the economy of California. California is the state with the largest population and the largest economy in the United States. It is second in energy consumption after Texas. As of 2018, per capita consumption was the fourth-lowest in the United States partially because of the mild climate and energy efficiency programs.

<span class="mw-page-title-main">Electricity sector in Australia</span>

The Australian electricity sector has been historically dominated by coal-fired power stations, but renewables are forming a rapidly growing fraction of supply.

<span class="mw-page-title-main">Battery storage power station</span> Energy storage system using electrochemical secondary cells

A battery storage power station is a type of energy storage power station that uses a group of batteries to store electrical energy. Battery storage is the fastest responding dispatchable source of power on electric grids, and it is used to stabilise those grids, as battery storage can transition from standby to full power in under a second to deal with grid contingencies.

References

  1. Britain peak power demand (from BBC TV series: Britain from Above) , retrieved 2022-04-16
  2. "Does the UK Really Experience Massive Power Surges When Soap Operas Finish from People Making Tea?". Today I Found Out. 2017-05-28. Retrieved 2022-04-19.
  3. 1 2 3 4 5 6 7 8 9 10 11 12 "Can you have a big 'switch off'?". BBC News. 6 September 2007. Archived from the original on 30 September 2021. Retrieved 30 October 2010.
  4. 1 2 3 "National Grid anticipates power surges during World Cup". The Daily Telegraph. London. 11 June 2010. Archived from the original on 13 June 2010. Retrieved 31 October 2010.
  5. 1 2 3 4 Easton, Nick. "A Day in the Life of an Operational Energy Manager" (PDF). National Grid Transco. Archived from the original (PDF) on 7 February 2010. Retrieved 31 October 2010.
  6. "Notes for guidance" (PDF). National STEM Centre. Archived from the original (PDF) on 14 March 2012. Retrieved 6 November 2010.
  7. "Balancing Services Open Day" (PDF). National Grid. Archived from the original (PDF) on 7 February 2010. Retrieved 6 November 2010.
  8. 1 2 3 4 Carrington, Damian (2013-12-20). "Strictly Come Dancing: National Grid prepares for biggest surge of the year". The Guardian. Archived from the original on 2015-01-20. Retrieved 2016-12-13.
  9. "News Roundup for June 14". Electric Co-op. Archived from the original on 2011-07-18. Retrieved 6 November 2010.
  10. 1 2 3 Darvill, Andy. "Pumped Storage Reservoirs: Storing energy to cope with big demands". Archived from the original on 1 September 2010. Retrieved 31 October 2010.
  11. Manton, Keegan (22 October 2021). "TV Pickup | Why Britain Throws Millions of Gallons of Water From Enormous Mountains". A Life of Mastery. Archived from the original on 22 October 2021. Retrieved 22 October 2021.
  12. 1 2 3 4 5 6 "7 of the biggest TV moments in UK electricity history". Drax Group Plc. 6 October 2016. Archived from the original on 14 October 2017. Retrieved 31 May 2017.
  13. "The Thorn Birds". The Radio Times Archive. BBC. 1984. p. 27. Archived from the original on 14 October 2017. Retrieved 14 October 2017.
  14. 1 2 3 4 5 6 7 Miller, Toby (2017). Greenwashing Sport. Taylor & Francis. p. 63. ISBN   9781317333470. Archived from the original on 2021-09-30. Retrieved 2020-10-01.
  15. 1 2 3 4 5 6 7 8 9 10 11 Hornby, Win; Gammie, Robert; Wall, Stuart (2001). Business Economics. Financial Times Prentice Hall. ISBN   9780273646037. Archived from the original on 2021-09-30. Retrieved 2020-10-01.
  16. "The Thorn Birds". The Radio Times Archive. BBC. 1984. p. 27. Archived from the original on 14 October 2017. Retrieved 14 October 2017.
  17. 1 2 3 4 5 Patel, Raj (2013). Stuffed And Starved. Granta Publications. ISBN   9781846275050. Archived from the original on 2021-09-30. Retrieved 2020-10-01.
  18. "National Grid ESO on Twitter". Twitter. 12 July 2021. Archived from the original on 12 July 2021. Retrieved 12 July 2021.
  19. "National Grid Media on Twitter". Twitter. Archived from the original on 2021-03-08. Retrieved 2018-07-12.
  20. "National Grid Media on Twitter". Twitter. 7 July 2018. Archived from the original on 31 August 2020. Retrieved 3 September 2018.
  21. "National Grid ESO on Twitter". Twitter. 8 July 2021. Archived from the original on 8 July 2021. Retrieved 8 July 2021.
  22. "National Grid Media on Twitter". Twitter. 3 July 2018. Archived from the original on 8 March 2021. Retrieved 4 July 2018.
  23. 1 2 Montalbano, William D. (21 November 1995). "Princess Diana, in TV Interview, Vows a 'Fight to the End'". Los Angeles Times. Retrieved 20 August 2022.
  24. "BBC News: Eclipse sparks record power surge". BBC. Archived from the original on 4 September 2017. Retrieved 10 July 2012.
  25. Hornby, Win; Gammie, Robert; Wall, Stuart (2001). Business Economics. 206: Financial Times Prentice Hall. ISBN   9780273646037. Archived from the original on 2021-09-30. Retrieved 2020-10-01.{{cite book}}: CS1 maint: location (link)
  26. Batsone, Dorcas. "Introduction Seminar – ELEXON, the BSC arrangements and the electricity industry" (PDF). Elexon. Retrieved 31 October 2010.[ dead link ]
  27. "4 ways lockdown life affected UK electricity use | National Grid Group". National Grid. Retrieved 24 January 2022.