Water cooling

Last updated

Cooling tower and water discharge of a nuclear power plant KKP Auslauf.jpg
Cooling tower and water discharge of a nuclear power plant

Water cooling is a method of heat removal from components and industrial equipment. Evaporative cooling using water is often more efficient than air cooling. Water is inexpensive and non-toxic; however, it can contain impurities and cause corrosion.

Contents

Water cooling is commonly used for cooling automobile internal combustion engines and power stations. Water coolers utilising convective heat transfer are used inside high-end personal computers to lower the temperature of CPUs and other components.

Other uses include the cooling of lubricant oil in pumps; for cooling purposes in heat exchangers; for cooling buildings in HVAC and in chillers.

Mechanism

Advantages

Water is inexpensive, non-toxic, and available over most of the earth's surface. Liquid cooling offers higher thermal conductivity than air cooling. Water has unusually high specific heat capacity among commonly available liquids at room temperature and atmospheric pressure allowing efficient heat transfer over distance with low rates of mass transfer. Cooling water may be recycled through a recirculating system or used in a single-pass once-through cooling (OTC) system. Water's high enthalpy of vaporization allows the option of efficient evaporative cooling to remove waste heat in cooling towers or cooling ponds. [1] Recirculating systems are open if they rely upon evaporative cooling or closed if heat removal is accomplished in heat exchangers, thus with negligible evaporative loss. A heat exchanger or condenser may separate non-contact cooling water from a fluid being cooled, [2] or contact cooling water may directly impinge on items like saw blades where phase difference allows easy separation. Environmental regulations emphasize the reduced concentrations of waste products in non-contact cooling water. [3]

Disadvantages

Water accelerates the corrosion of metal parts and is a favorable medium for biological growth. Dissolved minerals in natural water supplies are concentrated by evaporation to leave deposits called scale. Cooling water often requires the addition of chemicals to minimize corrosion and insulating deposits of scale and biofouling. [4]

Water contains varying amounts of impurities from contact with the atmosphere, soil, and containers. Being both an electrical conductor and a solvent for metal ions and oxygen, water can accelerate corrosion of machinery being cooled. Corrosion reactions proceed more rapidly as temperature increases. [4] Preservation of machinery in the presence of hot water has been improved by addition of corrosion inhibitors including zinc, chromates and phosphates. [5] [6] The first two have toxicity concerns; [7] and the last has been associated with eutrophication. [8] Residual concentrations of biocides and corrosion inhibitors are of potential concern for OTC and blowdown from open recirculating cooling water systems. [9] With the exception of machines with short design life, closed recirculating systems require periodic cooling-water treatment or replacement raising similar concern about ultimate disposal of cooling water containing chemicals used with environmental safety assumptions of a closed system. [10]

Biofouling occurs because water is a favorable environment for many life forms. Flow characteristics of recirculating cooling water systems encourage colonization by sessile organisms using the circulating supply of food, oxygen and nutrients. [11] Temperatures may become high enough to support thermophilic populations of organisms such as types of fungi. [12] Biofouling of heat exchange surfaces can reduce heat transfer rates of the cooling system, and biofouling of cooling towers can alter flow distribution to reduce evaporative cooling rates. Biofouling may also create differential oxygen concentrations increasing corrosion rates. OTC and open recirculating systems are more susceptible to biofouling. Biofouling may be inhibited by temporary habitat modifications. Temperature differences may discourage the establishment of thermophilic populations in intermittently operated facilities, and intentional short-term temperature spikes may periodically kill less tolerant populations. Biocides have been commonly used to control biofouling where sustained facility operation is required. [13]

Chlorine may be added in the form of hypochlorite to decrease biofouling in cooling water systems, but is later reduced to chloride to minimize the toxicity of blowdown or OTC water returned to natural aquatic environments. Hypochlorite is increasingly destructive to wooden cooling towers as pH increases. Chlorinated phenols have been used as biocides or leached from preserved wood in cooling towers. Both hypochlorite and pentachlorophenol have reduced effectiveness at pH values greater than 8. [14] Non-oxidizing biocides may be more difficult to detoxify prior to release of blowdown or OTC water to natural aquatic environments. [15]

Concentrations of polyphosphates or phosphonates with zinc and chromates or similar compounds have been maintained in cooling systems to keep heat exchange surfaces clean enough that a film of gamma iron oxide and zinc phosphate can inhibit corrosion by passivating anodic and cathodic reaction points. [16] These increase salinity and total dissolved solids, and phosphorus compounds may provide the limiting essential nutrient for algal growth contributing to biofouling of the cooling system or to eutrophication of natural aquatic environments receiving blowdown or OTC water. Chromates reduce biofouling in addition to effective corrosion inhibition in the cooling water system, but residual toxicity in blowdown or OTC water has encouraged lower chromate concentrations and the use of less-flexible corrosion inhibitors. [7] Blowdown may also contain chromium leached from cooling towers constructed of wood preserved with chromated copper arsenate. [17]

Total dissolved solids or TDS (sometimes called filterable residue) is reported as the mass of residue remaining when a measured volume of filtered water is evaporated. [18] Salinity indicates water density or conductivity changes caused by dissolved materials. [19] Probability of scale formation increases with increasing total dissolved solids. Solids commonly associated with scale formation are calcium and magnesium both as carbonate and sulfate. Corrosion rates initially increase with salinity in response to increasing electrical conductivity, but then decrease after reaching a peak as higher levels of salinity decrease dissolved oxygen levels. [4]

Some groundwater contains very little oxygen when pumped from wells, but most natural water supplies include dissolved oxygen. Increasing oxygen concentrations accelerate corrosion. [4] Dissolved oxygen approaches saturation levels in cooling towers. It is beneficial in blowdown or OTC water being returned to natural aquatic environments. [20]

Water ionizes into hydronium (H3O+) cations and hydroxide (OH) anions. The concentration of ionized hydrogen (as protonated water) in a cooling water system is reported as the pH level. [21] Low pH values increase the rate of corrosion; high pH values encourage scale formation. Amphoterism is uncommon among metals used in water cooling systems, but aluminum corrosion rates increase with pH values above 9. Galvanic corrosion may be severe in water systems with copper and aluminum components. Acid can be added to cooling water systems to prevent scale formation if the pH decrease will offset increased salinity and dissolved solids. [22]

Steam power stations

The Indian Point Energy Center. Over a billion fish eggs and larvae are killed in its cooling system each year. Indian Point.jpg
The Indian Point Energy Center. Over a billion fish eggs and larvae are killed in its cooling system each year.
Cooling water intake of a nuclear power plant KKP Einlauf.jpg
Cooling water intake of a nuclear power plant

Few other cooling applications approach the large volumes of water required to condense low-pressure steam at power stations. [24] Many facilities, particularly electric power plants, use millions of gallons of water per day for cooling. [25] Water cooling on this scale may alter natural water environments and create new environments. Thermal pollution of rivers, estuaries and coastal waters is a consideration when siting such plants. Water returned to aquatic environments at temperatures higher than the ambient receiving water modifies aquatic habitat by increasing biochemical reaction rates and decreasing the oxygen saturation capacity of the habitat. Temperature increases initially favor a population shift from species requiring the high-oxygen concentration of cold water to those enjoying the advantages of increased metabolic rates in warm water. [11]

Once-through cooling (OTC) systems may be used on very large rivers or at coastal and estuarine sites. These power stations put the waste heat into the river or coastal water. These OTC systems thus rely upon an ample supply of river water or seawater for their cooling needs. Such facilities are built with intake structures designed for bringing in large volumes of water at a high rate of flow. These structures tend to also pull in large numbers of fish and other aquatic organisms, which are killed or injured on the intake screens. [26] Large flow rates may trap slow-swimming organisms including fish and shrimp on screens protecting the small bore tubes of the heat exchangers from blockage. High temperatures or pump turbulence and shear may kill or disable smaller organisms that pass through the screens entrained with the cooling water. [27] :Ch. A2 More than 1,200 power plants and manufacturing facilities in the U.S. use OTC systems; [28] :4–4 the intake structures kill billions of fish and other organisms each year. [29] More-agile aquatic predators consume organisms impinged on the screens; and warm water predators and scavengers colonize the cooling water discharge to feed on entrained organisms.

The U.S. Clean Water Act required the Environmental Protection Agency (EPA) to issue regulations on industrial cooling water intake structures. [30] EPA issued final regulations for new facilities in 2001 (amended 2003), [26] [31] and for existing facilities in 2014. [32]

Cooling towers

A Marley mechanical induced draft cooling tower A Marley industrial cooling tower.jpg
A Marley mechanical induced draft cooling tower

As an alternative to OTC, industrial cooling towers may use recirculated river water, coastal water (seawater), or well water. Large mechanical induced-draft or forced-draft cooling towers in industrial plants continuously circulate cooling water through heat exchangers and other equipment where the water absorbs heat. That heat is then rejected to the atmosphere by the evaporation of some of the water in cooling towers where upflowing air contacts the downflowing water. The loss of evaporated water into the air exhausted to the atmosphere is replaced by "make-up" fresh river water or fresh cooling water, but the amount of water lost during evaporative cooling may affect the natural habitat for aquatic organisms. Because the evaporated pure water is replaced by make-up water containing carbonates and other dissolved salts, a portion of the circulating water is continuously discarded as "blowdown" water to minimize the excessive build-up of salts in the circulating water; these blowdown wastes may change the receiving water quality. [33]

Internal combustion engines

The heated coolant mixture can be used to warm the air inside the car by means of the heater core. Also, the water jacket around an engine is very effective at deadening mechanical noises, making the engine quieter.

Open method

An antique gasoline engine with an evaporative cooler and mesh screen to improve evaporation. Water is pumped up to the top and flows down the screen to the tank. Moore-single-cylinder-gasoline-engine.jpg
An antique gasoline engine with an evaporative cooler and mesh screen to improve evaporation. Water is pumped up to the top and flows down the screen to the tank.

An open water cooling system makes use of evaporative cooling, lowering the temperature of the remaining (unevaporated) water. This method was common in early internal combustion engines until scale buildup was observed from dissolved salts and minerals in the water. Modern open cooling systems continuously waste a fraction of recirculating water as blowdown to remove dissolved solids at concentrations low enough to prevent scale formation. Some open systems use inexpensive tap water, but this requires higher blowdown rates than deionized or distilled water. Purified water systems still require blowdown to remove the accumulation of byproducts of chemical treatment to prevent corrosion and biofouling. [34]

Pressurization

Water for cooling has a boiling point temperature of around 100 degrees C at atmospheric pressure. Engines operating at higher temperatures may require a pressurized recycle loop to prevent overheating. [35] Modern automotive cooling systems often operate at 15 psi (103 kPa) to raise the boiling-point of the recycling water coolant and reduce evaporative losses. [36]

Antifreeze

The use of water cooling carries the risk of damage from freezing. Automotive and many other engine cooling applications require the use of a water and antifreeze mixture to lower the freezing point to a temperature unlikely to be experienced. Antifreeze also inhibits corrosion from dissimilar metals and can increase the boiling point, allowing a wider range of water cooling temperatures. [36] Its distinctive odor also alerts operators to cooling system leaks and problems that would go unnoticed in a water-only cooling system.

Other additives

Other less common chemical additives are products to reduce surface tension. These additives are meant to increase the efficiency of automotive cooling systems. Such products are used to enhance the cooling of underperforming or undersized cooling systems or in racing where the weight of a larger cooling system could be a disadvantage.[ citation needed ]

Power electronics and transmitters

Since approximately 1930 it is common to use water cooling for tubes of powerful transmitters. As these devices use high operation voltages (around 10 kV), the use of deionized water is required and it has to be carefully controlled. Modern solid-state transmitters can be built so that even high-power transmitters do not require water cooling. Water cooling is however also sometimes used for thyristors of HVDC valves, for which the use of deionized water is required.[ citation needed ]

Liquid cooling maintenance

CoolIT Rack DCLC AHx Liquid Cooling Solution (c) CoolIT Rack DCLC AHx Liquid Cooling Solution.jpg
CoolIT Rack DCLC AHx Liquid Cooling Solution

Liquid cooling techniques are increasingly being used for the thermal management of electronic components. This type of cooling is a solution to ensure the optimisation of energy efficiency while simultaneously minimising noise and space requirements. Especially useful in supercomputers or Data Centers because maintenance of the racks is quick and easy. After disassembly of the rack, advanced-technology quick-release couplings eliminate spillage for the safety of operators and protect the integrity of fluids (no impurities in the circuits). These couplings are also capable of being locked (Panel mounted?) to allow blind connection in difficult-to-access areas.[ citation needed ] It is important in electronics technology to analyse the connection systems to ensure:

Computer usage

GPU waterblock on an Nvidia 1080 Ti Watercool Heatkiller IV waterblock for Titan X mounted on 1080 Ti.jpg
GPU waterblock on an Nvidia 1080 Ti
This 60 mm diameter by 10 mm high impingement-type water-cooled copper cold plate (heat sink) animation shows temperature contoured flow trajectories, predicted using a CFD analysis package. CFD Water Cooled Copper Cold Plate.gif
This 60 mm diameter by 10 mm high impingement-type water-cooled copper cold plate (heat sink) animation shows temperature contoured flow trajectories, predicted using a CFD analysis package.

Water cooling often adds complexity and cost in comparison to air cooling design by requiring a pump, tubing or piping to transport the water, and a radiator, often with fans, to reject the heat to the atmosphere. Depending on the application, water cooling may create an additional element of risk where leakage from the water coolant recycle loop can corrode or short-circuit sensitive electronic components.

The primary advantage of water cooling for cooling CPU cores in computing equipment is transporting heat away from the source to a secondary cooling surface to allow for large, more optimally designed radiators rather than small, relatively inefficient fins mounted directly on the heat source. Cooling hot computer components with various fluids has been in use since at least the Cray-2 in 1982, which used Fluorinert. Through the 1990s, water cooling for home PCs slowly gained recognition among enthusiasts, but it became noticeably more prevalent after the introduction of the first Gigahertz-clocked processors in the early 2000s. As of 2018, there are dozens of manufacturers of water cooling components and kits, and many computer manufacturers include preinstalled water cooling solutions for their high-performance systems.

Water cooling can be used for many computer components, but usually it is used for the CPU and GPUs. Water cooling typically uses a water block, a water pump, and a water-to-air heat exchanger. By transferring device heat to a separate larger heat exchanger using larger, lower-speed fans, water cooling can allow quieter operation, improved processor speeds (overclocking), or a balance of both. Less commonly, Northbridges, Southbridges, hard disk drives, memory, voltage regulator modules (VRMs), and even power supplies can be water-cooled. [37]

Internal radiator size may vary: from 40 mm dual fan (80 mm) to 140 quad fan (560 mm) and thickness from 30 mm to 80 mm. Radiator fans may be mounted on one or both sides. External radiators can be much larger than their internal counterparts as they do not need to fit in the confines of a computer case. High-end cases may have two rubber grommeted ports in the back for the inlet and outlet hoses, which allow external radiators to be placed far away from the PC.

Typical 2000s single-waterblock DIY watercooling setup in a PC utilizing a T-Line PC watercooling T-Line-2009-12-03.jpg
Typical 2000s single-waterblock DIY watercooling setup in a PC utilizing a T-Line

A T-Line is used to remove trapped air bubbles from the circulating water. It is made with a t-connector and a capped-off length of tubing. The tube n acts as a mini-reservoir and allows air bubbles to travel into it as they are caught into the "tee" connector, and ultimately removed from the system by bleeding. The capped line may be capped with a fill-port fitting to allow the release of trapped gas and the addition of liquid. [ citation needed ]

Water coolers for desktop computers were, until the end of the 1990s, homemade. They were made from car radiators (or more commonly, a car's heater core), aquarium pumps and home-made water blocks, laboratory-grade PVC and silicone tubing and various reservoirs (homemade using plastic bottles, or constructed using cylindrical acrylic or sheets of acrylic, usually clear) and or a T-Line. More recently[ when? ] a growing number of companies are manufacturing water-cooling components compact enough to fit inside a computer case. [38] This, and the trend to CPUs of higher power dissipation, has greatly increased the popularity of water cooling.

Dedicated overclockers have occasionally used vapor-compression refrigeration or thermoelectric coolers in place of more common standard heat exchangers. Water cooling systems in which water is cooled directly by the evaporator coil of a phase change system are able to chill the circulating coolant below the ambient air temperature (impossible with a standard heat exchanger) and, as a result, generally provide superior cooling of the computer's heat-generating components. The downside of phase-change or thermoelectric cooling is that it uses much more electricity, and antifreeze must be added due to the low temperature. Additionally, insulation, usually in the form of lagging around water pipes and neoprene pads around the components to be cooled, must be used in order to prevent damage caused by condensation of water vapour from the air on chilled surfaces. Common places from which to obtain the required phase transition systems are a household dehumidifier or air conditioner. [39]

An alternative cooling scheme, which also enables components to be cooled below the ambient temperature while obviating the requirement for antifreeze and lagged pipes, is to place a thermoelectric device (commonly referred to as a 'Peltier junction' or 'pelt' after Jean Peltier, who documented the effect) between the heat-generating component and the water block. Because the only sub-ambient temperature zone now is at the interface with the heat-generating component itself, insulation is required only in that localized area. The disadvantage of such a system is higher power dissipation.[ citation needed ]

To avoid damage from condensation around the Peltier junction, a proper installation requires it to be "potted" with silicone epoxy. The epoxy is applied around the edges of the device, preventing air from entering or leaving the interior.[ citation needed ]

Apple's Power Mac G5 was the first mainstream desktop computer to have water cooling as standard (although only on its fastest models). Dell followed suit by shipping their XPS computers with liquid cooling[ citation needed ], using thermoelectric cooling to help cool the liquid. Currently, Dell's only computers to offer liquid cooling are their Alienware desktops. [40]

Asus are the first and only mainstream brand to have put water-cooled laptops into mass production. Those laptops have a built-in air/water hybrid cooling system and can be docked to an external liquid cooling radiator for additional cooling and electrical power. [41] [42]

Ships and boats

Water is an ideal cooling medium for vessels as they are constantly surrounded by water that generally remains at a low temperature throughout the year. Systems operating with seawater need to be manufactured from cupronickel, bronze, titanium or similarly corrosion-resistant materials. Water containing sediment may require velocity restrictions through piping to avoid erosion at high velocity or blockage by settling at low velocity. [43]

Other applications

Plant transpiration and animal perspiration use evaporative cooling to prevent high temperatures from causing unsustainable metabolic rates.

Machine guns used in fixed defensive positions sometimes use water cooling to extend barrel life through periods of rapid fire, but the weight of the water and pumping system significantly reduces the portability of water-cooled firearms. Water-cooled machine guns were extensively used by both sides during World War I; however, by the end of the war lighter weapons that rivaled the firepower, effectiveness and reliability of water-cooled models began to appear on the battlefield. Thus water-cooled weapons have played a far lesser role in subsequent conflicts.

A hospital in Sweden relies on snow-cooling from melt-water to cool its data centers, medical equipment, and maintain a comfortable ambient temperature. [44]

Some nuclear reactors use heavy water as coolant. Heavy water is employed in nuclear reactors because it is a weaker neutron absorber. This allows for the use of less-enriched fuel. For the main cooling system, normal water is preferably employed through the use of a heat exchanger, as heavy water is much more expensive. Reactors that use other materials for moderation (graphite) may also use normal water for cooling.

High-grade industrial water (produced by reverse osmosis or distillation) and potable water are sometimes used in industrial plants requiring high-purity cooling water. Production of these high-purity waters creates waste byproduct brines containing the concentrated impurities from the source water.

In 2018, researchers from the University of Colorado Boulder and University of Wyoming invented a radiative cooling metamaterial known as "RadiCold", which has been developed since 2017. This metamaterial aids in cooling of water and increasing the efficiency of power generation, in which it would cool the underneath objects, by reflecting away the sun's rays while at the same time allowing the surface to discharge its heat as infrared thermal radiation. [45]

See also

Related Research Articles

<span class="mw-page-title-main">Radiator</span> Type of heat exchanger; radiant body through water or other liquids

A radiator is a heat exchanger used to transfer thermal energy from one medium to another for the purpose of cooling and heating. The majority of radiators are constructed to function in cars, buildings, and electronics.

<span class="mw-page-title-main">Intercooler</span> Heat exchanger used to cool a gas after compression

An intercooler is a heat exchanger used to cool a gas after compression. Often found in turbocharged engines, intercoolers are also used in air compressors, air conditioners, refrigeration and gas turbines.

<span class="mw-page-title-main">Evaporative cooler</span> Device that cools air through the evaporation of water

An evaporative cooler is a device that cools air through the evaporation of water. Evaporative cooling differs from other air conditioning systems, which use vapor-compression or absorption refrigeration cycles. Evaporative cooling exploits the fact that water will absorb a relatively large amount of heat in order to evaporate. The temperature of dry air can be dropped significantly through the phase transition of liquid water to water vapor (evaporation). This can cool air using much less energy than refrigeration. In extremely dry climates, evaporative cooling of air has the added benefit of conditioning the air with more moisture for the comfort of building occupants.

<span class="mw-page-title-main">Cooling tower</span> Device which rejects waste heat to the atmosphere through the cooling of a water stream

A cooling tower is a device that rejects waste heat to the atmosphere through the cooling of a coolant stream, usually a water stream, to a lower temperature. Cooling towers may either use the evaporation of water to remove heat and cool the working fluid to near the wet-bulb air temperature or, in the case of dry cooling towers, rely solely on air to cool the working fluid to near the dry-bulb air temperature using radiators.

<span class="mw-page-title-main">Chiller</span> Machine that removes heat from a liquid coolant via vapor compression

A chiller is a machine that removes heat from a liquid coolant via a vapor-compression, adsorption refrigeration, or absorption refrigeration cycles. This liquid can then be circulated through a heat exchanger to cool equipment, or another process stream. As a necessary by-product, refrigeration creates waste heat that must be exhausted to ambience, or for greater efficiency, recovered for heating purposes. Vapor compression chillers may use any of a number of different types of compressors. Most common today are the hermetic scroll, semi-hermetic screw, or centrifugal compressors. The condensing side of the chiller can be either air or water cooled. Even when liquid cooled, the chiller is often cooled by an induced or forced draft cooling tower. Absorption and adsorption chillers require a heat source to function.

<span class="mw-page-title-main">Computer cooling</span> The process of removing waste heat from a computer

Computer cooling is required to remove the waste heat produced by computer components, to keep components within permissible operating temperature limits. Components that are susceptible to temporary malfunction or permanent failure if overheated include integrated circuits such as central processing units (CPUs), chipsets, graphics cards, hard disk drives, and solid state drives.

<span class="mw-page-title-main">Thermal pollution</span> Water temperature changes resulting in degraded water quality

Thermal pollution, sometimes called "thermal enrichment", is the degradation of water quality by any process that changes ambient water temperature. Thermal pollution is the rise or drop in the temperature of a natural body of water caused by human influence. Thermal pollution, unlike chemical pollution, results in a change in the physical properties of water. A common cause of thermal pollution is the use of water as a coolant by power plants and industrial manufacturers. Urban runoff—stormwater discharged to surface waters from rooftops, roads, and parking lots—and reservoirs can also be a source of thermal pollution. Thermal pollution can also be caused by the release of very cold water from the base of reservoirs into warmer rivers.

<span class="mw-page-title-main">Thermal power station</span> Power plant that generates electricity from heat energy

A thermal power station, also known as a thermal power plant, is a type of power station in which the heat energy generated from various fuel sources is converted to electrical energy. The heat from the source is converted into mechanical energy using a thermodynamic power cycle. The most common cycle involves a working fluid heated and boiled under high pressure in a pressure vessel to produce high-pressure steam. This high pressure-steam is then directed to a turbine, where it rotates the turbine's blades. The rotating turbine is mechanically connected to an electric generator which converts rotary motion into electricity. Fuels such as natural gas or oil can also be burnt directly in gas turbines, skipping the steam generation step. These plants can be of the open cycle or the more efficient combined cycle type.

<span class="mw-page-title-main">Thermosiphon</span> Method of heat exchange in which convection drives pumpless circulation

A thermosiphon is a device that employs a method of passive heat exchange based on natural convection, which circulates a fluid without the necessity of a mechanical pump. Thermosiphoning is used for circulation of liquids and volatile gases in heating and cooling applications such as heat pumps, water heaters, boilers and furnaces. Thermosiphoning also occurs across air temperature gradients such as those occurring in a wood-fire chimney or solar chimney.

<span class="mw-page-title-main">Fouling</span> Accumulation of unwanted material on solid surfaces

Fouling is the accumulation of unwanted material on solid surfaces. The fouling materials can consist of either living organisms or a non-living substance (inorganic). Fouling is usually distinguished from other surface-growth phenomena in that it occurs on a surface of a component, system, or plant performing a defined and useful function and that the fouling process impedes or interferes with this function.

There are many uses of water in industry and, in most cases, the used water also needs treatment to render it fit for re-use or disposal. Raw water entering an industrial plant often needs treatment to meet tight quality specifications to be of use in specific industrial processes. Industrial water treatment encompasses all these aspects which include industrial wastewater treatment, boiler water treatment and cooling water treatment.

<span class="mw-page-title-main">Boiler water</span>

Boiler water is liquid water within a boiler, or in associated piping, pumps and other equipment, that is intended for evaporation into steam. The term may also be applied to raw water intended for use in boilers, treated boiler feedwater, steam condensate being returned to a boiler, or boiler blowdown being removed from a boiler.

Economizers, or economisers (UK), are mechanical devices intended to reduce energy consumption, or to perform useful function such as preheating a fluid. The term economizer is used for other purposes as well. Boiler, power plant, heating, refrigeration, ventilating, and air conditioning (HVAC) may all use economizers. In simple terms, an economizer is a heat exchanger.

<span class="mw-page-title-main">Boiler feedwater</span>

Boiler feedwater is the water which is supplied to a boiler. The feed water is put into the steam drum from a feed pump. In the steam drum the feed water is then turned into steam from the heat. After the steam is used, it is then dumped to the main condenser. From the condenser, it is then pumped to the deaerated feed tank. From this tank it then goes back to the steam drum to complete its cycle. The feedwater is never open to the atmosphere. This cycle is known as a closed system or Rankine cycle.

<span class="mw-page-title-main">Radiator (engine cooling)</span> Heat exchangers used for cooling internal combustion engines

Radiators are heat exchangers used for cooling internal combustion engines, mainly in automobiles but also in piston-engined aircraft, railway locomotives, motorcycles, stationary generating plants or any similar use of such an engine.

HVAC is a major sub discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary.

Quenching, in the context of pollution scrubbers, refers to the cooling of hot exhaust gas by water sprays before it enters the scrubber proper. Hot gases are often cooled to near the saturation level. If not cooled, the hot gas stream can evaporate a large portion of the scrubbing liquor, adversely affecting collection efficiency and damaging scrubber internal parts. If the gases entering the scrubber are too hot, some liquid droplets may evaporate before they have a chance to contact pollutants in the exhaust stream, and others may evaporate after contact, causing captured particles to become reentrained. In some cases, quenching can actually save money. Cooling the gases reduces the temperature and, therefore, the volume of gases, permitting the use of less expensive construction materials and a smaller scrubber vessel and fan.

<span class="mw-page-title-main">Boiler blowdown</span> Wastewater removal of impurities from boilers

Boiler blowdown is water intentionally wasted from a boiler to avoid concentration of impurities during continuing evaporation of steam. The water is blown out of the boiler with some force by steam pressure within the boiler. Bottom blowdown used with early boilers caused abrupt downward adjustment of boiler water level and was customarily expelled downward to avoid the safety hazard of showering hot water on nearby individuals.

<span class="mw-page-title-main">Hygroscopic cycle</span> Thermodynamic cycle converting thermal energy into mechanical power

The Hygroscopic cycle is a thermodynamic cycle converting thermal energy into mechanical power by the means of a steam turbine. It is similar to the Rankine cycle using water as the motive fluid but with the novelty of introducing salts and their hygroscopic properties for the condensation. The salts are desorbed in the boiler or steam generator, where clean steam is released and superheated in order to be expanded and generate power through the steam turbine. Boiler blowdown with the concentrated hygroscopic compounds is used thermally to pre-heat the steam turbine condensate, and as reflux in the steam-absorber.

Heat exchangers are devices that transfer heat to achieve desired heating or cooling. An important design aspect of heat exchanger technology is the selection of appropriate materials to conduct and transfer heat fast and efficiently.

References

  1. Kemmer (1979), pp. 1–1, 1–2.
  2. Kemmer (1979), pp. 38–1, 38–4, 38-7 & 38-8.
  3. King (1995), pp. 143, 439.
  4. 1 2 3 4 Betz, pp. 183–184.
  5. Hemmasian-Ettefagh, Ali (2010). "Corrosion Inhibition of Carbon Steel in Cooling Water". Materials Performance. 49: 60–65.
  6. Mahgoub, F.M.; Abdel-Nabey, B.A.; El-Samadisy, Y.A. (March 2010). "Adopting a multipurpose inhibitor to control corrosion of ferrous alloys in cooling water systems". Materials Chemistry and Physics. 120 (1): 104–108. doi:10.1016/j.matchemphys.2009.10.028. ISSN   0254-0584.
  7. 1 2 Kemmer (1979), pp. 38–20, 38–21.
  8. Goldman & Horne (1983), pp. 153, 160.
  9. Betz, p. 215.
  10. Krosofsky, Andrew (18 January 2021). "How to Properly and Safely Dispose of Antifreeze". Green Matters. Retrieved 23 June 2021.
  11. 1 2 Reid (1961), pp. 267–268.
  12. Jones, E.B.G.; Eaton, R.A. (1969). "Savoryella lignicola gen. et sp. nov. from water cooling towers". Transactions of the British Mycological Society. 52: 161–174. doi:10.1016/S0007-1536(69)80169-5.
  13. Betz, p. 202.
  14. Betz, pp. 203–209.
  15. Veil, John A.; Rice, James K.; Raivel, Mary E.S. "Biocide Usage in Cooling Towers in the Electric Power and Petroleum Refining Industries" (PDF). United States Department of Energy. Retrieved 23 June 2021.
  16. Betz, pp. 198–199.
  17. "Leaching of CCA From Treated Wood". National Pesticide Information Center. Retrieved 23 June 2021.
  18. Franson (1975), pp. 89–98.
  19. Franson (1975), pp. 99–100.
  20. "Dissolved Oxygen and water quality". State of Kentucky. Retrieved 23 June 2021.
  21. Franson (1975), pp. 406–407.
  22. Betz, pp. 191–194.
  23. McGeehan, Patrick (12 May 2015). "Fire Prompts Renewed Calls to Close the Indian Point Nuclear Plant". New York Times.
  24. U.S. Environmental Protection Agency (EPA). (1997). Profile of the Fossil Fuel Electric Power Generation Industry (Report). Washington, D.C. Document No. EPA/310-R-97-007. p. 79.
  25. EPA (2010). "Partial List of Facilities Subject to Clean Water Act 316(b)."
  26. 1 2 EPA (2014). "Cooling Water Intakes."
  27. Economic and Benefits Analysis for the Final Section 316(b) Phase II Existing Facilities Rule (PDF) (Report). EPA. 2004. EPA 821-R-04-005.
  28. Technical Development Document for the Final Section 316(b) Existing Facilities Rule (PDF) (Report). EPA. May 2014. EPA 821-R-14-002.
  29. Final Regulations to Establish Requirements for Cooling Water Intake Structures at Existing Facilities; Fact sheet (PDF) (Report). EPA. May 2014. EPA 821-F-14-001. Archived from the original (PDF) on 19 June 2020. Retrieved 23 November 2015.
  30. United States. Clean Water Act, Section 316(b), 33 U.S.C.   § 1316.
  31. EPA. Cooling Water Intake Structures. Final rule: 2001-12-18, 66 FR 65255. Amended: 2003-06-19, 68 FR 36749.
  32. EPA. "National Pollutant Discharge Elimination System—Final Regulations To Establish Requirements for Cooling Water Intake Structures at Existing Facilities and Amend Requirements at Phase I Facilities" Final rule. Federal Register,79 FR 48300. 2014-08-15.
  33. Beychok, Milton R. (1967). Aqueous Wastes from Petroleum and Petrochemical Plants (1st ed.). John Wiley and Sons. LCCN   67019834. (See Chapter 2 for material balance relationships in a cooling tower)
  34. Betz, p. 192.
  35. Sturgess, Steve (August 2009). "Column: Keep Your Cool". Heavy Duty Trucking. Retrieved 2 April 2018.
  36. 1 2 Nice, Karim (22 November 2000). "How Car Cooling Systems Work". HowStuffWorks. HowStuffWorks, Inc. Retrieved 20 August 2012.
  37. "Koolance 1300/1700W Liquid-Cooled Power Supply". Koolance.com. 22 March 2008. Retrieved 19 January 2018.
  38. "Featured Projects – LiquidHaus". 6 May 2022. Archived from the original on 6 May 2022. Retrieved 6 May 2022.
  39. "Dehumidifier & Air Conditioner". extremeoverclocking.com. 5 April 2011. Retrieved 11 March 2018.
  40. "Alienware Desktops". Dell. Archived from the original on 28 July 2012. Retrieved 5 November 2009.
  41. hermesauto (16 August 2016). "The Asus ROG GX800 is a water-cooled gaming laptop with two graphics chips". The Straits Times. Retrieved 7 May 2021.
  42. "Asus ROG GX800VH Watercooled Laptop Review | KitGuru" . Retrieved 7 May 2021.
  43. Thermex "Heat Exchanger FAQ Page" 2016-12-12.
  44. "Snow cooling in Sundsvall". www.lvn.se (in Swedish). Retrieved 20 August 2017.
  45. Dongliang Zhao; Ablimit Aili; Yao Zhai; Jiatao Lu; Dillon Kidd; Gang Tan; Xiaobo Yin; Ronggui Yang (26 October 2018). "Subambient Cooling of Water: Toward Real-World Applications of Daytime Radiative Cooling". Joule. 3: 111–123. doi: 10.1016/j.joule.2018.10.006 .

Bibliography