Fire pump

Last updated
A vertical turbine type fire pump with a diesel engine attached on the right Vertturbdslfirepump.jpg
A vertical turbine type fire pump with a diesel engine attached on the right
Antique Japanese fire pump Antique Japanese Fire pump.jpg
Antique Japanese fire pump
Horse-drawn fire pump given to Brockhampton Estate in 1818 Brockhampton Estate - horse-drawn fire pump.jpg
Horse-drawn fire pump given to Brockhampton Estate in 1818
The portable fire pump normal pressure (PFPN) was standard equipment in many Zuk A-15 fire engines; ca. 1977 TS 8 2023 07 04 JM (4).jpg
The portable fire pump normal pressure (PFPN) was standard equipment in many Żuk A-15 fire engines; ca. 1977

A fire pump usually refers to a pressure-increasing component of the water supply for fixed-place fire suppression systems such as fire sprinklers, standpipes, and foam systems. Fire pumps are also a critical component integrated into fire trucks and fire boats, and serve a similar purpose boosting water supplies for firefighting hose operations.

Contents

Description

Fire pumps are used to increase the pressure of water sourced from a municipal underground water supply piping network, or a static supply (e.g., tank, reservoir, lake). A fire pump is a centrifugal- or positive displacement- pump that has been tested and listed by a third-party testing and listing agency, such as UL or FM Global specifically for fire service use. The main standard that governs fire pump fixed-place installations in North America is the National Fire Protection Association's NFPA 20 Standard for the Installation of Stationary Fire Pumps for Fire Protection. [1]

Fire pumps are powered most commonly by an electric motor or a diesel engine, or, occasionally a steam turbine. If the governing model building code requires backup power independent of the local electric power grid, a fire pump using an electric motor may utilize an emergency generator when connected via a listed transfer switch. Fire pumps installed on fire trucks and boats are powered by the engine of the vehicle/vessel.

Utilizing a control panel with pressure sensors, fire pumps automatically start when the pressure in the fire sprinkler system drops below a pre-designated threshold. Given the incompressibility of water, fire suppression system pressures drops significantly and quickly when one or more outlets open. Examples would be fused (opened) fire sprinklers, fire hose valves connected to a standpipe, or automatic control valves opened by release panels.

Fire pumps are utilized when determined by hydraulic calculations that the existing water supply cannot provide sufficient pressure to meet the hydraulic design requirements of the suppression system. This usually occurs if the building is very tall, such as in high-rise buildings (to overcome hydraulic head losses created from elevation differences), in systems that require a relatively high terminal pressure at the fire suppression outlets (to provide sufficient water droplet penetration of a fire plume), or in systems that require a large discharge of water (such as storage warehouses). Fire pumps are also needed if fire protection water supply is provided from a static source which provides little or no pressure. Some situations may be compounded by all of these factors, requiring large water supplies and powerful fire pumps.

Common types of fire pumps used for fire service include: horizontal split case, vertical split case, vertical inline, vertical turbine, and end suction.

Fire pumps, circulation relief valve

Each pump shall have a circulation relief valve listed for the fire pump service installed and set below the shutoff pressure at minimum expected suction pressure. Exception: This rule shall not apply to engine-driven pumps for which engine cooling water is taken from the pump discharge. [2]

Jockey pump

A jockey pump, also known as a pressure-maintenance pump, is a small pump connected to a fire suppression system near the fire pump and is intended to maintain pressure in a fire protection piping system. These pumps recover pressures lost from gradual, slow pressure declines in a system due to temperature changes, trapped air escapement, or very small leaks. The jockey pump is essentially a portion of the fire pump's control system. A jockey pump is sized for a flow less than one sprinkler in order to ensure a system pressure drop significant enough to start the main fire pump. Jockey pumps are typically small multistage centrifugal pumps, and do not have to be listed or certified for fire system application. The control equipment for jockey pumps may however carry approvals. Jockey pumps should be sized for 3% of the flow of the main fire pump and to provide 10psi more pressure than the main fire pump (As per Code IS 15105 : 2002)

In the United States, the application of a jockey pump in a fire protection system is provided by NFPA 20. They are inspected per NFPA 25 "Inspection and Testing of Water-Based Fire Protection Systems".

In India, the pump manufacturers generally adhere to the TAC (Tariff Advisory Committee) guidelines, although pump manufacturers also obtain listings with UL or FM Global. For the purpose of installation & maintenance of fire-fighting pumps, Bureau of Indian Standards has published IS 15301 which is being followed throughout India.

Related Research Articles

<span class="mw-page-title-main">Fire engine</span> Emergency vehicle intended to put out fires

A fire engine is a road vehicle that functions as a firefighting apparatus. The primary purposes of a fire engine include transporting firefighters and water to an incident as well as carrying equipment for firefighting operations. Some fire engines have specialized functions, such as wildfire suppression and aircraft rescue and firefighting, and may also carry equipment for technical rescue.

<span class="mw-page-title-main">Fire hose</span> Flexible tube used for delivering water or foam at high pressure, to fight fires

A fire hose is a high-pressure hose that carries water or other fire retardant to a fire to extinguish it. Outdoors, it attaches either to a fire engine, fire hydrant, or a portable fire pump. Indoors, it can permanently attach to a building's standpipe or plumbing system.

<span class="mw-page-title-main">Fire sprinkler system</span> Fire protection method

A fire sprinkler system is an active fire protection method, consisting of a water supply system providing adequate pressure and flowrate to a water distribution piping system, to which fire sprinklers are connected. Although initially used only in factories and large commercial buildings, systems for homes and small buildings are now available at a cost-effective price.

<span class="mw-page-title-main">Fire hydrant</span> Connection point by which firefighters can tap into a water supply

A fire hydrant, fireplug, or firecock (archaic) is a connection point by which firefighters can tap into a water supply. It is a component of active fire protection. Underground fire hydrants have been used in Europe and Asia since at least the 18th century. Above-ground pillar-type hydrants are a 19th-century invention.

<span class="mw-page-title-main">Backflow prevention device</span> Device that prevents undesired water flow

A backflow prevention device is used to protect potable water supplies from contamination or pollution due to backflow.

<span class="mw-page-title-main">Standpipe (firefighting)</span> Firefighting water supply

A standpipe or riser is a type of rigid water piping which is built into multi-story buildings in a vertical position, or into bridges in a horizontal position, to which fire hoses can be connected, allowing manual application of water to the fire. Within the context of a building or bridge, a standpipe serves the same purpose as a fire hydrant.

Firefighting jargon includes a diverse lexicon of both common and idiosyncratic terms. One problem that exists in trying to create a list such as this is that much of the terminology used by a particular department is specifically defined in their particular standing operating procedures, such that two departments may have completely different terms for the same thing. For example, depending on whom one asks, a safety team may be referred to as a standby, a RIT or RIG or RIC, or a FAST. Furthermore, a department may change a definition within its SOP, such that one year it may be RIT, and the next RIG or RIC.

<span class="mw-page-title-main">Fire sprinkler</span> Component that discharges water to protect buildings

A fire sprinkler or sprinkler head is the component of a fire sprinkler system that discharges water when the effects of a fire have been detected, such as when a predetermined temperature has been exceeded. Fire sprinklers are extensively used worldwide, with over 40 million sprinkler heads fitted each year. In buildings protected by properly designed and maintained fire sprinklers, over 99% of fires were controlled by fire sprinklers alone.

This is a glossary of firefighting equipment.

<span class="mw-page-title-main">Fire suppression system</span>

Fire suppression systems are used to extinguish, control, or in some cases, entirely prevent fires from spreading or occurring. Fire suppression systems have an incredibly large variety of applications, and as such, there are many different types of suppression systems for different applications being used today. Of these, there are some that are still in use but are no longer legal to manufacture and produce.

Active fire protection (AFP) is an integral part of fire protection. AFP is characterized by items and/or systems, which require a certain amount of motion and response in order to work, contrary to passive fire protection.

Firefighting is the act of extinguishing destructive fires. A firefighter fights these fires with the intent to prevent destruction of life, property and the environment. Firefighting is a highly technical profession, which requires years of training and education in order to become proficient. A fire can rapidly spread and endanger many lives; however, with modern firefighting techniques, catastrophe can usually be avoided. To help prevent fires from starting, a firefighter's duties include public education and conducting fire inspections. Because firefighters are often the first responders to victims in critical conditions, firefighters often also provide basic life support as emergency medical technicians or advanced life support as licensed paramedics. Firefighters make up one of the major emergency services, along with the emergency medical service, the police, and many others.

<span class="mw-page-title-main">Automatic fire suppression</span> Automatic Emergency Systems

Automatic fire suppression systems control and extinguish fires without human intervention. Examples of automatic systems include fire sprinkler system, gaseous fire suppression, and condensed aerosol fire suppression. When fires are extinguished in the early stages loss of life is minimal since 93% of all fire-related deaths occur once the fire has progressed beyond the early stages.

<span class="mw-page-title-main">Hard suction hose</span> Drafting fire hose made to withstand vacuum

Flexible suction hose, not to be confused with hard suction hose in U.S., is a specific type of fire hose used in drafting operations, when a fire engine uses a vacuum to draw water from a portable water tank, pool, or other static water source. It is built to withstand vacuum, rather than pressure, abrasion, and heat. Conversely, hard suction is capable of withstanding up to 200 PSIG, as well as vacuum. In the United States, it is standard equipment according to the National Fire Protection Association standards for fire engines. It is used in both structural and wildland firefighting throughout the world, and is made in various diameters and connection types.

A rotodynamic pump is a kinetic machine in which energy is continuously imparted to the pumped fluid by means of a rotating impeller, propeller, or rotor, in contrast to a positive displacement pump in which a fluid is moved by trapping a fixed amount of fluid and forcing the trapped volume into the pump's discharge. Examples of rotodynamic pumps include adding kinetic energy to a fluid such as by using a centrifugal pump to increase fluid velocity or pressure.

<span class="mw-page-title-main">Sprinkler fitting</span>

Sprinkler fitting is an occupation consisting of the installing, testing, inspecting, and certifying of automatic fire suppression systems in all types of structures. Sprinkler systems installed by sprinkler fitters can include the underground supply as well as integrated overhead piping systems and standpipes. The fire suppression piping may contain water, air, antifreeze, gas or chemicals as in a hood system, or a mixture producing fire retardant foam.

Water transportation and distribution networks require hydraulic calculations to determination the flowrate and pressure characteristics at one or several consumption points and the water supply flowrate and pressures needed to meet the design requirements.

<span class="mw-page-title-main">Sundyne</span>

Sundyne is the company’s common name and the brand name for its products and services.

<span class="mw-page-title-main">Variable speed fire pump controller</span>

A Variable Speed (VFD) Fire Pump Controller is a fire pump controller that is able to vary the speed of the motor depending on the demand of the fire pump, resulting in the ability to hold a constant discharge pressure. It differs from other industrial variable speed control devices because it is now considered a life safety device, and so must adhere to the more rigid standards set forth by NFPA-20.

<span class="mw-page-title-main">Booster pump</span> Machine to increase pressure of a fluid

A booster pump is a machine which will increase the pressure of a fluid. They may be used with liquids or gases, but the construction details will vary depending on the fluid. A gas booster is similar to a gas compressor, but generally a simpler mechanism which often has only a single stage of compression, and is used to increase pressure of a gas already above ambient pressure. Two-stage boosters are also made. Boosters may be used for increasing gas pressure, transferring high pressure gas, charging gas cylinders and scavenging.

References

  1. "NFPA 20: Standard for the Installation of Stationary Pumps for Fire Protection". Nfpa.org. Retrieved 2011-12-15.
  2. https://www.fmglobal.com/assets/pdf/fmapprovals/1319.pdf FM Global, Standards for Fire Pumps

"Chapter 9 - Fire Protection Systems". International Code Council. Archived from the original on 3 November 2015. Retrieved 30 December 2015.