A fan filter unit (FFU) is a type of motorized air filtering equipment. It is used to supply purified air to cleanrooms, laboratories, medical facilities or microenvironments by removing harmful airborne particles from recirculating air. [1] The units are installed within the system's ceiling or floor grid. Large cleanrooms require a proportionally large number of FFUs, which in some cases may range from several hundred to several thousand. [1] [2] Units often contain their own pre-filter, HEPA filter and internally controllable fan air distribution. [3]

Contents

Design

FFUs are typically manufactured in 4' x 2', 3' x 2', or 2' x 2' steel housings, which can be placed in ceiling grid bays of similar dimensions. [2] Units often contain a pre-filter as well as a HEPA (high-efficiency particulate air), ULPA (ultra-low particulate air) or other MERV (minimum efficiency reporting value) filter. A motorized fan is used to pull air through the filters for distribution to rooms or enclosed work stations such as hoods. [3] Fan speed is typically controlled via a step-wise or rheostat motor adjustment. [2] [3] Desired cleanliness levels determine the filter used: HEPA filters remove particles 0.3 μm or larger at 99.99% efficiency, while ULPA filters remove particles 0.12 μm or larger at 99.999% efficiency. [3] FFUs are engineered for laminar air flow, as is required in critical environments. Controlled air flowing in a uniform direction and speed (carrying microparticles) is cleaner than turbulent air that flows in multiple directions or at inconsistent speeds. Eddies created by turbulent air cause contaminating microparticles to settle on clean surfaces.

Uses

4' x 2' or 2' x 2' FFUs are designed to be placed in ceiling grid bays with similar dimensions. [3] Ceiling grids with standard size bays that match FFU dimensions are used to construct cleanrooms. Depending on the cleanliness requirements of the controlled space, more fan filter units can be added to the grid in order to meet ISO standards for airflow velocity and air changes per hour. [4]

FFUs can be used in place of a more conventional recirculating air unit such as a ducted or plenum air system. [1] [2] As FFUs require space above the ceiling grid (13" for the FFU module plus another 1–2 feet of "empty" air-filled space), plenums are commonly used for clean rooms with height restrictions; they are the only air systems that work in layouts with smaller internal floor dimensions. [2] Additionally, when less than 20 filters are installed in a room, a fan- powered HEPA, FFU is generally considered to be less expensive than a more conventional ducted supply system. [5]

When a microenvironment of clean air is required, FFUs can be used to construct enclosed work spaces, or laminar flow cabinets. Applying the same principle as the larger cleanroom grid, FFUs can be placed directly in a free- standing grid above the space that requires clean air. In fact, this approach is also used for silicon wafer etching in the semiconductor industry. [6]

Related Research Articles

<span class="mw-page-title-main">Heating, ventilation, and air conditioning</span> Technology of indoor and vehicular environmental comfort

Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.

<span class="mw-page-title-main">Cleanroom</span> Dust-free room for research or production

A cleanroom or clean room is an engineered space that maintains a very low concentration of airborne particulates. It is well isolated, well controlled from contamination, and actively cleansed. Such rooms are commonly needed for scientific research and in industrial production for all nanoscale processes, such as semiconductor manufacturing. A cleanroom is designed to keep everything from dust to airborne organisms or vaporised particles away from it, and so from whatever material is being handled inside it.

<span class="mw-page-title-main">Air ioniser</span> ION is mostly used on air conditioning products. Ioniser is another word for air purifier

An air ioniser is a device that uses high voltage to ionise air molecules. Negative ions, or anions, are particles with one or more extra electrons, conferring a net negative charge to the particle. Cations are positive ions missing one or more electrons, resulting in a net positive charge. Some commercial air purifiers are designed to generate negative ions. Another type of air ioniser is the electrostatic discharge (ESD) ioniser used to neutralise static charge.

<span class="mw-page-title-main">HEPA</span> Efficiency standard of air filters

HEPA filter, also known as high-efficiency particulate absorbing filter and high-efficiency particulate arrestance filter, is an efficiency standard of air filters.

<span class="mw-page-title-main">Air purifier</span> Device that removes contaminants from the air in a room

An air purifier or air cleaner is a device which removes contaminants from the air in a room to improve indoor air quality. These devices are commonly marketed as being beneficial to allergy sufferers and asthmatics, and at reducing or eliminating second-hand tobacco smoke.

<span class="mw-page-title-main">Air filter</span> Device composed of fibrous or porous materials which removes solid particulates from the air

A particulate air filter is a device composed of fibrous, or porous materials which removes particulates such as smoke, dust, pollen, mold, viruses and bacteria from the air. Filters containing an adsorbent or catalyst such as charcoal (carbon) may also remove odors and gaseous pollutants such as volatile organic compounds or ozone. Air filters are used in applications where air quality is important, notably in building ventilation systems and in engines.

<span class="mw-page-title-main">Air handler</span> Device used to regulate and circulate air as part of an HVAC system

An air handler, or air handling unit, is a device used to regulate and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. An air handler is usually a large metal box containing a blower, furnace or A/C elements, filter racks or chambers, sound attenuators, and dampers. Air handlers usually connect to a ductwork ventilation system that distributes the conditioned air through the building and returns it to the AHU, sometimes exhausting air to the atmosphere and bringing in fresh air. Sometimes AHUs discharge (supply) and admit (return) air directly to and from the space served without ductwork

Ultra-low particulate air (ULPA) is a type of air filter. A ULPA filter can remove from the air at least 99.999% of dust, pollen, mold, bacteria and any airborne particles with a minimum particle penetration size of 120 nanometres. A ULPA filter can remove—to a large extent but not 100%—oil smoke, tobacco smoke, rosin smoke, smog, and insecticide dust. It can also remove carbon black to some extent. Some fan filter units incorporate ULPA filters. The EN 1822 and ISO 29463 standards may be used to rate ULPA filters.

<span class="mw-page-title-main">Dust collector</span> Industrial machine

A dust collector is a system used to enhance the quality of air released from industrial and commercial processes by collecting dust and other impurities from air or gas. Designed to handle high-volume dust loads, a dust collector system consists of a blower, dust filter, a filter-cleaning system, and a dust receptacle or dust removal system. It is distinguished from air purifiers, which use disposable filters to remove dust.

<span class="mw-page-title-main">Laminar flow cabinet</span> Type of laboratory equipment used to prevent contamination of samples

A laminar flow cabinet or tissue culture hood is a partially enclosed bench work surface designed to prevent contamination of biological samples, semiconductor wafers, or any particle sensitive materials. Air is drawn through a HEPA filter and blown in a very smooth laminar flow in a narrow vertical curtain, separating the interior of the cabinet from the environment around it. The cabinet is usually made of stainless steel with no gaps or joints where spores might collect.

<span class="mw-page-title-main">Air shower (room)</span>

Air showers are specialized enclosed antechambers which are incorporated as entryways of cleanrooms and other controlled environments to reduce particle contamination. Air showers utilize high-pressure, HEPA- or ULPA-filtered air to remove dust, fibrous lint and other contaminants from personnel or object surfaces. The forceful "cleansing" of surfaces before entering clean environments reduces the number of airborne particulates introduced.

Minimum Efficiency Reporting Value, commonly known as MERV, is a measurement scale designed in 1987 by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) to report the effectiveness of air filters in more detail than other ratings. For example, often a high-efficiency particulate air (HEPA) filter is impractical in residential central heating, ventilation, and air conditioning (HVAC) systems due to the large pressure drop the dense filter material causes. Experiments indicate that less obstructive, medium-efficiency filters of MERV 7 to 13 are almost as effective as true HEPA filters at removing allergens within residential air handling units.

The Institute of Environmental Sciences and Technology (IEST) is a non-profit, technical society where professionals who impact controlled environments connect, gain knowledge, receive advice, and work together to create industry best practices. The organization uniquely serves environmental test engineers, qualification engineers, cleanroom professionals, those who work in product testing and evaluation, and others who work across a variety of industries, including: acoustics, aerospace, automotive, biotechnology/bioscience, climatics, cleanroom operations/design/equipment/certification, dynamics, filtration, food processing, HVAC design, medical devices, nanotechnology, pharmaceutical, semiconductors/microelectronics, and shock/vibration. Information on ISO 14644 and ISO 14698 standards can be found through this organization.

<span class="mw-page-title-main">Contamination control</span> Activities aiming to reduce contamination

Contamination control is the generic term for all activities aiming to control the existence, growth and proliferation of contamination in certain areas. Contamination control may refer to the atmosphere as well as to surfaces, to particulate matter as well as to microbes and to contamination prevention as well as to decontamination.

Aerobiological engineering is the science of designing buildings and systems to control airborne pathogens and allergens in indoor environments. The most-common environments include commercial buildings, residences and hospitals. This field of study is important because controlled indoor climates generally tend to favor the survival and transmission of contagious human pathogens as well as certain kinds of fungi and bacteria.

A hypoallergenic vacuum cleaner is a vacuum cleaner with filters designed to retain the vast majority of particles within the vacuum system. If successful this retention would greatly reduce the amount of potential allergens in the environment in which it is used. Regular vacuum cleaners are unable to retain most very fine dust and many allergens which simply are too small for the system to trap and are released from the system along with the exhaust air.

HVAC is a major sub discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary.

<span class="mw-page-title-main">Biosafety cabinet</span> Type of laboratory equipment

A biosafety cabinet (BSC)—also called a biological safety cabinet or microbiological safety cabinet—is an enclosed, ventilated laboratory workspace for safely working with materials contaminated with pathogens requiring a defined biosafety level. Several different types of BSC exist, differentiated by the degree of biocontainment they provide. BSCs first became commercially available in 1950.

<span class="mw-page-title-main">Clean air delivery rate</span> Filtration efficacy measurement

The clean air delivery rate (CADR) is a figure of merit that is the cubic feet per minute (CFM) of air that has had all the particles of a given size distribution removed. For air filters that have air flowing through them, it is the fraction of particles that have been removed from the air, multiplied by the air flow rate through the device. More precisely, it is the CFM of air in a 1,008-cubic-foot (28.5 m3) room that has had all the particles of a given size distribution removed from the air, over and above the rate at which the particles are naturally falling out of the air. Different filters have different abilities to remove different particle distributions, so three CADR's for a given device are typically measured: smoke, pollen, and dust. By combining the amount of airflow and particle removal efficiency, consumers are less likely to be misled by a high efficiency filter that is filtering a small amount of air, or by a high volume of air that is not being filtered very well.

Air filtration guidelines for operating rooms are determined by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) using a standard known as Minimum Efficiency Reporting Value (MERV). MERV is determined based on the size of particles successfully removed from the air and is used to classify the efficiency of HEPA filters. Ratings range from 1-16 and efficiency increases as the rating increases. ASHRAE groups surgeries into three categories: minor surgical procedures (A); minor or major surgical procedures performed with minor sedation (B); and major surgical procedures performed with general anesthesia or regional block anesthesia (C). Each surgical category is given a minimum MERV rating it must comply with.

References

  1. 1 2 3 Kohli, Rajiv; Mittal, Kashmiri L. (2009). Developments in surface contamination and cleaning - particle deposition, control and removal. William Andrew. p. 164. ISBN   978-1-4377-7830-4.
  2. 1 2 3 4 5 "Building and Environment: Performance of large fan-filter units for cleanroom applications". Building and Environment. 42. ScienceDirect: 2299–2304. doi:10.1016/j.buildenv.2006.05.007.
  3. 1 2 3 4 5 Pennwell (Mar 2007). CleanRooms. Vol. 21. pp. 16–17. ISSN   1043-8017 . Retrieved 26 October 2011.
  4. Schneider, Raymond K (2001). Designing clean room HVAC systems (PDF). ASHRAE Journal. Archived from the original (PDF) on 2016-10-28. Retrieved 2001-08-22.
  5. Pennwell (March 2008). CleanRooms. Vol. 22. p. 36. ISSN   1043-8017 . Retrieved 26 October 2011.
  6. Park, Jae Yong; et al. (2007). "Single-wafer process for improved metal contact hole cleaning". EBSCO Host. Retrieved 2007-05-10.[ dead link ]