Deep water source cooling

Last updated

Deep water source cooling (DWSC) or deep water air cooling is a form of air cooling for process and comfort space cooling which uses a large body of naturally cold water as a heat sink. It uses water at 4 to 10 degrees Celsius drawn from deep areas within lakes, oceans, aquifers or rivers, which is pumped through the one side of a heat exchanger. On the other side of the heat exchanger, cooled water is produced. [1]

Contents

Basic concept

Water is most dense at 3.98 °C (39.16 °F) at standard atmospheric pressure. Thus as water cools below 3.98 °C it increases in density and will settle below. As the temperature climbs above 3.98 °C, water density also decreases and causes the water to rise, which is why lakes are warmer on the surface during the summer. The combination of these two effects means that the bottom of most deep bodies of water located well away from the equatorial regions is at a constant 3.98 °C.

Air conditioners are heat pumps. During the summer, when outside air temperatures are higher than the temperature inside a building, air conditioners use electricity to transfer heat from the cooler interior of the building to the warmer exterior ambient. This process uses electrical energy.

Unlike residential air conditioners, most modern commercial air conditioning systems do not transfer heat directly into the exterior air. The thermodynamic efficiency of the overall system can be improved by utilizing evaporative cooling, where the temperature of the cooling water is lowered close to the wet-bulb temperature by evaporation in a cooling tower. This cooled water then acts as the heat sink for the heat pump.

Deep lake water cooling uses cold water pumped from the bottom of a lake as a heat sink for climate control systems. Because heat pump efficiency improves as the heat sink gets colder, deep lake water cooling can reduce the electrical demands of large cooling systems where it is available. It is similar in concept to modern geothermal sinks, but generally simpler to construct given a suitable water source.

Deep lake water cooling allows higher thermodynamic efficiency by using cold deep lake water, which is colder than the ambient wet bulb temperature. The higher efficiency results in less electricity used. For many buildings, the lake water is sufficiently cold that the refrigeration portion of the air conditioning systems can be shut down during some environmental conditions and the building interior heat can be transferred directly to the lake water heat sink. This is referred to as "free cooling", but is not actually free, since pumps and fans run to circulate the lake water and building air.

One added attraction of deep lake water cooling is that it saves energy during peak load times, such as summer afternoons, when a sizable amount of the total electrical grid load is air conditioning.

Advantages

Deep water source cooling is very energy efficient, requiring only 1/10 of the average energy required by conventional cooler systems. [1] Consequently, its running costs can also be expected to be much lower.

The energy source is very local and fully renewable, provided that the water and heat rejected into the environment (often the same lake or a nearby river) does not disturb the natural cycles. It does not use any ozone depleting refrigerant.

Depending on the building's cooling demand, and local weather, deep water source cooling can often satisfy a complete portion of a building's cooling demand, eradicating a building's reliance on mechanical refrigeration provided through a chiller. This not only reduces the building's electrical demand (or steam demand for applications using absorption refrigeration), but also curtails dependency on evaporative cooling towers which can often times harbor the fatal bacterium Legionella pneumophila. However, building operators must adhere to, and practice correct disinfection procedures before restarting any cooling towers which remained dormant during cooler days when deep water source cooling was able to meet the building's cooling demand.

Depending on the needs and on the water temperature, couple heating and cooling can be considered. For example, heat could first be extracted from the water (making it colder); and, secondly, that same water could cycle to a refrigerating unit to be used for even more effective cold production.

Lake temperature is rarely significantly changed by these systsms. In Europe, lake-based heating and cooling could save 0.8 TWh per year, and is most promising in Italy, Germany, Turkey and Switzerland. [2]

Disadvantages

Deep water source cooling requires a large and deep water quantity in the surroundings. To obtain water in the 3 to 6 °C (37 to 43 °F) range, a depth of 50 m (160 ft) to 70 m (230 ft) is generally required, depending on the local conditions.

The set-up of a system is expensive and labour-intensive. The system also requires a great amount of source material for its construction and placement.

Although deep water source cooling is referred to as "free cooling" in some literatures, a considerable amount of energy (typically electrical) is expended to operate pumps with a sufficient head to overcome frictional, and minor losses in distribution piping, and any heat exchangers.

One study found lakes in Europe would only economically serve about 17% of the cooling demand and 7% of combined heating and cooling demand in nearby areas. [2]

First major system in the United States

Cornell University's Lake Source Cooling System uses Cayuga Lake as a heat sink to operate the central chilled water system for its campus and to also provide cooling to the Ithaca City School District. [3] The system has operated since the summer of 2000 and was built at a cost of $55–60 million. It cools a 14,500 ton (51 megawatt) load. The intake pipe of the system is 3,200 m (10,498 ft) long and has a pipe diameter of 1,600 mm (63"), installed at a depth of 229 m (750 ft), allowing access to water temperatures between 3-5 C (37-41 F). The water is returned to the lake through a 1,200 mm (47") outfall pipe, 780 m (2,560 ft) long. The pipe selected for the project was Sclairpipe, made from high density polypropylene (HDPE). Estimated savings is an 80% reduction in fossil fuel previously required to operate a conventional electric cooling system.

First system in Canada

Since August 2004, a deep lake water cooling system has been operated by the Enwave Energy Corporation in Toronto, Ontario. [4] It draws water from Lake Ontario through tubes extending 5 kilometres (3.1 mi) into the lake, reaching to a depth of 83 metres (272 ft) where the water is maintained at a constant 4°C, its temperature protected by a layer of water above it, called a thermocline. The deep lake water cooling system is part of an integrated district cooling system that covers Toronto's financial district, and has a cooling power of 59,000 tons (207 MW). The system currently has enough capacity to cool 40,000,000 square feet (3,700,000 m2) of office space. [5]

The installed deep lake cooling water intake line was 1,600mm (63") in diameter, 15,000 m (49,213 ft) long and installed at a depth of 85 m (278 ft) allowing access to water temperatures of between 3-5 C (37-41 F). The selected pipe was Sclairpipe, made from high density polyethylene (HDPE) resin.

Water drawn from the depths of Lake Ontario is not circulated directly through terminal air-conditioning units within buildings. Instead, water from the Lake is circulated through a set of closed-loop heat exchangers in order to allow for a net transfer of thermal energy from heat transfer fluid returning from buildings to the Lake water. Chilled water within the buildings is part of a closed-loop district cooling system, pumped from a centralized location where the heat-exchangers are installed, back to the buildings where it can absorb heat from fan coil units installed to provide latent, and sensible space cooling.

The cold water drawn from Lake Ontario's deep layer in the Enwave system is not returned directly to the lake once it has been run through the heat exchange system. Instead, water is pumped to the City's water filtration plant for treatment and distribution to residential and commercial users.

Sea water air conditioning

Seawater pipes of The Excelsior hotel system in Hong Kong. HK CWB Victoria Park Road Pedestrian tunnel 2 Noonday Gun 2.jpg
Seawater pipes of The Excelsior hotel system in Hong Kong.

This version is also known as ocean water cooling. The InterContinental Resort and Thalasso-Spa on the island of Bora Bora uses a seawater air conditioning (SWAC) system to air condition its buildings. The system accomplishes this by passing cold seawater through a heat exchanger where it cools freshwater in a closed loop system. This cool freshwater is then pumped to buildings and is used for cooling directlyno conversion to electricity takes place. Similar systems are also in place in The Excelsior hotel [6] and The Hong Kong and Shanghai Banking Corporation main building in Hong Kong, and at the Natural Energy Laboratory of Hawaii Authority. [7]

Salt water air conditioning systems have been used in Sydney's Circular Quay and prominent buildings within the harbour since the rise of commercial air conditioning systems in the 1960s. These include the heritage-listed AMP 'Palm Cove' Building (constructed 1962) and the Sydney Opera House. [8] [9]

The InterContinental Resort is the largest seawater air conditioning system to date, though there are several other, larger systems being planned. [10] Honolulu Seawater Air Conditioning was a project intended to use seawater air conditioning to deliver renewable cooling to commercial and residential properties in the downtown Honolulu area. [11] On December 19, 2020, Honolulu Seawater Air Conditioning announced it was ending its development and would end operations by the end of January 2021. [12] Honolulu Seawater Air Conditioning is majority owned by eBay founder Pierre Omidyar's Ulupono Initiative. [13]

See also

Notes

  1. 1 2 Burford, Hazen E.; Wiedemann, Les; Joyce, W. S.; McCabe, Robert E. (1995). Deep Water Source Cooling: An Untapped Resource. 10th Annual District Cooling Conference. International District Energy Association. OSTI   272719. Archived from the original on 2012-02-16.{{cite conference}}: CS1 maint: unfit URL (link)
  2. 1 2 Eggimann S., Vivian J., Che R., Orehounig K., Patt A., Fiorentini M. (2023). "The potential of lake-source district heating and cooling for European buildings". Energy Conversion and Management. 283: 116914. doi: 10.1016/j.enconman.2023.116914 . hdl: 20.500.11850/604951 . S2CID   257618187.{{cite journal}}: CS1 maint: multiple names: authors list (link)
  3. "Lake Source Cooling". Facilities and Campus Services. Cornell University. Archived from the original on 2020-07-02. Retrieved 2020-07-18.
  4. "A Brief History of Enwave". Enwave. Archived from the original on 2007-12-30.{{cite web}}: CS1 maint: unfit URL (link)
  5. "Toronto". Enwave. Archived from the original on 2020-04-06. Retrieved 2020-07-21.
  6. Wong, Yiu-ming (1998). Biofouling treatment of seawater cooling systems in Hong Kong (M.Sc. in Environmental Management thesis). University of Hong Kong. doi:10.5353/th_b4257477 (inactive 2024-04-12).{{cite thesis}}: CS1 maint: DOI inactive as of April 2024 (link)
  7. "Seawater/Lake Water Air Conditioning (SWAC/LWAC)". Ocean Thermal Energy Corporation. Archived from the original on 2020-06-07. Retrieved 2020-07-21.
  8. "AMP Building". Sydney Living Museums. Archived from the original on 2020-06-06. Retrieved 2020-07-21.
  9. "Lend Lease looks to Sydney Harbour for water cooling at Barangaroo". The Fifth Estate. November 20, 2012. Archived from the original on 2020-06-06. Retrieved 2020-07-21.
  10. "The Basics of Seawater Air Conditioning Explained". YouTube. Retrieved 2020-07-21.
  11. Lincoln, Mileka (6 August 2013). "$1M local investment in Honolulu Seawater Air Conditioning". Hawaii News Now . Archived from the original on 2020-07-21. Retrieved 2020-07-21.
  12. "Honolulu Seawater Air Conditioning to end development after 15 years". www.bizjournals.com. Retrieved 2020-12-21.
  13. Shimogawa, Duane (March 24, 2015). "Honolulu Seawater A/C project clears federal environmental hurdle". Pacific Business News . Archived from the original on 2015-03-28. Retrieved 2020-07-21.

Related Research Articles

<span class="mw-page-title-main">Heating, ventilation, and air conditioning</span> Technology of indoor and vehicular environmental comfort

Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.

<span class="mw-page-title-main">Heat pump</span> System that transfers heat from one space to another

A heat pump is a device that uses work to transfer heat from a cool space to a warm space by transferring thermal energy using a refrigeration cycle, cooling the cool space and warming the warm space. In cold weather, a heat pump can move heat from the cool outdoors to warm a house; the pump may also be designed to move heat from the house to the warmer outdoors in warm weather. As they transfer heat rather than generating heat, they are more energy-efficient than other ways of heating or cooling a home.

Ocean thermal energy conversion (OTEC) is a renewable energy technology that harnesses the temperature difference between the warm surface waters of the ocean and the cold depths to run a heat engine to produce electricity. It is a unique form of clean energy generation that has the potential to provide a consistent and sustainable source of power. Although it has challenges to overcome, OTEC has the potential to provide a consistent and sustainable source of clean energy, particularly in tropical regions with access to deep ocean water.

The coefficient of performance or COP of a heat pump, refrigerator or air conditioning system is a ratio of useful heating or cooling provided to work (energy) required. Higher COPs equate to higher efficiency, lower energy (power) consumption and thus lower operating costs. The COP is used in thermodynamics.

<span class="mw-page-title-main">Enwave</span>

Enwave Energy Corporation is a Canadian multinational energy company based in Toronto that focuses on sustainable district energy including heating, cooling, hot water, combined heat and power, and geothermal energy systems. It is one of the largest district energy systems in North America and has been referred as the leading energy district system with 17 heating plants, 21 chilled water plants and ice on coil storage tanks. It serves over 700 customers including commercial properties, developers, municipalities, health care, educational centres and residential units.

<span class="mw-page-title-main">Heat recovery ventilation</span> Method of reusing thermal energy in a building

Heat recovery ventilation (HRV), also known as mechanical ventilation heat recovery (MVHR) or energy recovery ventilation (ERV), is a ventilation system that recovers energy by operating between two air sources at different temperatures. It is used to reduce the heating and cooling demands of buildings.

<span class="mw-page-title-main">Geothermal heating</span> Use of geothermal energy for heating

Geothermal heating is the direct use of geothermal energy for some heating applications. Humans have taken advantage of geothermal heat this way since the Paleolithic era. Approximately seventy countries made direct use of a total of 270 PJ of geothermal heating in 2004. As of 2007, 28 GW of geothermal heating capacity is installed around the world, satisfying 0.07% of global primary energy consumption. Thermal efficiency is high since no energy conversion is needed, but capacity factors tend to be low since the heat is mostly needed in the winter.

<span class="mw-page-title-main">District heating</span> Centralized heat distribution system

District heating is a system for distributing heat generated in a centralized location through a system of insulated pipes for residential and commercial heating requirements such as space heating and water heating. The heat is often obtained from a cogeneration plant burning fossil fuels or biomass, but heat-only boiler stations, geothermal heating, heat pumps and central solar heating are also used, as well as heat waste from factories and nuclear power electricity generation. District heating plants can provide higher efficiencies and better pollution control than localized boilers. According to some research, district heating with combined heat and power (CHPDH) is the cheapest method of cutting carbon emissions, and has one of the lowest carbon footprints of all fossil generation plants.

<span class="mw-page-title-main">Electric heating</span> Process in which electrical energy is converted to heat

Electric heating is a process in which electrical energy is converted directly to heat energy. Common applications include space heating, cooking, water heating and industrial processes. An electric heater is an electrical device that converts an electric current into heat. The heating element inside every electric heater is an electrical resistor, and works on the principle of Joule heating: an electric current passing through a resistor will convert that electrical energy into heat energy. Most modern electric heating devices use nichrome wire as the active element; the heating element, depicted on the right, uses nichrome wire supported by ceramic insulators.

Renewable heat is an application of renewable energy referring to the generation of heat from renewable sources; for example, feeding radiators with water warmed by focused solar radiation rather than by a fossil fuel boiler. Renewable heat technologies include renewable biofuels, solar heating, geothermal heating, heat pumps and heat exchangers. Insulation is almost always an important factor in how renewable heating is implemented.

<span class="mw-page-title-main">District cooling</span> Delivery of chilled water to building needing cooling

District cooling is the cooling equivalent of district heating. Working on broadly similar principles to district heating, district cooling delivers chilled water to buildings like offices and factories. In winter, the source for the cooling can often be seawater, so it is a cheaper resource than using electricity to run compressors for cooling. Alternatively, District Cooling can be provided by a Heat Sharing Network which enables each building on the circuit to use a heat pump to reject heat to an ambient ground temperature circuit.

<span class="mw-page-title-main">Air source heat pump</span> Most common type of heat pump

An air source heat pump (ASHP) is a heat pump that can absorb heat from air outside a building and release it inside; it uses the same vapor-compression refrigeration process and much the same equipment as an air conditioner, but in the opposite direction. ASHPs are the most common type of heat pump and, usually being smaller, tend to be used to heat individual houses or flats rather than blocks, districts or industrial processes.

<span class="mw-page-title-main">Ground source heat pump</span> System to transfer heat to/from the ground

A ground source heat pump is a heating/cooling system for buildings that use a type of heat pump to transfer heat to or from the ground, taking advantage of the relative constancy of temperatures of the earth through the seasons. Ground-source heat pumps (GSHPs) – or geothermal heat pumps (GHP), as they are commonly termed in North America – are among the most energy-efficient technologies for providing HVAC and water heating, using far less energy than can be achieved by burning a fuel in a boiler/furnace or by use of resistive electric heaters.

<span class="mw-page-title-main">Air conditioning</span> Cooling of air in an enclosed space

Air conditioning, often abbreviated as A/C (US) or air con (UK), is the process of removing heat from an enclosed space to achieve a more comfortable interior environment and in some cases also strictly controlling the humidity of internal air. Air conditioning can be achieved using a mechanical 'air conditioner' or by other methods, including passive cooling and ventilative cooling. Air conditioning is a member of a family of systems and techniques that provide heating, ventilation, and air conditioning (HVAC). Heat pumps are similar in many ways to air conditioners, but use a reversing valve to allow them both to heat and to cool an enclosed space.

HVAC is a major sub discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary.

<span class="mw-page-title-main">Ice storage air conditioning</span>

Ice storage air conditioning is the process of using ice for thermal energy storage. The process can reduce energy used for cooling during times of peak electrical demand. Alternative power sources such as solar can also use the technology to store energy for later use. This is practical because of water's large heat of fusion: one metric ton of water can store 334 megajoules (MJ) of energy, equivalent to 93 kWh.

The Glossary of Geothermal Heating and Cooling provides definitions of many terms used within the Geothermal heat pump industry. The terms in this glossary may be used by industry professionals, for education materials, and by the general public.

<span class="mw-page-title-main">Cold district heating</span> District heating with very low temperatures

Cold district heating is a technical variant of a district heating network that operates at low transmission temperatures well below those of conventional district heating systems and can provide both space heating and cooling. Transmission temperatures in the range of approx. 10 to 25 °C are common, allowing different consumers to heat and cool simultaneously and independently of each other. Hot water is produced and the building heated by water heat pumps, which obtain their thermal energy from the heating network, while cooling can be provided either directly via the cold heat network or, if necessary, indirectly via chillers. Cold local heating is sometimes also referred to as an anergy network. The collective term for such systems in scientific terminology is 5th generation district heating and cooling. Due to the possibility of being operated entirely by renewable energies and at the same time contributing to balancing the fluctuating production of wind turbines and photovoltaic systems, cold local heating networks are considered a promising option for a sustainable, potentially greenhouse gas and emission-free heat supply.

<span class="mw-page-title-main">Deep Lake Water Cooling System</span>

The Deep Lake Water Cooling System or DLWC is a deep water source cooling project in Toronto, Canada. As a renewable energy project, it involves running cold water from Lake Ontario, to air-condition buildings located downtown Toronto.

Sea water air conditioning (SWAC), also known as ocean water cooling, is an alternative cooling system that uses the deep cold seawater as the chilling agent for a closed-loop fresh water distributed cooling system. It is one type of deep water source cooling. Once installed, SWAC systems typically operate at approximately 15% of the power consumption of conventional chillers. A SWAC system basically consists of deep seawater intake and return pipelines, titanium heat exchangers, seawater and freshwater pumps, and a distribution system for the chilled fresh water.

References