Underfloor heating and cooling is a form of central heating and cooling that achieves indoor climate control for thermal comfort using hydronic or electrical heating elements embedded in a floor. Heating is achieved by conduction, radiation and convection. Use of underfloor heating dates back to the Neoglacial and Neolithic periods.
This section needs additional citations for verification .(July 2024) |
Underfloor heating has a long history back into the Neoglacial and Neolithic periods. Archeological digs in Asia and the Aleutian islands of Alaska reveal how the inhabitants drafted smoke from fires through stone covered trenches which were excavated in the floors of their subterranean dwellings. The hot smoke heated the floor stones and the heat then radiated into the living spaces. These early forms have evolved into modern systems using fluid filled pipes or electrical cables and mats. Below is a chronological overview of under floor heating from around the world.
Time period, c. BC [1] | Description [1] |
---|---|
5,000 | Evidence of "baked floors" are found foreshadowing early forms of kang and dikang "heated floor" later ondol meaning "warm stone" in Manchuria and Korea respectively. [2] |
3,000 | Korean fire hearth, was used both as kitchen range and heating stove. |
1,000 | Ondol type system used in the Aleutian Islands, Alaska [3] and in Unggi, Hamgyeongbuk-do (present-day North Korea). |
1,000 | More than two hearths were used in one dwelling; one hearth located at the center was used for heating, the other at the perimeter was used for cooking throughout the year. This perimeter hearth is the initial form of the budumak (meaning kitchen range), which composes the combustion section of the traditional ondol in Korea. At this point the floor it's still not heated directly from below but rather by thermal convection of hearth and stove from above. |
500 | Romans scale up the use of conditioned surfaces (floors and walls) with the invention of the hypocausts. [4] |
200 | Central hearth developed into gudeul (meaning heat releasing section of ondol) and perimeter hearth for cooking became more developed and budumak was almost established in Korea. |
50 | China, Korea and Roman Empire use kang, dikang/ondol and hypocaust respectively. |
Time period, c. AD [5] | Description [5] |
---|---|
500 | Anecdotal literary reference to radiant cooling system in the Middle East using snow packed wall cavities. |
700 | More sophisticated and developed gudeul was found in some palaces and living quarters of upper-class people in Korea. Countries in the Mediterranean Basin (Iran, Algeria, Turkey et al.) use various forms of hypocaust type heating in public baths and homes (ref.: tabakhana, atishkhana, sandali) but also use heat from cooking (see: tandoor, also tanur) to heat the floors. [6] [7] [8] |
1000 | Ondol continues to evolve in Asia. The most advanced true ondol system was established. The fire furnace was moved outside and the room was entirely floored with ondol in Korea. |
1300 | Hypocaust type systems used to heat monasteries in Poland and teutonic Malbork Castle. [9] |
1400 | Hypocaust type systems used to heat hammams of the Ottoman Empire. |
1500 | Attention to comfort and architecture in Europe evolves; China and Korea continue to apply floor heating with wide scale adoption. |
1600 | In France, heated flues in floors and walls are used in greenhouses. |
1700 | Benjamin Franklin studies the French and Asian cultures and makes note of their respective heating system leading to the development of the Franklin stove. Steam based radiant pipes are used in France. Hypocaust type system used to heat public bath (hammam) in the citadel town of Erbil located in modern-day Iraq. [10] |
1800 | Beginnings of the European evolution of the modern water heater/boiler and water based piping systems including studies in thermal conductivities and specific heat of materials and emissivity/reflectivity of surfaces (Watt/Leslie/Rumford). [11] Reference to the use of small bore pipes used in the John Soane house and museum. [12] |
1864 | Underfloor heating type system used at Civil War hospital sites in America. [13] Reichstag building in Germany uses the thermal mass of the building for cooling and heating. |
1899 | The earliest beginnings of polyethylene-based pipes occur when German scientist, Hans von Pechmann, discovered a waxy residue at the bottom of a test tube, colleagues Eugen Bamberger and Friedrich Tschirner called it polymethylene but it was discarded as having no commercial use at the time. [14] |
1904 | Liverpool Cathedral in England is heated with system based on the hypocaust principles. |
1905 | Frank Lloyd Wright makes his first trip to Japan, later incorporates various early forms of radiant heating in his projects. |
1907 | England, Prof. Barker granted Patent No. 28477 for panel warming using small pipes. Patents later sold to the Crittal Company who appointed representatives across Europe. A.M. Byers of America promotes radiant heating using small bore water pipes. Asia continues to use traditional ondol and kang—wood is used as the fuel, combustion gases sent under floor. |
1930 | Oscar Faber in England uses water pipes used to radiant heat and cool several large buildings. [15] |
1933 | Explosion at England's Imperial Chemical Industries (ICI) laboratory during a high pressure experiment with ethylene gas results in a wax like substance—later to become polyethylene and the re-beginnings of PEX pipe. [16] |
1937 | Frank Lloyd Wright designs the radiant heated Herbert Jacobs house, the first Usonian home. |
1939 | First small scale polyethylene plant built in America. |
1945 | American developer William Levitt builds large scale developments for returning GIs. Water based (copper pipe) radiant heating used throughout thousands of homes. Poor building envelopes on all continents require excessive surface temperatures leading in some cases to health problems. Thermal comfort and health science research (using hot plates, thermal manikins and comfort laboratories) in Europe and America later establishes lower surface temperature limits and development of comfort standards. |
1950 | Korean War wipes out wood supplies for ondol, population forced to use coal. Developer Joseph Eichler in California begins the construction of thousands of radiant heated homes. |
1951 | J. Bjorksten of Bjorksten Research Laboratories in Madison, WI, announces first results of what is believed to be the first instance of testing three types of plastic tubing for radiant floor heating in America. Polyethylene, vinyl chloride copolymer, and vinylidene chloride were tested over three winters. [17] |
1953 | The first Canadian polyethylene plant is built near Edmonton, Alberta. [18] |
1960 | NRC researcher from Canada installs underfloor heating in his home and later remarks, "Decades later it would be identified as a passive solar house. It incorporated innovative features such as the radiant heating system supplied with hot water from an automatically stoked anthracite furnace." [19] |
1965 | Thomas Engel patents method for stabilizing polyethylene by cross linking molecules using peroxide (PEx-A) and in 1967 sells license options to a number of pipe producers. [20] |
1970 | Evolution of Korean architecture leads to multistory housings, flue gases from coal based ondol results in many deaths leading to the removal of the home based flue gas system to a central water based heating plants. Oxygen permeation becomes corrosion issue in Europe leading to the development of barriered pipe and oxygen permeation standards. |
1980 | The first standards for floor heating are developed in Europe. Water-based ondol system is applied to almost all of residential buildings in Korea. |
1985 | Floor heating becomes a traditional heating systems in residential buildings in Middle Europe and Nordic countries and increasing applications in non-residential buildings. |
1995 | The application of floor cooling and thermal active building systems (TABS) in residential and commercial buildings are widely introduced into the market. [21] |
2000 | The use of embedded radiant cooling systems in the middle of Europe becomes a standard system with many parts of the world applying radiant based HVAC systems as means of using low temperatures for heating and high temperatures for cooling. |
2010 | Radiant conditioned Pearl River Tower in Guangzhou, China, topped out at 71 stories. |
Modern underfloor heating systems use either electrical resistance elements ("electric systems") or fluid flowing in pipes ("hydronic systems") to heat the floor. Either type can be installed as the primary, whole-building heating system or as localized floor heating for thermal comfort. Some systems allow for single rooms to be heated when they are a part of a larger multi-room system, avoiding any wasted heat. Electrical resistance can only be used for heating; when space cooling is also required, hydronic systems must be used. Other applications for which either electric or hydronic systems are suited include snow/ice melting for walks, driveways and landing pads, turf conditioning of football and soccer fields and frost prevention in freezers and skating rinks. A range of underfloor heating systems and designs are available to suit different types of flooring. [22] Some underfloor heating systems are designed to be laid within the floor construction with the pipework embedded within a screed beneath the floor covering, typically used in extensions or new builds, meanwhile other underfloor heating systems can be fitted directly on top of an existing floor (providing it is level and stable) using self-adhesive panels into which the pipework is laid and a self-levelling screed is poured, a popular solution for retrofit projects. [23]
Electric heating elements or hydronic piping can be cast in a concrete floor slab ("poured floor system" or "wet system"). They can also be placed under the floor covering ("dry system") or attached directly to a wood sub floor ("sub floor system" or "dry system").
Some commercial buildings are designed to take advantage of thermal mass which is heated or cooled during off-peak hours when utility rates are lower. With the heating/cooling system turned off during the day, the concrete mass and room temperature drift up or down within the desired comfort range. Such systems are known as thermally activated building systems or TABS. [24] [25]
The terms radiant heating and radiant cooling are commonly used to describe this approach because radiation is responsible for a significant portion of the resulting thermal comfort but this usage is technically correct only when radiation composes more than 50% of the heat exchange between the floor and the rest of the space. [26]
Hydronic systems use water or a mix of water and anti-freeze such as propylene glycol [27] as the heat transfer fluid in a "closed-loop" that is recirculated between the floor and the boiler.
Various types of pipes are available specifically for hydronic underfloor heating and cooling systems and are generally made from polyethylene including PEX, PEX-Al-PEX and PERT. Older materials such as Polybutylene (PB) and copper or steel pipe are still used in some locales or for specialized applications.
Hydronic systems require skilled designers and tradespeople familiar with boilers, circulators, controls, fluid pressures and temperature. The use of modern factory assembled sub-stations, used primarily in district heating and cooling, can greatly simplify design requirements and reduce the installation and commissioning time of hydronic systems.
Hydronic systems can use a single source or combination of energy sources to help manage energy costs. Hydronic system energy source options are:
Underfloor heating is particularly suitable when the energy source is a heat pump, because underfloor heating uses lower water temperatures than systems using radiators, which improves the efficiency of the heat pump. [28]
Electric systems are used only for heating and employ non-corrosive, flexible heating elements including cables, pre-formed cable mats, bronze mesh, and carbon films. Due to their low profile, they can be installed in a thermal mass or directly under floor finishes. Electric systems can also take advantage of time-of-use electricity metering and are frequently used as carpet heaters, portable under area rug heaters, under laminate floor heaters, under tile heating, under wood floor heating, and floor warming systems, including under shower floor and seat heating. Large electric systems also require skilled designers and tradespeople but this is less so for small floor warming systems. Electric systems use fewer components and are simpler to install and commission than hydronic systems. Some electric systems use line voltage technology while others use low voltage technology. The power consumption of an electric system is not based on voltage but rather wattage output produced by the heating element.
As defined by ANSI/ASHRAE Standard 55 – Thermal Environmental Conditions for Human Occupancy, thermal comfort is, "that condition of mind which expresses satisfaction with the thermal environment and is assessed by subjective evaluation." Relating specifically to underfloor heating, thermal comfort is influenced by floor surface temperature and associated elements such as radiant asymmetry, mean radiant temperature, and operative temperature. Research by Nevins, Rohles, Gagge, P. Ole Fanger et al. show that humans at rest with clothing typical of light office and home wear, exchange over 50% of their sensible heat via radiation.
Underfloor heating influences the radiant exchange by warming the interior surfaces. The heating of the surfaces suppresses body heat loss resulting in a perception of heating comfort. This general sensation of comfort is further enhanced through conduction (feet on floor) and through convection by the surface's influence on air density. Underfloor cooling works by absorbing both short wave and long wave radiation resulting in cool interior surfaces. These cool surfaces encourage the loss of body heat resulting in a perception of cooling comfort. Localized discomfort due to cold and warm floors wearing normal footwear and stocking feet is addressed in the ISO 7730 and ASHRAE 55 standards and ASHRAE Fundamentals Handbooks and can be corrected or regulated with floor heating and cooling systems.
Underfloor heating can have a positive effect on the quality of indoor air by facilitating the choice of otherwise perceived cold flooring materials such as tile, slate, terrazzo, and concrete. These masonry surfaces typically have very low VOC emissions (volatile organic compounds) in comparison to other flooring options. In conjunction with moisture control, floor heating also establishes temperature conditions that are less favorable in supporting mold, bacteria, viruses and dust mites. [29] [30] By removing the sensible heating load from the total HVAC (Heating, Ventilating, and Air Conditioning) load, ventilation, filtration and dehumidification of incoming air can be accomplished with dedicated outdoor air systems having less volumetric turnover to mitigate distribution of airborne contaminates. There is recognition from the medical community relating to the benefits of floor heating especially as it relates to allergens. [31] [32]
Under floor radiant systems are evaluated for sustainability through the principles of efficiency, entropy, exergy [33] and efficacy. When combined with high-performance buildings, underfloor systems operate with low temperatures in heating and high temperatures in cooling [34] in the ranges found typically in geothermal [35] and solar thermal systems. When coupled with these non-combustible, renewable energy sources the sustainability benefits include reduction or elimination of combustion and greenhouse gases produced by boilers and power generation for heat pumps [36] and chillers, as well as reduced demands for non-renewables and greater inventories for future generations. This has been supported through simulation evaluations [37] [38] [39] [40] and through research funded by the U.S. Department of Energy, [41] [42] Canada Mortgage and Housing Corporation, [43] Fraunhofer Institute ISE [44] as well as ASHRAE. [45]
Low-temperature underfloor heating is embedded in the floor or placed under the floor covering. As such it occupies no wall space and creates no burn hazards, nor is it a hazard for physical injuries due to accidental contact leading to tripping and falling. This has been referenced as a positive feature in healthcare facilities including those serving elderly clients and those with dementia. [46] [47] [48] Anecdotally, under similar environmental conditions, heated floors will speed evaporation of wetted floors (showering, cleaning, and spills). Additionally, underfloor heating with fluid-filled pipes is useful in heating and cooling explosion-proof environments where combustion and electrical equipment can be located remotely from the explosive environment.
There is a likelihood that underfloor heating may add to offgassing and sick building syndrome in an environment, particularly when the carpet is used as flooring.[ citation needed ]
Electric underfloor heating systems cause low frequency magnetic fields (in the 50–60 Hz range), old 1-wire systems much more so than modern 2-wire systems. [49] [50] The International Agency for Research on Cancer (IARC) has classified static and low-frequency magnetic fields as possibly carcinogenic (Group 2B). [51]
Equipment maintenance and repair is the same as for other water or electrical based HVAC systems except when pipes, cables or mats are embedded in the floor. Early trials (for example homes built by Levitt and Eichler, c. 1940–1970s) experienced failures in embedded copper and steel piping systems as well as failures assigned by the courts to Shell, Goodyear and others for polybutylene and EPDM materials. [52] [53] There also have been a few publicized claims of failed electric heated gypsum panels from the mid-1990s. [54]
Failures associated with most installations are attributable to job site neglect, installation errors, and product mishandling such as exposure to ultraviolet radiation. Pre-pour pressure tests required by concrete installation standards [55] and good practice guidelines [56] for the design, construction, operation and repair of radiant heating and cooling systems mitigate problems resulting from improper installation and operation.
Fluid based systems using cross-linked polyethylene (PEX) a product developed in the 1930s and its various derivatives such as PE-rt have demonstrated reliable long term performance in harsh cold-climate applications such as bridge decks, aircraft hangar aprons, and landing pads. PEX has become a popular and reliable option in-home use for new concrete slab construction, and new underfloor joist construction as well as (joist) retrofit. Since the materials are produced from polyethylene and its bonds are cross-linked, it is highly resistant to corrosion or the temperature and pressure stresses associated with typical fluid-based HVAC systems. [57] For PEX reliability, installation procedures must be precise (especially at joints) and manufacturers specifications for a maximum temperature of water or fluid, etc. must be carefully followed.
The engineering of underfloor cooling and heating systems is governed by industry standards and guidelines. [58] [59] [notes 2]
The amount of heat exchanged from or to an underfloor system is based on the combined radiant and convective heat transfer coefficients.
Convective heat transfer with underfloor systems is much greater when the system is operating in a heating rather than cooling mode. [60] Typically with underfloor heating the convective component is almost 50% of the total heat transfer and in underfloor cooling the convective component is less than 10%. [61]
When heated and cooled pipes or heating cables share the same spaces as other building components, parasitic heat transfer can occur between refrigeration appliances, cold storage areas, domestic cold water lines, air conditioning and ventilation ducts. To control this, the pipes, cables and other building components must all be well insulated.
With underfloor cooling, condensation may collect on the surface of the floor. To prevent this, air humidity is kept low, below 50%, and floor temperatures are maintained above the dew point, 19 °C (66F). [62]
Underfloor heating and cooling systems can have several control points including the management of:
Illustrated is a simplified mechanical schematic of an underfloor heating and cooling system for thermal comfort quality [67] with a separate air handling system for indoor air quality. [68] [69] In high performance residential homes of moderate size (e.g. under 3000 ft2 (278 m2) total conditioned floor area), this system using manufactured hydronic control appliances would take up about the same space as a three or four piece bathroom.
Modeling radiant piping (also tube or loop) patterns with finite element analysis (FEA) predicts the thermal diffusions and surface temperature quality or efficacy of various loop layouts. The performance of the model (left image below) and image to the right are useful to gain an understanding in relationships between flooring resistances, conductivities of surrounding mass, tube spacings, depths and fluid temperatures. As with all FEA simulations, they depict a snap shot in time for a specific assembly and may not be representative of all floor assemblies nor for system that have been operative for considerable time in a steady state condition. The practical application of FEA for the engineer is being able to assess each design for fluid temperature, back losses and surface temperature quality. Through several iterations it is possible to optimize the design for the lowest fluid temperature in heating and the highest fluid temperature in cooling which enables combustion and compression equipment to achieve its maximum rated efficiency performance.
There is a wide range of pricing for underfloor systems based on regional differences, materials, application and project complexity. It is widely adopted in the Nordic, Asian and European communities. Consequently, the market is more mature and systems relatively more affordable than less developed markets such as North America where market share for fluid based systems remains between 3% and 7% of HVAC systems (ref. Statistics Canada and United States Census Bureau).
In energy efficiency buildings such as Passive House, R-2000 or Net Zero Energy, simple thermostatic radiator valves can be installed along with a single compact circulator and small condensing heater controlled without or with basic hot water reset [70] control. Economical electric resistance based systems also are useful in small zones such as bathrooms and kitchens, but also for entire buildings where heating loads are very low. Larger structures will need more sophisticated systems to deal with cooling and heating needs, and often require building management control systems to regulate the energy use and control the overall indoor environment.
Low temperature radiant heating and high temperature radiant cooling systems lend themselves well to district energy systems (community based systems) due to the temperature differentials between the plant and the buildings which allow small diameter insulated distribution networks and low pumping power requirements. The low return temperatures in heating and high return temperatures in cooling enable the district energy plant to achieve maximum efficiency. The principles behind district energy with underfloor systems can also be applied to stand alone multi story buildings with the same benefits. [71] Additionally, underfloor radiant systems are ideally suited to renewable energy sources including geothermal and solar thermal systems or any system where waste heat is recoverable.
In the global drive for sustainability, long term economics supports the need to eliminate where possible, compression for cooling and combustion for heating. It will then be necessary to use low quality heat sources for which radiant underfloor heating and cooling is well suited.[ clarify ][ citation needed ]
System efficiency and energy use analysis takes into account building enclosure performance, efficiency of the heating and cooling plant, system controls and the conductivities, surface characteristics, tube/element spacing and depth of the radiant panel, operating fluid temperatures and wire to water efficiency of the circulators. [72] The efficiency in electric systems is analyzed by similar processes and includes the efficiency of electricity generation.
Though the efficiency of radiant systems is under constant debate with no shortage of anecdotal claims and scientific papers presenting both sides, the low return fluid temperatures in heating and high return fluid temperatures in cooling enable condensing boilers, [73] chillers [74] and heat pumps [75] to operate at or near their maximum engineered performance. [76] [77] The greater efficiency of 'wire to water' versus 'wire to air' flow due to water's significantly greater heat capacity favors fluid based systems over air based systems. [78] Both field application and simulation research have demonstrated significant electrical energy savings with radiant cooling and dedicated outdoor air systems based in part on the previous noted principles. [79] [80]
In Passive Houses, R-2000 homes or Net Zero Energy buildings the low temperatures of radiant heating and cooling systems present significant opportunities to exploit exergy. [81]
System efficiency is also affected by the floor covering serving as the radiational boundary layer between the floor mass and occupants and other contents of the conditioned space. For example, carpeting has a greater resistance or lower conductance than tile. Thus carpeted floors need to operate at higher internal temperatures than tile which can create lower efficiencies for boilers and heat pumps. However, when the floor covering is known at the time the system is installed, then the internal floor temperature required for a given covering can be achieved through proper tube spacing without sacrificing plant efficiency (though the higher internal floor temperatures may result in increased heat loss from the non-room surfaces of the floor). [82]
The emissivity, reflectivity and absorptivity of a floor surface are critical determinants of its heat exchange with the occupants and room. Unpolished flooring surface materials and treatments have very high emissivity's (0.85 to 0.95) and therefore make good heat radiators. [83]
With underfloor heating and cooling ("reversible floors") flooring surfaces with high absorbance and emissivity and low reflectivity are most desirable.
Thermography is a useful tool to see the actual thermal efficacy of an underfloor system from its start up (as shown) to its operating conditions. In a startup it is easy to identify the tube location but less so as the system moves into a steady state condition. It is important to interpret thermographic images correctly. As is the case with finite element analysis (FEA), what is seen, reflects the conditions at the time of the image and may not represent the steady conditions. For example, the surfaces viewed in the images shown, may appear ‘hot’, but in reality are actually below the nominal temperature of the skin and core temperatures of the human body and the ability to ‘see’ the pipes does not equate to ‘feel’ the pipes. Thermography can also point out flaws in the building enclosures (left image, corner intersection detail), thermal bridging (right image, studs) and the heat losses associated with exterior doors (center image).
Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.
A central heating system provides warmth to a number of spaces within a building from one main source of heat. It is a component of heating, ventilation, and air conditioning systems, which can both cool and warm interior spaces.
Heat recovery ventilation (HRV), also known as mechanical ventilation heat recovery (MVHR) is a ventilation system that recovers energy by operating between two air sources at different temperatures. It is used to reduce the heating and cooling demands of buildings.
Hydronics is the use of liquid water or gaseous water (steam) or a water solution as a heat-transfer medium in heating and cooling systems. The name differentiates such systems from oil and refrigerant systems.
Cross-linked polyethylene, commonly abbreviated PEX, XPE or XLPE, is a form of polyethylene with cross-links. It is used predominantly in building services pipework systems, hydronic radiant heating and cooling systems, domestic water piping, insulation for high tension electrical cables, and baby play mats. It is also used for natural gas and offshore oil applications, chemical transportation, and transportation of sewage and slurries. PEX is an alternative to polyvinyl chloride (PVC), chlorinated polyvinyl chloride (CPVC) or copper tubing for use as residential water pipes.
Electric heating is a process in which electrical energy is converted directly to heat energy. Common applications include space heating, cooking, water heating and industrial processes. An electric heater is an electrical device that converts an electric current into heat. The heating element inside every electric heater is an electrical resistor, and works on the principle of Joule heating: an electric current passing through a resistor will convert that electrical energy into heat energy. Most modern electric heating devices use nichrome wire as the active element; the heating element, depicted on the right, uses nichrome wire supported by ceramic insulators.
Displacement ventilation (DV) is a room air distribution strategy where conditioned outdoor air is supplied at a low velocity from air supply diffusers located near floor level and extracted above the occupied zone, usually at ceiling height.
Variable air volume (VAV) is a type of heating, ventilating, and/or air-conditioning (HVAC) system. Unlike constant air volume (CAV) systems, which supply a constant airflow at a variable temperature, VAV systems vary the airflow at a constant or varying temperature. The advantages of VAV systems over constant-volume systems include more precise temperature control, reduced compressor wear, lower energy consumption by system fans, less fan noise, and additional passive dehumidification.
A ground source heat pump is a heating/cooling system for buildings that use a type of heat pump to transfer heat to or from the ground, taking advantage of the relative constancy of temperatures of the earth through the seasons. Ground-source heat pumps (GSHPs) – or geothermal heat pumps (GHP), as they are commonly termed in North America – are among the most energy-efficient technologies for providing HVAC and water heating, using far less energy than can be achieved by burning a fuel in a boiler/furnace or by use of resistive electric heaters.
Thermal comfort is the condition of mind that expresses subjective satisfaction with the thermal environment. The human body can be viewed as a heat engine where food is the input energy. The human body will release excess heat into the environment, so the body can continue to operate. The heat transfer is proportional to temperature difference. In cold environments, the body loses more heat to the environment and in hot environments the body does not release enough heat. Both the hot and cold scenarios lead to discomfort. Maintaining this standard of thermal comfort for occupants of buildings or other enclosures is one of the important goals of HVAC design engineers.
Passive ventilation is the process of supplying air to and removing air from an indoor space without using mechanical systems. It refers to the flow of external air to an indoor space as a result of pressure differences arising from natural forces.
A snowmelt system prevents the build-up of snow and ice on cycleways, walkways, patios and roadways, or more economically, only a portion of the area such as a pair of 2-foot (0.61 m)-wide tire tracks on a driveway or a 3-foot (0.91 m) center portion of a sidewalk, etc. It is also used to keep entire driveways and patios snow free in snow prone climates. The "snow melt" system is designed to function during a storm to improve safety and eliminate winter maintenance labor including shoveling, plowing snow and spreading de-icing salt or traction grit (sand). A snowmelt system may extend the life of the concrete, asphalt or under pavers by eliminating the use of salts or other de-icing chemicals, and physical damage from winter service vehicles. Many systems are fully automatic and require no human input to maintain a snow/ice-free horizontal surface.
Radiators and convectors are heat exchangers designed to transfer thermal energy from one medium to another for the purpose of space heating.
HVAC is a major sub discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary.
Underfloor air distribution (UFAD) is an air distribution strategy for providing ventilation and space conditioning in buildings as part of the design of a HVAC system. UFAD systems use an underfloor supply plenum located between the structural concrete slab and a raised floor system to supply conditioned air to supply outlets, located at or near floor level within the occupied space. Air returns from the room at ceiling level or the maximum allowable height above the occupied zone.
A dedicated outdoor air system (DOAS) is a type of heating, ventilation and air-conditioning (HVAC) system that consists of two parallel systems: a dedicated system for delivering outdoor air ventilation that handles both the latent and sensible loads of conditioning the ventilation air, and a parallel system to handle the loads generated by indoor/process sources and those that pass through the building enclosure.
Radiant heating and cooling is a category of HVAC technologies that exchange heat by both convection and radiation with the environments they are designed to heat or cool. There are many subcategories of radiant heating and cooling, including: "radiant ceiling panels", "embedded surface systems", "thermally active building systems", and infrared heaters. According to some definitions, a technology is only included in this category if radiation comprises more than 50% of its heat exchange with the environment; therefore technologies such as radiators and chilled beams are usually not considered radiant heating or cooling. Within this category, it is practical to distinguish between high temperature radiant heating, and radiant heating or cooling with more moderate source temperatures. This article mainly addresses radiant heating and cooling with moderate source temperatures, used to heat or cool indoor environments. Moderate temperature radiant heating and cooling is usually composed of relatively large surfaces that are internally heated or cooled using hydronic or electrical sources. For high temperature indoor or outdoor radiant heating, see: Infrared heater. For snow melt applications see: Snowmelt system.
The Glossary of Geothermal Heating and Cooling provides definitions of many terms used within the Geothermal heat pump industry. The terms in this glossary may be used by industry professionals, for education materials, and by the general public.
Heating films are a method of electric resistance heating, providing relatively low temperatures over large areas. Heating films can be directly installed to provide underfloor heating, wall radiant heating and ceiling radiant heating.
Cooling load is the rate at which sensible and latent heat must be removed from the space to maintain a constant space dry-bulb air temperature and humidity. Sensible heat into the space causes its air temperature to rise while latent heat is associated with the rise of the moisture content in the space. The building design, internal equipment, occupants, and outdoor weather conditions may affect the cooling load in a building using different heat transfer mechanisms. The SI units are watts.