Heat recovery ventilation (HRV), also known as mechanical ventilation heat recovery (MVHR) is a ventilation system that recovers energy by operating between two air sources at different temperatures. It is used to reduce the heating and cooling demands of buildings.
By recovering the residual heat in the exhaust gas, the fresh air introduced into the air conditioning system is preheated (or pre-cooled) before it enters the room, or the air cooler of the air conditioning unit performs heat and moisture treatment. [1] A typical heat recovery system in buildings comprises a core unit, channels for fresh and exhaust air, and blower fans. Building exhaust air is used as either a heat source or heat sink, depending on the climate conditions, time of year, and requirements of the building. Heat recovery systems typically recover about 60–95% of the heat in the exhaust air and have significantly improved the energy efficiency of buildings. [2]
Energy recovery ventilation (ERV) is the energy recovery process in residential and commercial HVAC systems that exchanges the energy contained in normally exhausted air of a building or conditioned space, using it to treat (precondition) the incoming outdoor ventilation air. The specific equipment involved may be called an Energy Recovery Ventilator, also commonly referred to simply as an ERV.
An ERV is a type of air-to-air heat exchanger that transfers latent heat as well as sensible heat. Because both temperature and moisture are transferred, ERVs are described as total enthalpic devices. In contrast, a heat recovery ventilator (HRV) can only transfer sensible heat. HRVs can be considered sensible only devices because they only exchange sensible heat. In other words, all ERVs are HRVs, but not all HRVs are ERVs. It is incorrect to use the terms HRV, AAHX (air-to-air heat exchanger), and ERV interchangeably. [3]
During the warmer seasons, an ERV system pre-cools and dehumidifies; during cooler seasons the system humidifies[ need quotation to verify ] and pre-heats. [4] An ERV system helps HVAC design meet ventilation and energy standards (e.g., ASHRAE), improves indoor air quality and reduces total HVAC equipment capacity, thereby reducing energy consumption. ERV systems enable an HVAC system to maintain a 40-50% indoor relative humidity, essentially in all conditions. ERV's must use power for a blower to overcome the pressure drop in the system, hence incurring a slight energy demand. [4]
A heat recovery system is designed to supply conditioned air to the occupied space to maintain a certain temperature. [5] A heat recovery system helps keep a house ventilated while recovering heat being emitted from the inside environment. The purpose of heat recovery systems is to transfer the thermal energy from one fluid to another fluid, from one fluid to a solid, or from a solid surface to a fluid at different temperatures and in thermal contact. There is no direct interaction between fluid and fluid or fluid and solid in most heat recovery systems. In some heat recovery systems, fluid leakage is observed due to pressure differences between fluids, resulting in a mixture of the two fluids. [6]
A thermal wheel, also known as a rotary heat exchanger, or rotary air-to-air enthalpy wheel, energy recovery wheel, or heat recovery wheel, is a type of energy recovery heat exchanger positioned within the supply and exhaust air streams of air-handling units or rooftop units or in the exhaust gases of an industrial process, in order to recover the heat energy. Other variants include enthalpy wheels and desiccant wheels. A cooling-specific thermal wheel is sometimes referred to as a Kyoto wheel.
Rotary thermal wheels are a mechanical means of heat recovery. A rotating porous metallic wheel transfers thermal energy from one air stream to another by passing through each fluid alternately. The system operates by working as a thermal storage mass whereby the heat from the air is temporarily stored within the wheel matrix until it is transferred to the cooler air stream. [7]
Two types of rotary thermal wheels exist: heat wheels and enthalpy (desiccant) wheels. Though there is a geometrical similarity between heat and enthalpy wheels, there are differences that affect the operation of each design. In a system using a desiccant wheel, the moisture in the air stream with the highest relative humidity is transferred to the opposite air stream after flowing through the wheel. This can work in both directions of incoming air to exhaust air and exhaust air to incoming air. The supply air can then be used directly or employed to further cool the air. This is an energy-intensive process. [8] [ need quotation to verify ][ why? ]
The rotary air-to-air enthalpy wheel heat exchanger is a rotating cylinder filled with an air permeable material, typically polymer, aluminum, or synthetic fiber, providing the large surface area required for the sensible enthalpy transfer (enthalpy is a measure of heat). As the wheel rotates between the supply and exhaust air streams it picks up heat energy and releases it into the colder air stream. The driving force behind the exchange is the difference in temperatures between the opposing air streams (the thermal gradient).
The enthalpy exchange is accomplished through the use of desiccants. Desiccants transfer moisture through the process of adsorption which is predominately driven by the difference in the partial pressure of vapor within the opposing air-streams. Typical desiccants consist of silica gel, and molecular sieves.
Enthalpy wheels are the most effective devices to transfer both latent and sensible heat energy. Choice of construction materials for the rotor, most commonly polymer, aluminum, or fiberglass, determines durability.
When using rotary energy recovery devices the two air streams must be adjacent to one another to allow for the local transfer of energy. Also, there should be special considerations paid in colder climates to avoid wheel frosting. Systems can avoid frosting by modulating wheel speed, preheating the air, or stop/jogging the system.
O’Connor et al. [9] studied the effect that a rotary thermal wheel has on the supply air flow rates into a building. A computational model was created to simulate the effects of a rotary thermal wheel on air flow rates when incorporated into a commercial wind tower system. The simulation was validated with a scale model experiment in a closed-loop subsonic wind tunnel. The data obtained from both tests were compared in order to analyze the flow rates. Although the flow rates were reduced compared to a wind tower which did not include a rotary thermal wheel, the guideline ventilation rates for occupants in a school or office building were met above an external wind speed of 3 m/s, which is lower than the average wind speed of the UK (4–5 m/s).
No full-scale experimental or field test data was completed in this study, therefore it cannot be conclusively proved that rotary thermal wheels are feasible for integration into a commercial wind tower system. However, despite the air flow rate decrease within the building after the introduction of the rotary thermal wheel, the reduction was not large enough to prevent the ventilation guideline rates from being met. Sufficient research has not yet been conducted to determine the suitability of rotary thermal wheels in natural ventilation, ventilation supply rates can be met but the thermal capabilities of the rotary thermal wheel have not yet been investigated. Further work would beneficial to increase understanding of the system. [10]Fixed plate heat exchangers have no moving parts, and consist of alternating layers of plates that are separated and sealed. Typical flow is cross current and since the majority of plates are solid and non permeable, sensible only transfer is the result.
The tempering of incoming fresh air is done by a heat or energy recovery core. In this case, the core is made of aluminum or plastic plates. Humidity levels are adjusted through the transferring of water vapor. This is done with a rotating wheel either containing a desiccant material or permeable plates. [11]
Enthalpy plates were introduced in 2006 by Paul, a special company for ventilation systems for passive houses. A crosscurrent countercurrent air-to-air heat exchanger built with a humidity permeable material. Polymer fixed-plate countercurrent energy recovery ventilators were introduced in 1998 by Building Performance Equipment (BPE), a residential, commercial, and industrial air-to-air energy recovery manufacturer. These heat exchangers can be both introduced as a retrofit for increased energy savings and fresh air as well as an alternative to new construction. In new construction situations, energy recovery will effectively reduce the required heating/cooling capacity of the system. The percentage of the total energy saved will depend on the efficiency of the device (up to 90% sensible) and the latitude of the building.
Due to the need to use multiple sections, fixed plate energy exchangers are often associated with high pressure drop and larger footprints. Due to their inability to offer a high amount of latent energy transfer these systems also have a high chance of frosting in colder climates.
The technology patented by Finnish company RecyclingEnergy Int. Corp. [12] is based on a regenerative plate heat exchanger taking advantage of humidity of air by cyclical condensation and evaporation, e.g. latent heat, enabling not only high annual thermal efficiency but also microbe-free plates due to self-cleaning/washing method. Therefore, the unit is called an enthalpy recovery ventilator rather than heat or energy recovery ventilator. Company's patented LatentHeatPump is based on its enthalpy recovery ventilator having COP of 33 in the summer and 15 in the winter.
Fixed plate heat exchangers are the most commonly used type of heat exchanger and have been developed for 40 years. Thin metal plates are stacked with a small spacing between plates. Two different air streams pass through these spaces, adjacent to each other. Heat transfer occurs as the temperature transfers through the plate from one air stream to the other. The efficiency of these devices has reached 90% sensible heat efficiency in transferring sensible heat from one air stream to another. [13] The high levels of efficiency are attributed to the high heat transfer coefficients of the materials used, operational pressure and temperature range. [2]
Heat pipes are a heat recovery device that uses a multi-phase process to transfer heat from one air stream to another. [2] Heat is transferred using an evaporator and condenser within a wicked, sealed pipe containing a fluid which undergoes a constant phase change to transfer heat. The fluid within the pipes changes from a fluid to a gas in the evaporator section, absorbing the thermal energy from the warm air stream. The gas condenses back to a fluid in the condenser section where the thermal energy is dissipated into the cooler air stream raising the temperature. The fluid/gas is transported from one side of the heat pipe to the other through pressure, wick forces or gravity, depending on the arrangement of the heat pipe.
Run-around systems are hybrid heat recovery system that incorporates characteristics from other heat recovery technology to form a single device, capable of recovering heat from one air stream and delivering to another a significant distance away. The general case of run-around heat recovery, two fixed plate heat exchangers are located in two separate air streams and are linked by a closed loop containing a fluid that is continually pumped between the two heat exchangers. The fluid is heated and cooled constantly as it flows around the loop, providing heat recovery. The constant flow of the fluid through the loop requires pumps to move between the two heat exchangers. Though this is an additional energy demand, using pumps to circulate fluid is less energy intensive than fans to circulate air. [14]
Phase change materials, or PCMs, are a technology that is used to store sensible and latent heat within a building structure at a higher storage capacity than standard building materials. PCMs have been studied extensively due to their ability to store heat and transfer heating and cooling demands from conventional peak times to off-peak times.
The concept of the thermal mass of a building for heat storage, that the physical structure of the building absorbs heat to help cool the air, has long been understood and investigated. A study of PCMs in comparison to traditional building materials has shown that the thermal storage capacity of PCMs is twelve times higher than standard building materials over the same temperature range. [15] The pressure drop across PCMs has not been investigated to be able to comment on the effect that the material may have on air streams. However, as the PCM can be incorporated directly into the building structure, this would not affect the flow in the same way other heat exchanger technologies do, it can be suggested that there is no pressure loss created by the inclusion of PCMs in the building fabric. [16]
Mardiana et al. [17] integrated a fixed plate heat exchanger into a commercial wind tower, highlighting the advantages of this type of system as a means of zero energy ventilation which can be simply modified. Full scale laboratory testing was undertaken in order to determine the effects and efficiency of the combined system. A wind tower was integrated with a fixed plate heat exchanger and was mounted centrally in a sealed test room.
The results from this study indicate that the combination of a wind tower passive ventilation system and a fixed plate heat recovery device could provide an effective combined technology to recover waste heat from exhaust air and cool incoming warm air with zero energy demand. Though no quantitative data for the ventilation rates within the test room was provided, it can be assumed that due to the high-pressure loss across the heat exchanger that these were significantly reduced from the standard operation of a wind tower. Further investigation of this combined technology is essential in understanding the air flow characteristics of the system. [16]
Due to the low-pressure loss of heat pipe systems, more research has been conducted into the integration of this technology into passive ventilation than other heat recovery systems. Commercial wind towers were again used as the passive ventilation system for integrating this heat recovery technology. This further enhances the suggestion that commercial wind towers provide a worthwhile alternative to mechanical ventilation, capable of supplying and exhausting air at the same time. [16]
Flaga-Maryanczyk et al. [18] conducted a study in Sweden which examined a passive ventilation system which integrated a run-around system using a ground source heat pump as the heat source to warm incoming air. Experimental measurements and weather data were taken from the passive house used in the study. A CFD model of the passive house was created with the measurements taken from the sensors and weather station used as input data. The model was run to calculate the effectiveness of the run-around system and the capabilities of the ground source heat pump.
Ground source heat pumps provide a reliable source of consistent thermal energy when buried 10–20 m below the ground surface. The ground temperature is warmer than the ambient air in winter and cooler than the ambient air in summer, providing both a heat source and a heat sink. It was found that in February, the coldest month in the climate, the ground source heat pump was capable of delivering almost 25% of the heating needs of the house and occupants. [16]
The majority of research interest in PCMs is the application of phase change material integration into traditional porous building materials such as concrete and wall boards. Kosny et al. [19] analyzed the thermal performance of buildings that have PCM-enhanced construction materials within the structure. Analysis showed that the addition of PCMs is beneficial in terms of improving thermal performance.
A significant drawback of PCM used in a passive ventilation system for heat recovery is the lack of instantaneous heat transfer across different airstreams. Phase change materials are a heat storage technology, whereby the heat is stored within the PCM until the air temperature has fallen to a significant level where it can be released back into the air stream. No research has been conducted into the use of PCMs between two airstreams of different temperatures where continuous, instantaneous heat transfer can occur. An investigation into this area would be beneficial for passive ventilation heat recovery research. [16]
Source: [16]
Type of HRV | Advantages | Disadvantages | Performance Parameters | Efficiency % | Pressure Drop (Pa) | Humidity Control |
Rotary thermal wheel | High efficiency Sensible and latent heat recovery Compact design Frost control available | Cross contamination possible Requires adjacent airstreams Mechanically driven, requiring energy input | Rotation speed Air velocity Wheel Porosity | 80+ | 4-45 | Yes |
Fixed plate | No moving parts hence high reliability High heat transfer coefficient No cross contamination Frost control possible Sensible and latent heat recovery | High pressure loss across exchanger Limited to two separate air streams Condensation build up Frost building up in cold climates | Material type Operating pressure Temperature Flow arrangement | 70-90 | 7-30 | Yes |
Heat pipes | No moving parts, high reliability No cross contamination Low pressure loss Compact design Heat recovery in two directions possible | Requires close air streams Internal fluid should match local climate conditions | Fluid type Contact time Arrangement/configuration Structure | 80 | 1-5 | No |
Run-around | Airstreams can be separate No cross contamination Low pressure loss Multiple sources of heat recovery | Multiple pumps required to move fluid Difficult to integrate into existing structures Low efficiency Cost | Exchanger type Fluid type Heat source | 50-80 | ~1 | No |
Phase change materials | Easy incorporation into building materials Offset peak energy demands No pressure loss No cross contamination No moving parts Long life cycle | Thermal storage as opposed to instantaneous transfer Expensive Not proven technology Difficulty in selecting appropriate material | Impregnation method | ~ | 0 | No |
Energy recovery device | Type of transfer |
---|---|
Rotary enthalpy wheel | Total & sensible |
Fixed plate | Total** & sensible |
Heat pipe | Sensible |
Run around coil | Sensible |
Thermosiphon | Sensible |
Twin towers [20] | Sensible |
**Total energy exchange only available on hygroscopic units and condensate return units
Source: [21]
Energy saving is one of the key issues for both fossil fuel consumption and the protection of the global environment. The rising cost of energy and global warming underlined that developing improved energy systems is necessary to increase energy efficiency while reducing greenhouse gas emissions. One of the most effective ways to reduce energy demand is to use energy more efficiently. Therefore, waste heat recovery is becoming popular in recent years[ when? ] since it improves energy efficiency. About 26% of industrial energy is still wasted as hot gas or fluid in many countries. [22] However, during last two decades[ when? ] there has been remarkable attention to recover waste heat from various industries and to optimize the units which are used to absorb heat from waste gases. [23] Thus, these attempts enhance reducing of global warming as well as of energy demand.
In most industrialized countries, HVAC is responsible for one-third of the total energy consumption. Moreover, cooling and dehumidifying fresh ventilation air compose 20–40% of the total energy load for HVAC in hot and humid climatic regions. However, that percentage can be higher where 100% fresh air ventilation is required. This means more energy is needed to meet the fresh air requirements of the occupants. Heat recovery is becoming more necessary due to an increased energy cost for the treatment of fresh air. The main purpose of heat recovery systems is to mitigate the energy consumption of buildings for heating, cooling, and ventilation by recovering the waste heat. In this regard, stand-alone or combined heat recovery systems can be incorporated into residential or commercial buildings for energy saving. Reduction in energy consumption levels can also notably contribute in reducing greenhouse gas emissions.[ citation needed ]
Nearly half of global energy is used in buildings, [24] [ obsolete source ]and half of heating/cooling cost is caused by ventilation when it is done by the "open window" method [ definition needed ] according to the regulations[ citation needed ]. Secondly, energy generation and grid is made to meet the peak demand of power. To use proper ventilation; recovery is a cost-efficient, sustainable and quick way to reduce global energy consumption and give better indoor air quality (IAQ) and protect buildings, and environment.[ citation needed ]
During the cooling season, the system works to cool and dehumidify the incoming, outside air. To do this, the system takes the rejected heat and sends it into the exhaust airstream. Subsequently, this air cools the condenser coil at a lower temperature than if the rejected heat had not entered the exhaust airstream. During the heating seasons, the system works in reverse. Instead of discharging the heat into the exhaust airstream, the system draws heat from the exhaust airstream in order to pre-heat the incoming air. At this stage, the air passes through a primary unit and then into the space being conditioned. With this type of system, it is normal during the cooling seasons for the exhaust air to be cooler than the ventilation air and, during the heating seasons, warmer than the ventilation air. It is for this reason the system works efficiently and effectively. The coefficient of performance (COP) will increase as the conditions become more extreme (i.e., more hot and humid for cooling and colder for heating). [25]
The efficiency of an ERV system is the ratio of energy transferred between the two air streams compared with the total energy transported through the heat exchanger. [26] [27]
With the variety of products on the market, efficiency will vary as well. Some of these systems have been known to have heat exchange efficiencies as high as 70-80% while others have as low as 50%. Even though this lower figure is preferable to the basic HVAC system, it is not up to par with the rest of its class. Studies are being done to increase the heat transfer efficiency to 90%. [26] [ obsolete source ]
The use of modern low-cost gas-phase heat exchanger technology will allow for significant improvements in efficiency. The use of high conductivity porous material is believed to produce an exchange effectiveness in excess of 90%, producing a five times improvement in energy recovery. [26] [ obsolete source ]
The Home Ventilating Institute (HVI) has developed a standard test for any and all units manufactured within the United States. Regardless, not all have been tested. It is imperative to investigate efficiency claims, comparing data produced by HVI as well as that produced by the manufacturer. (Note: all units sold in Canada are placed through the R-2000 program, a standard test equivalent to the HVI test). [27] [ obsolete source ]
An exhaust air heat pump (EAHP) extracts heat from the exhaust air of a building and transfers the heat to the supply air, hot tap water and/or hydronic heating system (underfloor heating, radiators). [28] [29] This requires at least mechanical exhaust but mechanical supply is optional; see mechanical ventilation. This type of heat pump requires a certain air exchange rate to maintain its output power. Since the inside air is approximately 20–22 degrees Celsius all year round, the maximum output power of the heat pump is not varying with the seasons and outdoor temperature.[ citation needed ]
Air leaving the building when the heat pump's compressor is running is usually at around −1° in most versions. [30] Thus, the unit is extracting heat from the air that needs to be changed (at a rate of around a half an air change per hour). Air entering the house is of course generally warmer than the air processed through the unit so there is a net 'gain'. Care must be taken that these are only used in the correct type of houses. Exhaust air heat pumps have minimum flow rates so that when installed in a small flat, the airflow chronically over-ventilates the flat and increases the heat loss by drawing in large amounts of unwanted outside air. [31] There are some models though that can take in additional outdoor air to negate this and this air is also feed to the compressor to avoid over ventilation.For most earlier exhaust air heat pumps there will be a low heat output to the hot water and heating of just around 1.8 kW from the compressor/heat pump process, but if that falls short of the building's requirements additional heat will be automatically triggered in the form of immersion heaters or an external gas boiler. The immersion heater top-up could be substantial ( if you select the wrong unit), and when a unit with a 6 kW immersion heater operates at the full output it will cost £1 per hour to run. [32] [33]
Between 2009 and 2013, some 15,000 brand new social homes were built in the UK with NIBE EAHPs used as primary heating. Owners and housing association tenants reported crippling electric bills. [34] [35] High running costs are usual with exhaust air heat pumps and should be expected, due to the very small heat recovery with these units. Typically the ventilation air stream is around 31 litres per second and the heat recovery is 750W and no more. All additional heat necessary to provide heating and hot water is from electricity, either compressor electrical input or immersion heater. At outside temperatures below 0 degrees Celsius, this type of heat pump removes more heat from a home than it supplies. Over a year around 60% of the energy input to a property with an exhaust air heat pump will be from electricity. [36]
Many families are still battling with developers to have their EAHP systems replaced with more reliable and efficient heating, noting the success of residents in Coventry. [37]
This section may contain an excessive amount of intricate detail that may interest only a particular audience.(February 2024) |
Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.
A heat exchanger is a system used to transfer heat between a source and a working fluid. Heat exchangers are used in both cooling and heating processes. The fluids may be separated by a solid wall to prevent mixing or they may be in direct contact. They are widely used in space heating, refrigeration, air conditioning, power stations, chemical plants, petrochemical plants, petroleum refineries, natural-gas processing, and sewage treatment. The classic example of a heat exchanger is found in an internal combustion engine in which a circulating fluid known as engine coolant flows through radiator coils and air flows past the coils, which cools the coolant and heats the incoming air. Another example is the heat sink, which is a passive heat exchanger that transfers the heat generated by an electronic or a mechanical device to a fluid medium, often air or a liquid coolant.
Solar thermal energy (STE) is a form of energy and a technology for harnessing solar energy to generate thermal energy for use in industry, and in the residential and commercial sectors. Solar thermal collectors are classified by the United States Energy Information Administration as low-, medium-, or high-temperature collectors. Low-temperature collectors are generally unglazed and used to heat swimming pools or to heat ventilation air. Medium-temperature collectors are also usually flat plates but are used for heating water or air for residential and commercial use.
A heat pipe is a heat-transfer device that employs phase transition to transfer heat between two solid interfaces.
A solar thermal collector collects heat by absorbing sunlight. The term "solar collector" commonly refers to a device for solar hot water heating, but may refer to large power generating installations such as solar parabolic troughs and solar towers or non-water heating devices such as solar cookers or solar air heaters.
A recuperator is a special purpose counter-flow energy recovery heat exchanger positioned within the supply and exhaust air streams of an air handling system, or in the exhaust gases of an industrial process, in order to recover the waste heat. Generally, they are used to extract heat from the exhaust and use it to preheat air entering the combustion system. In this way they use waste energy to heat the air, offsetting some of the fuel, and thereby improve the energy efficiency of the system as a whole.
An air handler, or air handling unit, is a device used to regulate and circulate air as part of a heating, ventilating, and air-conditioning (HVAC) system. An air handler is usually a large metal box containing a blower, furnace or A/C elements, filter racks or chambers, sound attenuators, and dampers. Air handlers usually connect to a ductwork ventilation system that distributes the conditioned air through the building and returns it to the AHU, sometimes exhausting air to the atmosphere and bringing in fresh air. Sometimes AHUs discharge (supply) and admit (return) air directly to and from the space served without ductwork
Renewable heat is an application of renewable energy referring to the generation of heat from renewable sources; for example, feeding radiators with water warmed by focused solar radiation rather than by a fossil fuel boiler. Renewable heat technologies include renewable biofuels, solar heating, geothermal heating, heat pumps and heat exchangers. Insulation is almost always an important factor in how renewable heating is implemented.
Economizers, or economisers (UK), are mechanical devices intended to reduce energy consumption, or to perform useful function such as preheating a fluid. The term economizer is used for other purposes as well. Boiler, power plant, heating, refrigeration, ventilating, and air conditioning (HVAC) may all use economizers. In simple terms, an economizer is a heat exchanger.
A ground-coupled heat exchanger is an underground heat exchanger that can capture heat from and/or dissipate heat to the ground. They use the Earth's near constant subterranean temperature to warm or cool air or other fluids for residential, agricultural or industrial uses. If building air is blown through the heat exchanger for heat recovery ventilation, they are called earth tubes.
Underfloor heating and cooling is a form of central heating and cooling that achieves indoor climate control for thermal comfort using hydronic or electrical heating elements embedded in a floor. Heating is achieved by conduction, radiation and convection. Use of underfloor heating dates back to the Neoglacial and Neolithic periods.
Solar air conditioning, or "solar-powered air conditioning", refers to any air conditioning (cooling) system that uses solar power.
Energy recovery includes any technique or method of minimizing the input of energy to an overall system by the exchange of energy from one sub-system of the overall system with another. The energy can be in any form in either subsystem, but most energy recovery systems exchange thermal energy in either sensible or latent form.
Passive ventilation is the process of supplying air to and removing air from an indoor space without using mechanical systems. It refers to the flow of external air to an indoor space as a result of pressure differences arising from natural forces.
A waste heat recovery unit (WHRU) is an energy recovery heat exchanger that transfers heat from process outputs at high temperature to another part of the process for some purpose, usually increased efficiency. The WHRU is a tool involved in cogeneration. Waste heat may be extracted from sources such as hot flue gases from a diesel generator, steam from cooling towers, or even waste water from cooling processes such as in steel cooling.
Photovoltaic thermal collectors, typically abbreviated as PVT collectors and also known as hybrid solar collectors, photovoltaic thermal solar collectors, PV/T collectors or solar cogeneration systems, are power generation technologies that convert solar radiation into usable thermal and electrical energy. PVT collectors combine photovoltaic solar cells, which convert sunlight into electricity, with a solar thermal collector, which transfers the otherwise unused waste heat from the PV module to a heat transfer fluid. By combining electricity and heat generation within the same component, these technologies can reach a higher overall efficiency than solar photovoltaic (PV) or solar thermal (T) alone.
HVAC is a major sub discipline of mechanical engineering. The goal of HVAC design is to balance indoor environmental comfort with other factors such as installation cost, ease of maintenance, and energy efficiency. The discipline of HVAC includes a large number of specialized terms and acronyms, many of which are summarized in this glossary.
A thermal wheel, also known as a rotary heat exchanger, or rotary air-to-air enthalpy wheel, energy recovery wheel, or heat recovery wheel, is a type of energy recovery heat exchanger positioned within the supply and exhaust air streams of air-handling units or rooftop units or in the exhaust gases of an industrial process, in order to recover the heat energy. Other variants include enthalpy wheels and desiccant wheels. A cooling-specific thermal wheel is sometimes referred to as a Kyoto wheel.
A run-around coil is a type of energy recovery heat exchanger most often positioned within the supply and exhaust air streams of an air handling system, or in the exhaust gases of an industrial process, to recover the heat energy. Generally, it refers to any intermediate stream used to transfer heat between two streams that are not directly connected for reasons of safety or practicality. It may also be referred to as a run-around loop, a pump-around coil or a liquid coupled heat exchanger.
Computational Fluid Dynamics (CFD) modeling and simulation for phase change materials (PCMs) is a technique used to analyze the performance and behavior of PCMs. The CFD models have been successful in studying and analyzing the air quality, natural ventilation and stratified ventilation, air flow initiated by buoyancy forces and temperature space for the systems integrated with PCMs. Simple shapes like flat plates, cylinders or annular tubes, fins, macro- and micro-encapsulations with containers of different shapes are often modeled in CFD software's to study.