The stack effect or chimney effect is the movement of air into and out of buildings through unsealed openings, chimneys, flue-gas stacks, or other purposefully designed openings or containers, resulting from air buoyancy. Buoyancy occurs due to a difference in indoor-to-outdoor air density resulting from temperature and moisture differences. The result is either a positive or negative buoyancy force. The greater the thermal difference and the height of the structure, the greater the buoyancy force, and thus the stack effect. The stack effect can be useful to drive natural ventilation in certain climates, but in other circumstances may be a cause of unwanted air infiltration or fire hazard.
Since buildings are not totally sealed (at the very minimum, there is always a ground level entrance), the stack effect will cause air infiltration. During the heating season, the warmer indoor air rises up through the building and escapes at the top either through open windows, ventilation openings, or unintentional holes in ceilings, like ceiling fans and recessed lights. The rising warm air reduces the pressure in the base of the building, drawing cold air in through either open doors, windows, or other openings and leakage. During the cooling season, the stack effect is reversed, but is typically weaker due to lower temperature differences. [1]
In a modern high-rise building with a well-sealed envelope, the stack effect can create significant pressure differences that must be given design consideration and may need to be addressed with mechanical ventilation. Stairwells, shafts, elevators, and the like, tend to contribute to the stack effect, while interior partitions, floors, and fire separations can mitigate it. Especially in case of fire, the stack effect needs to be controlled to prevent the spread of smoke and fire, and to maintain tenable conditions for occupants and firefighters. [2] While natural ventilation methods may be effective, such as air outlets being installed closer to the ground, mechanical ventilation is often preferred for taller structures or in buildings with limited space. Smoke extraction is a key consideration in new constructions and must be evaluated in design stages. [3]
The stack effect can also exacerbate the spreading of fire, especially in tall buildings where design flaws allow the formation of unwanted drafts. Examples include Kaprun tunnel fire, King's Cross underground station fire and the Grenfell Tower fire, as a result of which 72 people died. [4] The latter of these was in part exacerbated by the stack effect, when a cavity between the outer aluminium cladding and the inner insulation inadvertently formed a chimney and drew the fire upwards. [5] [6]
Some buildings are designed with strategically placed openings at different heights to induce the stack effect where cool air enters through low-level windows or vents, and warm air escapes through higher-level openings like skylights, roof vents, or clerestory windows. This vertical movement of air creates a natural ventilation system that can significantly reduce indoor temperatures. Combining the stack effect with cross ventilation, where airflow moves across the building from one side to the other, can enhance the overall cooling effect. [7] [8]
The stack effect is used both in traditional buildings and modern green architecture. Examples of traditional usage include the wind towers common in Middle Eastern architecture, which capture and direct cooler breezes into the building while expelling hot air to maintain comfortable indoor temperatures. [9] Contemporary sustainable buildings often make use of the stack effect along with related non-electric techniques like ground coupling, earth sheltering, and evaporative cooling to enhance the passive cooling profile of a building. By carefully designing the building's structure, orientation and ventilation paths, architects can leverage the stack effect to reduce reliance on mechanical cooling systems and improve overall energy efficiency. [8]
Two regimes of stack effect can exist in buildings: normal and reverse. Normal stack effect occurs in buildings which are maintained at a higher temperature than the outdoor environment. Warm air within the building has a low density (or high specific volume) and exhibits a greater buoyancy force. Consequently, it rises from lower levels to upper levels through penetrations between floors. This presents a situation where floors underneath the neutral axis of the building have a net negative pressure, whereas floors above the neutral axis have a net positive pressure. The net negative pressure on lower floors can induce outdoor air to infiltrate the building through doors, windows, or ductwork without backdraft dampers. Warm air will attempt to exfiltrate the building envelope through floors above the neutral axis.
Mechanical refrigeration equipment provides sensible and latent cooling during summer months. This reduces the dry-bulb temperature of the air within the building relative to the outdoor ambient air. It also decreases the specific volume of the air contained within the building, thereby reducing the buoyancy force. Consequently, cool air will travel vertically down the building through elevator shafts, stairwells, and unsealed utility penetrations (i.e., hydronics, electric and water risers). Once the conditioned air reaches the bottom floors underneath the neutral axis, it exfiltrates the building envelopes through unsealed openings such as through dampers, curtainwall, etc. The exfiltrating air on floors underneath the neutral axis will induce outdoor air to infiltrate the building envelope through unsealed openings.
The stack effect in industrial flue gas stacks is similar to that in buildings, except that it involves hot flue gases having large temperature differences with the ambient outside air. Furthermore, an industrial flue gas stack typically provides little obstruction for the flue gas along its length and is, in fact, normally optimized to enhance the stack effect to reduce fan energy requirements.
Large temperature differences between the outside air and the flue gases can create a strong stack effect in chimneys for buildings using a fireplace for heating.
Before the development of large volume fans, mines were ventilated using the stack effect. A downcast shaft allowed air into the mine. At the foot of the upcast shaft a furnace was kept continuously burning. The shaft (commonly several hundred yards deep) behaved like a chimney and air rose through it drawing fresh air down the downcast stack and around the mine.
There is a pressure difference between the outside air and the air inside the building caused by the difference in temperature between the outside air and the inside air. That pressure difference ( ΔP ) is the driving force for the stack effect and it can be calculated with the equations presented below. [10] [11] The equations apply only to buildings where air is both inside and outside the buildings. For buildings with one or two floors, h is the height of the building. For multi-floor, high-rise buildings, h is the distance from the openings at the neutral pressure level (NPL) of the building to either the topmost openings or the lowest openings. Reference [10] explains how the NPL affects the stack effect in high-rise buildings.
For flue gas stacks and chimneys, where air is on the outside and combustion flue gases are on the inside, the equations will only provide an approximation and h is the height of the flue gas stack or chimney.
where: | |
ΔP | = available pressure difference, in Pa |
---|---|
C | = 0.0342, in K/m |
a | = atmospheric pressure, in Pa |
h | = height or distance, in m |
To | = absolute outside temperature, in K |
Ti | = absolute inside temperature, in K |
The draft (draught in British English) flow rate induced by the stack effect can be calculated with the equation presented below. [12] [13] The equation applies only to buildings where air is both inside and outside the buildings. For buildings with one or two floors, h is the height of the building and A is the flow area of the openings. For multi-floor, high-rise buildings, A is the flow area of the openings and h is the distance from the openings at the neutral pressure level (NPL) of the building to either the topmost openings or the lowest openings. Reference [10] explains how the NPL affects the stack effect in high-rise buildings.
For flue gas stacks or chimneys, where air is on the outside and combustion flue gases are on the inside, the equation will only provide an approximation. Also, A is the cross-sectional flow area and h is the height of the flue gas stack or chimney.
where: | |
Q | = stack effect draft (draught in British English) flow rate, m3/s |
---|---|
A | = flow area, m2 |
C | = discharge coefficient (usually taken to be from 0.65 to 0.70) [14] |
g | = gravitational acceleration, 9.81 m/s2 |
h | = height or distance, m |
Ti | = average inside temperature, K |
To | = outside air temperature, K |
where: | |
Q | = stack effect draft flow rate, ft3/s |
---|---|
A | = area, ft2 |
C | = discharge coefficient (usually taken to be from 0.65 to 0.70) [14] |
g | = gravitational acceleration, 32.17 ft/s2 |
h | = height or distance, ft |
Ti | = average inside temperature, °R |
To | = outside air temperature, °R |
This equation assumes that the resistance to the draft flow is similar to the resistance of flow through an orifice characterized by a discharge coefficient C.
Convection is single or multiphase fluid flow that occurs spontaneously due to the combined effects of material property heterogeneity and body forces on a fluid, most commonly density and gravity. When the cause of the convection is unspecified, convection due to the effects of thermal expansion and buoyancy can be assumed. Convection may also take place in soft solids or mixtures where particles can flow.
A boiler is a closed vessel in which fluid is heated. The fluid does not necessarily boil. The heated or vaporized fluid exits the boiler for use in various processes or heating applications, including water heating, central heating, boiler-based power generation, cooking, and sanitation.
Heat transfer is a discipline of thermal engineering that concerns the generation, use, conversion, and exchange of thermal energy (heat) between physical systems. Heat transfer is classified into various mechanisms, such as thermal conduction, thermal convection, thermal radiation, and transfer of energy by phase changes. Engineers also consider the transfer of mass of differing chemical species, either cold or hot, to achieve heat transfer. While these mechanisms have distinct characteristics, they often occur simultaneously in the same system.
A chimney is an architectural ventilation structure made of masonry, clay or metal that isolates hot toxic exhaust gases or smoke produced by a boiler, stove, furnace, incinerator, or fireplace from human living areas. Chimneys are typically vertical, or as near as possible to vertical, to ensure that the gases flow smoothly, drawing air into the combustion in what is known as the stack, or chimney effect. The space inside a chimney is called the flue. Chimneys are adjacent to large industrial refineries, fossil fuel combustion facilities or part of buildings, steam locomotives and ships.
Ventilation is the intentional introduction of outdoor air into a space. Ventilation is mainly used to control indoor air quality by diluting and displacing indoor pollutants; it can also be used to control indoor temperature, humidity, and air motion to benefit thermal comfort, satisfaction with other aspects of the indoor environment, or other objectives.
A solar chimney – often referred to as a thermal chimney – is a way of improving the natural ventilation of buildings by using convection of air heated by passive solar energy. A simple description of a solar chimney is that of a vertical shaft utilizing solar energy to enhance the natural stack ventilation through a building.
Mound-building termites are a group of termite species that live in mounds which are made of a combination of soil, termite saliva and dung. These termites live in Africa, Australia and South America. The mounds sometimes have a diameter of 30 metres (98 ft). Most of the mounds are in well-drained areas. Termite mounds usually outlive the colonies themselves. If the inner tunnels of the nest are exposed it is usually dead. Sometimes other colonies, of the same or different species, occupy a mound after the original builders' deaths.
A windcatcher, wind tower, or wind scoop is a traditional architectural element, originated in Iran (Persia), used to create cross ventilation and passive cooling in buildings. Windcatchers come in various designs, depending on whether local prevailing winds are unidirectional, bidirectional, or multidirectional, on how they change with altitude, on the daily temperature cycle, on humidity, and on how much dust needs to be removed. Despite the name, windcatchers can also function without wind.
A thermal power station is a type of power station in which heat energy is converted to electrical energy. In a steam-generating cycle heat is used to boil water in a large pressure vessel to produce high-pressure steam, which drives a steam turbine connected to an electrical generator. The low-pressure exhaust from the turbine enters a steam condenser where it is cooled to produce hot condensate which is recycled to the heating process to generate more high pressure steam. This is known as a Rankine cycle.
A flue is a duct, pipe, or opening in a chimney for conveying exhaust gases from a fireplace, furnace, water heater, boiler, or generator to the outdoors. Historically the term flue meant the chimney itself. In the United States, they are also known as vents for boilers and as breeching for water heaters and modern furnaces. They usually operate by buoyancy, also known as the stack effect, or the combustion products may be "induced" via a blower. As combustion products contain carbon monoxide and other dangerous compounds, proper "draft", and admission of replacement air is imperative. Building codes, and other standards, regulate their materials, design, and installation.
In a water boiler, draft is the difference between atmospheric pressure and the pressure existing in the furnace or flue gas passage. Draft can also be referred to as the difference in pressure in the combustion chamber area which results in the motion of the flue gases and the air flow.
Economizers, or economisers (UK), are mechanical devices intended to reduce energy consumption, or to perform useful function such as preheating a fluid. The term economizer is used for other purposes as well. Boiler, power plant, heating, refrigeration, ventilating, and air conditioning (HVAC) uses are discussed in this article. In simple terms, an economizer is a heat exchanger.
A flue-gas stack, also known as a smoke stack, chimney stack or simply as a stack, is a type of chimney, a vertical pipe, channel or similar structure through which combustion product gases called flue gases are exhausted to the outside air. Flue gases are produced when coal, oil, natural gas, wood or any other fuel is combusted in an industrial furnace, a power plant's steam-generating boiler, or other large combustion device. Flue gas is usually composed of carbon dioxide (CO2) and water vapor, as well as nitrogen and excess oxygen remaining from the intake combustion air. It also contains a small percentage of pollutants such as particulate matter, carbon monoxide, nitrogen oxides and sulfur oxides. The flue gas stacks are often quite tall, up to 420 metres (1,380 ft), to increase the stack effect and dispersion of pollutants.
Passive ventilation is the process of supplying air to and removing air from an indoor space without using mechanical systems. It refers to the flow of external air to an indoor space as a result of pressure differences arising from natural forces.
A boiler or steam generator is a device used to create steam by applying heat energy to water. Although the definitions are somewhat flexible, it can be said that older steam generators were commonly termed boilers and worked at low to medium pressure but, at pressures above this, it is more usual to speak of a steam generator.
A wood-burning stove is a heating or cooking appliance capable of burning wood fuel, often called solid fuel, and wood-derived biomass fuel, such as sawdust bricks. Generally the appliance consists of a solid metal closed firebox, often lined by fire brick, and one or more air controls. The first wood-burning stove was patented in Strasbourg in 1557. This was two centuries before the Industrial Revolution, so iron was still prohibitively expensive. The first wood-burning stoves were high-end consumer items and only gradually became used widely.
Underfloor air distribution (UFAD) is an air distribution strategy for providing ventilation and space conditioning in buildings as part of the design of a HVAC system. UFAD systems use an underfloor supply plenum located between the structural concrete slab and a raised floor system to supply conditioned air to supply outlets, located at or near floor level within the occupied space. Air returns from the room at ceiling level or the maximum allowable height above the occupied zone.
Interstitial condensation is a type of condensation that may occur within an enclosed wall, roof or floor cavity structure, which can create dampening.
Airflow, or air flow, is the movement of air. The primary cause of airflow is the existence of air. Air behaves in a fluid manner, meaning particles naturally flow from areas of higher pressure to those where the pressure is lower. Atmospheric air pressure is directly related to altitude, temperature, and composition.
Cross ventilation is a natural phenomenon where wind, fresh air or a breeze enters upon an opening, such as a window, and flows directly through the space and exits through an opening on the opposite side of the building. This produces a cool stream of air and as well as a current across the room from the exposed area to the sheltered area.