Minimum efficiency reporting value

Last updated

Minimum Efficiency Reporting Value, commonly known as MERV, is a measurement scale designed in 1987 by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) to report the effectiveness of air filters in more detail than other ratings. For example, often a HEPA filter is impractical in residential central HVAC systems due to the large pressure drop the dense filter material causes. Experiments indicate that less obstructive, medium-efficiency filters of MERV 7 to 13 are almost as effective as true HEPA filters at removing allergens within residential air handling units. [1]

Contents

The scale is designed to represent the worst-case performance of a filter when dealing with particles in the range of 0.3 to 10 micrometers. The MERV value is from 1 to 16; higher MERV values correspond to a greater percentage of particles captured on each pass. A MERV 16 filter is able to capture more than 95% of particles over the full range.

The table displayed below is a grouping of MERV values by particle size:

MERVMinimum particle sizeTypical controlled contaminant [1] Typical application [1]
1–4> 10.0 μmPollen, dust mites, cockroach debris, sanding dust, spray paint dust, textile fibers, carpet fibersResidential window A-C units
5–8 [2] 10.0–3.0 μm ("E3")Mold spores, dust mite debris, cat and dog dander, hair spray, fabric protector, dusting aids, pudding mixBetter residential, general commercial, industrial workspaces
9–123.0–1.0 μm ("E2")Legionella, humidifier dust, lead dust, milled flour, auto emission particulates, nebulizer dropletsSuperior residential, better commercial, hospital laboratories
13–161.0–0.3 μm ("E1")Bacteria, droplet nuclei (sneeze), cooking oil, most smoke and insecticide dust, most face powder, most paint pigmentsHospital and
general surgery

While the lowest MERV value in each row has no minimum requirement for filtering the particle size for that row, it does have stricter requirements for all larger particle sizes than any lower MERV value. For example, MERV 13 has no minimum requirement for removing 0.3–1.0 μm particles (the standard specifies <75%) but has higher minimum requirements for removing 1.0–3.0 μm, 3.0–10.0 μm, and > 10 μm particles than MERV 12 and all lower MERV values. All other MERV values on each row do have minimum removal percentages for that row's particle size. [1]

Similar scales

Two proprietary scales are used to rate sub-HEPA air filters.

The Home Depot scale is known as filter performance rating (FPR), and is reduced from a 1–10 scale to only 4, 7, 9, and 10. It measures ability to capture large particles, small particles, and weight change over the lifetime of the filter. [3]

The 3M scale is known as microparticle performance rating (MPR) and measures the ability to filter particles 0.3 to 1 microns. [4]

Although the standards measure slightly different attributes and thus, are not strictly convertible, one retailer reported the following typical equivalents. [4]

MERVFPRMPR
6(below lowest rating)300
85600
1171000-1200
13101500-1900

See also

Related Research Articles

<span class="mw-page-title-main">Heating, ventilation, and air conditioning</span> Technology of indoor and vehicular environmental comfort

Heating, ventilation, and air conditioning (HVAC) is the use of various technologies to control the temperature, humidity, and purity of the air in an enclosed space. Its goal is to provide thermal comfort and acceptable indoor air quality. HVAC system design is a subdiscipline of mechanical engineering, based on the principles of thermodynamics, fluid mechanics, and heat transfer. "Refrigeration" is sometimes added to the field's abbreviation as HVAC&R or HVACR, or "ventilation" is dropped, as in HACR.

<span class="mw-page-title-main">Cleanroom</span> Dust-free room for research or production

A cleanroom or clean room is an engineered space, which maintains a very low concentration of airborne particulates. It is well isolated, well-controlled from contamination, and actively cleansed. Such rooms are commonly needed for scientific research, and in industrial production for all nanoscale processes, such as semiconductor manufacturing. A cleanroom is designed to keep everything from dust, to airborne organisms, or vaporised particles, away from it, and so from whatever material is being handled inside it.

<span class="mw-page-title-main">HEPA</span> Efficiency standard of air filters

HEPA filter, also known as high-efficiency particulate absorbing filter and high-efficiency particulate arrestance filter, is an efficiency standard of air filters.

<span class="mw-page-title-main">Air purifier</span> Device which removes contaminants from the air in a room

An air purifier or air cleaner is a device which removes contaminants from the air in a room to improve indoor air quality. These devices are commonly marketed as being beneficial to allergy sufferers and asthmatics, and at reducing or eliminating second-hand tobacco smoke.

<span class="mw-page-title-main">Air filter</span> Device composed of fibrous or porous materials which removes solid particulates from the air

A particulate air filter is a device composed of fibrous, or porous materials which removes solid particulates such as dust, pollen, mold, and bacteria from the air. Filters containing an adsorbent or catalyst such as charcoal (carbon) may also remove odors and gaseous pollutants such as volatile organic compounds or ozone. Air filters are used in applications where air quality is important, notably in building ventilation systems and in engines.

ULPA is an acronym for "Ultra-low Penetration Air (filter)". A ULPA filter can remove from the air at least 99.999% of dust, pollen, mold, bacteria and any airborne particles with a minimum particle penetration size of 120 nanometres. A ULPA filter can remove – oil smoke, tobacco smoke, rosin smoke, smog, insecticide dust.

Carbon filtering is a method of filtering that uses a bed of activated carbon to remove impurities from a fluid using adsorption.

<span class="mw-page-title-main">Dust collector</span>

A dust collector is a system used to enhance the quality of air released from industrial and commercial processes by collecting dust and other impurities from air or gas. Designed to handle high-volume dust loads, a dust collector system consists of a blower, dust filter, a filter-cleaning system, and a dust receptacle or dust removal system. It is distinguished from air purifiers, which use disposable filters to remove dust.

Sedimentation is a physical water treatment process using gravity to remove suspended solids from water. Solid particles entrained by the turbulence of moving water may be removed naturally by sedimentation in the still water of lakes and oceans. Settling basins are ponds constructed for the purpose of removing entrained solids by sedimentation. Clarifiers are tanks built with mechanical means for continuous removal of solids being deposited by sedimentation. Clarification does not remove dissolved species. Sedimentation is the act of depositing sediment.

A hypoallergenic vacuum cleaner is a vacuum cleaner with filters designed to retain the vast majority of particles within the vacuum system. If successful this retention would greatly reduce the amount of potential allergens in the environment in which it is used. Regular vacuum cleaners are unable to retain most very fine dust and many allergens which simply are too small for the system to trap and are released from the system along with the exhaust air.

<span class="mw-page-title-main">Biosafety cabinet</span> Type of laboratory equipment

A biosafety cabinet (BSC)—also called a biological safety cabinet or microbiological safety cabinet—is an enclosed, ventilated laboratory workspace for safely working with materials contaminated with pathogens requiring a defined biosafety level. Several different types of BSC exist, differentiated by the degree of biocontainment they provide. BSCs first became commercially available in 1950.

ANSI/ASHRAE/IES Standard 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings is an American National Standards Institute (ANSI) standard published by ASHRAE and jointly sponsored by the Illuminating Engineering Society (IES) that provides minimum requirements for energy efficient designs for buildings except for low-rise residential buildings. The original standard, ASHRAE 90, was published in 1975. There have been multiple editions to it since. In 1999 the ASHRAE Board of Directors voted to place the standard on continuous maintenance, based on rapid changes in energy technology and energy prices. This allows it to be updated multiple times in a year. The standard was renamed ASHRAE 90.1 in 2001. It has since been updated in 2004, 2007, 2010, 2013, 2016, and 2019 to reflect newer and more efficient technologies.

<span class="mw-page-title-main">Clean air delivery rate</span> Filtration efficacy measurement

The clean air delivery rate (CADR) is a figure of merit that is the cubic feet per minute (CFM) of air that has had all the particles of a given size distribution removed. For air filters that have air flowing through them, it is the fraction of particles that have been removed from the air, multiplied by the air flow rate through the device. More precisely, it is the CFM of air in a 1,008-cubic-foot (28.5 m3) room that has had all the particles of a given size distribution removed from the air, over and above the rate at which the particles are naturally falling out of the air. Different filters have different abilities to remove different particle distributions, so three CADR's for a given device are typically measured: smoke, pollen, and dust. By combining the amount of airflow and particle removal efficiency, consumers are less likely to be misled by a high efficiency filter that is filtering a small amount of air, or by a high volume of air that is not being filtered very well.

<span class="mw-page-title-main">Fan filter unit</span>

A fan filter unit (FFU) is a type of motorized air filtering equipment. It is used to supply purified air to cleanrooms, laboratories, medical facilities or microenvironments by removing harmful airborne particles from recirculating air. The units are installed within the system's ceiling or floor grid. Large cleanrooms require a proportionally large number of FFUs, which in some cases may range from several hundred to several thousand. Units often contain their own pre-filter, HEPA filter and internally controllable fan air distribution.

The Microparticle Performance Rating (MPR) is an Air filter rating system created by the company 3M. It rates the ability of an air filter to filter out micro particles.

<span class="mw-page-title-main">NIOSH air filtration rating</span> U.S. rating of respirators such as face masks

The NIOSH air filtration rating is the U.S. National Institute for Occupational Safety and Health (NIOSH)'s classification of filtering respirators. The ratings describe the ability of the device to protect the wearer from solid and liquid particulates in the air. The certification and approval process for respiratory protective devices is governed by Part 84 of Title 42 of the Code of Federal Regulations. Respiratory protective devices so classified include air-purifying respirators (APR) such as filtering facepiece respirators and chemical protective cartridges that have incorporated particulate filter elements.

<span class="mw-page-title-main">Moisture removal efficiency</span>

Moisture Removal Efficiency (MRE) is a measure of the energy efficiency of any dehumidification process. Moisture removal efficiency is the water vapor removed from air at a defined inlet air temperature and humidity, divided by the total energy consumed by the dehumidification equipment during the same time period, including all fan and pump energy needed to move air and fluids through the system.

Air filtration guidelines for operating rooms are determined by the American Society of Heating, Refrigerating and Air-Conditioning Engineers (ASHRAE) using a standard known as Minimum Efficiency Reporting Value (MERV). MERV is determined based on the size of particles successfully removed from the air and is used to classify the efficiency of HEPA filters. Ratings range from 1-16 and efficiency increases as the rating increases. ASHRAE groups surgeries into three categories: minor surgical procedures (A); minor or major surgical procedures performed with minor sedation (B); and major surgical procedures performed with general anesthesia or regional block anesthesia (C). Each surgical category is given a minimum MERV rating it must comply with.

<span class="mw-page-title-main">Mechanical filter (respirator)</span> Air-filtering face masks or mask attachments

Mechanical filters are a class of filter for air-purifying respirators that mechanically stops particulates from reaching the wearer's nose and mouth. They come in multiple physical forms.

<span class="mw-page-title-main">Corsi–Rosenthal Box</span> Air purifier design

The Corsi–Rosenthal Box, also called Corsi–Rosenthal Cube, is a design for a do-it-yourself air purifier that can be built comparatively inexpensively. It was designed during the COVID-19 pandemic, with the goal of reducing the levels of airborne viral particles in indoor settings. It consists of five HVAC particulate air filters and a box fan.

References

  1. 1 2 3 4 "Residential Air Cleaners (2nd Edition): A Summary of Available Information" (PDF). EPA. Archived from the original on February 1, 2013. Retrieved 2012-08-20.{{cite web}}: CS1 maint: unfit URL (link)
  2. ANSI/ASHRAE Standard 62.1-2007 requires a filter of at least MERV 6 efficiency for residential applications in the U.S.
  3. Best Air Filters for Your Home
  4. 1 2 MERV vs. MPR vs. FPR Rating Systems